Drain Water Lift-Up Kit
Installation Manual
This installation manual contains only the description of how to install the Drain water Lift-Up Kit PAC-KE05DM-F. For information about how to
wire and how to install air conditioning units, see the installation manual for them.
For your safety, first be sure to read " 1 Safety Precautions " described below thoroughly and then install the Drain water Lift-Up Kit PAC-
KE05DM-F correctly.
1 Safety Precautions
● The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
WARNING
This symbol denotes what could lead to serious injury or death if your misuse the PAC-KE05DM-F.
CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAC-KE05DM-F.
● After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
When someone moves, repairs or uses the PAC-KE05DM-F, make sure that this manual is forwarded to the final user.
Always have the unit installed by Authorized Mitsubishi
Representative or similar professional.
Improper installation by the user could result in problems such as
water leakage, electric shock or fire.
Always use the designated cables and connect them properly.
When connecting the terminals, make sure that external forces
from the cable is not being conveyed to the terminal and then
tighten it securely.
Improper or loose connections could cause excessive heat or fire.
Only use Mitsubishi-approved accessories, such as an air
cleaner, humidifier or electric heater.
Always have such accessories installed by an Authorized Mitsubishi
Representative or similar professional. Improper installation by the
user may result in water leakage, electric shock or fire.
PRECAUTIONS BEFORE INSTALLATION
Never use for special applications such as storing food, plants,
precision equipment or art.
The quality of these items may deteriorate.
Never use the unit in special environments.
Special environments with high concentrations of oil, steam or
sulfuric gases will reduce the performance of the air condition and
cause its parts to deteriorate.
Never install the unit where run-off could result in damage.
If the humidity in the room exceeds 80% or if the drain becomes
clogged, water may drain off of the indoor unit. When the unit is
used for heating, there may be drainage from the outdoor unit. If
required, provide collector drain for the outdoor unit.
PRECAUTIONS BEFORE REMOVE AND ELECTRIC WORK
Route wiring so that there is no tension.
Tension could cause the wire to break and this could result in
excessive heat or fire.
Dispose of packing materials properly.
PRECAUTIONS BEFORE TEST RUN
Never touch the switch with wet hands.
Electric shock could occur.
Never operate the air conditioner with the panel or guard
removed.
The hand could come in contact with rotating, hot or high-pressure
components. They could cause electrical shock or entanglement.
PAC-KE05DM-F
WARNING
Install the unit according to this Installation Manual.
If the unit is installed improperly, water leakage, electric shock or
fire may result.
Have all electric work performed by a properly licensed
electrician. Electric work should be performed in strict
adherence to procedures to this Installation Manual. Always
provide a dedicated power supply.
If the capacity of the power supply is inadequate, it could result in
problems such electric shock or fire.
Never modify the unit and always have repairs performed by an
Authorized Mitsubishi Representative.
Improper repair could result in problems such water leakage,
electric shock or fire.
CAUTION
Always provide adequate signal noise protection when
installing in facilities such as hospitals and communication
stations.
Equipment at these facilities, such as inverters, in-house generators,
high-frequency medical equipment, two-way communication
equipment, may cause the air conditioner to operate improperly.
Conversely, the signal noise from the air conditioner may affect
the operation of medical equipment and two-way communication
equipment and this could interfere with the medical treatment being
given a patient or cause disturbances or interference in video
broadcasting equipment.
Use care when transporting the unit.
•Always use two or more people for lifting a product weight 20 kg.
or more.
•Some products are packaged with plastic wrapping bands.
Never use these for lifting or transporting the product.
•Never touch the fins on the heat exchanger. They are sharp and
could cause cuts.
•Never allow children to play with the plastic bags used for
packaging. Always tear them up when disposing. A child could
suffocate in these bags.
Never operate the air conditioner with the air filter removed.
Particles will enter into the air conditioner and cause damage.
Never turn off the power supply immediately after stopping the unit.
Wait five minutes or more before turning off the power supply.
Turning off the power supply before that time could result in water
leakage or damage.

Advertisement

loading

Summary of Contents for Mitsubishi Electric PAC-KE05DM-F

  • Page 1 PAC-KE05DM-F Installation Manual This installation manual contains only the description of how to install the Drain water Lift-Up Kit PAC-KE05DM-F. For information about how to wire and how to install air conditioning units, see the installation manual for them. For your safety, first be sure to read “ 1 Safety Precautions “ described below thoroughly and then install the Drain water Lift-Up Kit PAC- KE05DM-F correctly.
  • Page 2 2 Confirming the Supplied Parts 1. Model names and applicable models Model name Applicable types PEFY-P200VMHS-E, PEFY-P250VMHS-E PAC-KE05DM-F PEFY-P72NMHSU-E, PEFY-P96NMHSU-E 2. Provided parts Check that the packet includes the following parts in addition to this installation manual. PARTS 1DRAIN PUMP ASSY.
  • Page 3 3 Attach the Drain Pump The drain pump must be attached before installation of the indoor unit. 3-1 Preparation for the indoor unit Fixing screw Control box cover (1) Remove the fixing screws (5 locations) shown Photo 3-1, and remove the control box cover and the wire cover. Fixing screws Wire cover Photo 3-1...
  • Page 4 3-2. Attach the drain pump (1) Attach the drain pump 1 and drain socket as shown in Photo 3-4 using Drain pump assy 1 Drain socket four PTT screws 6. * When attaching the drain socket, make sure that drain hose is straight.
  • Page 5 4 Wiring 2-wire cord 4-1. Passing the pump wires (Photo 4-1) From drain pump a) Pass the 2-wire cord (with a blue connector) through the hole 2-wire cord shown in the photo. From float switch b) Pass the 2-wire cord (with a white connector) through the pipe sensor and LEV lead wire hole.
  • Page 6: Drain Piping Work

    5 Drain piping work Be sure to wind commercially available insulating material (with a form polyethylene's specific gravity of 0.03 and thickness given below) onto all pipes which pass through rooms. 1 Select the thickness of insulating material by pipe size. Pipe size Insulating material's thickness . mm to . mm...
  • Page 7 Take the following steps to install the drain hose. 1. Insert the drain hose (supplied with the indoor unit) into the drain port. (The drain hose must not be bent more than 45° to prevent the hose from breaking or clogging.) 2.
  • Page 8: Confirming Drain Discharge

    6 Confirming drain discharge Make sure that the Drain Water Lift-Up Kit operates normally for discharge and that there is no water leakage from the connections. •Be sure to confirm the above in a period of heating operation. •Be sure to confirm the above before ceiling work is done in the case of a new construction. •Before pouring water, be sure to confirm again the rubber plug is pushed in straight all the way.