2 FEATURES AND SPECIFICATIONS The EMB HubLite data acquisition system is designed to allow owners and managers of commercial and industrial facilities with a cost effective means of gathering crucial information in a timely manner. To meet these requirements, the EMB HubLite system provides the installer with all the tools necessary to install and configure the hard ware and software with a minimum of time and investment.
IP address and Netmask (check with system administrator) • Gateway address (check with system administrator) • DNS HUBLite address (check with system administrator) • HTTP Proxy address (optional), may be required if the EMB HubLite is behind a firewall (check with system administrator)
Unpack materials: Remove all materials from shipping box and verify all required components are available. 4.1.2 Mount the EMB HubLite on the wall, panel or other appropriate location. 4.1.3 Attach pulse output devices to the pulse inputs on the A7810. For dry contact.
Page 8
24VDC. After power is applied, the green “Alive” light in the upper right of the EMB HubLite should come on and the LCD display will display a series of diagnostic screens ending with the following message on the LCD display (this boot sequence may require up to 20 seconds to complete): This indicates that the EMB HubLite has loaded properly and is ready for configuration and connection...
• Dynamic Host Configuration Protocol (DHCP) address this process assigns an IP address dynamically to the EMB HubLite when it is connected to the network from a host DHCP HUBLite; or • Direct connection between the EMB HubLite and a single temporary computer such as a laptop.
Page 10
“(Previous Menu)” option after step B above. The menu will then state that the EMB HubLite must be rebooted to take effect. Press the Select button to allow the EMB HubLite to reboot. Once the EMB HubLite has rebooted, the new IP address will be displayed on the console. If DHCP addressing was specified, the HUBLite assigned address will be displayed.
Page 11
The remainder of this section will assume the installer has brought a laptop to the site, and will connect the laptop to the building LAN, or directly to the EMB HubLite . Attach the laptop to the EMB HubLite or LAN as shown in figure 6, ethernet hookup.
Page 12
Note: If you have multiple ethernet cards, you may have multiple lines labeled “TCP/IP ----> Ethernet card”. Locate the ethernet card that corresponds to the physical connection to the EMB HubLite and then select the TCP/IP option that is linked with that ethernet card. 5.3.3 Double click the TCP/IP option you selected in step 5.3.2.
Select the Modbus/Setup menu option. Specify the Modbus Loop Name. This will become the name of the EMB HubLite. This is the name that will appear on the BMO website service (if subscribed). Specify the data logging period. The default is 15 minutes.
Page 14
6.7.5 When configuring the EMB HubLite to send data to the BMO site or your own data collection HUBLite , the EMB HubLite will authenticate itself with the HUBLite by using the serial number and a password. This password must be supplied here, and can be obtained when you subscribe for the BMO service, or by your database administrator.
The EMB HubLite has three levels of security. These are “operator”, “user” and “admin”. When using a browser to access the EMB HubLite , basic http authentication is used to prompt your browser for a username and password. The admin account uses “admin” as the default password. To change the password, select the Accounts menu from the left side tree display.
Click on the Modbus address number for any of the devices for specific device details. NOTE: not all Modbus devices have built in driver support in the EMB HubLite . If a device appears in the list with “Unknown” in the status column, you may need to upgrade the firmware on the EMB HubLite to access the device.
Page 17
Modbus/TCP connected device. See the section on manually adding a device below. Troubleshoot: The EMB HubLite will review the devices connected and offer suggestions about any problems found.
Page 18
8 MODBUS 8.3 Device Details The device detail page will show a list of all the pulse input data points, alarm settings and console options. The data point names for most devices are automatically entered. At the top of the page, the status of the device is shown.
Page 19
Alarm, or above the High Alarm levels at the time a log entry is taken, the point will be considered in an alarm state. Console: Checking this checkbox will cause the EMB HubLite to display this data point on the LCD console. Multiple data points are rotated about every 10 seconds. The values on the LCD console are updated when the next log interval occurs.
Page 20
Device Type: This menu will allow the selection of any built in driver or any Modbus Framework template that is available on the EMB HubLite. It is important to select the driver or template that matches the Modbus device.
Page 21
The Modbus setup page provides several options related to the Modbus RS485 serial port. EMB HubLite Name: This is the name of the EMB HubLite. This name will be present on all log file descriptors when uploaded to a central database website such as BMO. It is helpful to name the EMB HubLite based on the physical location of the system, or building.
Page 22
The trap includes information about the EMB HubLite system data point, and alarm state. A full MIB is located on the EMB HubLite , click the MIB link to the right of this option.
Modbus/TCP gateway. If a ModHopper is connected in such a way, the wireless diagnostics options will be present in the EMB HubLite . Please refer to the A8812 or A8810 user manuals for further details on the wireless diagnostic features.
(MSIE/Tools/Connections tab/LAN Settings) then you most likely don’t need to configure the EMB HubLite to use a proxy. If in doubt, leave this blank first, and try the connection test. If it fails, ask your LAN administrator about proxy HubLites, if any.
Page 25
EMB HubLite. NOTE: one common mistake is configuring the Laptop IP to the same address as the IP address of the EMB HubLite. In order for the laptop and EMB HubLite to communicate, the IP addresses should not be identical. (See the basic network config for suggested IP addresses.) •...
11.3 Date and Time The EMB HubLite keeps time using UTC or Universal time. All log files are recorded in UTC time as well. Timestamps shown on the EMB HubLite local configuration pages are converted to local time for the convenience of the installer.
Page 27
If you store data in local time, you will have the following issues. Local time is relative. Is Local the time where the EMB HubLite exists, or local to where the data is stored? If local to the EMB HubLite, you must shift each EMB HubLite data set depending on its location.
Page 28
This is updated ever time the modem makes a dialin or dialout connection. Time Change Log: This log contains a list of time change events. When the EMB HubLite system clock is changed either manually or by automated time sync, and the change is more than a few seconds, the event is recorded here.
Traceroute: Send an echo request to the target address and attempt to locate every router in between the EMB HubLite and that address. Nslookup: convert the DNS name to an IP address, useful for testing the functionality of the DNS server configured in the Network/Setup webpage.
The EMB HubLite has an LCD console and two push buttons labeled “menu” and “select”. These can be used to configure some of the basic features of the EMB HubLite. The intended purpose of the console is to configure the EMB HubLite to a point where a computer can communicate with it for further detailed configuration.
Page 31
Note: selecting the modbus status option from the EMB HubLite console does not cause the EMB HubLite to search for new devices. The EMB HubLite checks for new devices in the background all the time, taking about 2.5 minutes to complete each pass through all 255 possible addresses. Complete each pass through all 255 possible addresses.
Log File Format Once you have downloaded the data from the EMB HubLite, you will need to process it. The file is an ASCII text file with comma delimited data. One line is recorded for each log cycle. The file will look something like the following example from a 4A4P-M I/O Module.
Page 33
This is because the 9600 baud speed of the Modbus loop is not fast enough to log all Modbus devices in less than 1 second. If a device does not respond during a log cycle, the EMB HubLite will attempt to query the device several more times.
Page 34
For data exported from the BMO website, the columns that are invalid (NULL) are reported as blank fields. This makes it easier to import into MS Excel as blank cells. With the current firmware, the EMB HubLite will report blank fields rather than “NULL” to make direct import of data from the EMB HubLite easier, as well as reduce the file size.
Page 35
files to your server, you must manually delete them. To delete log files, refer to the FTP method of downloading log files. One step detailed in the FTP section is how to delete a log file from the EMB HubLite.
Page 36
If all retries fail, the EMB HubLite will wait until the next scheduled upload time before trying again. • Time to wait before retry: In the event of a failure, the EMB HubLite can be configured to wait for a specified period of time before attempting another connection. This option specifies how long to wait before retrying.
HTTP Direct from the EMB HubLite The EMB HubLite has the ability to export log file data to a web browser directly from the setup web pages. To use this feature, access the EMB HubLite setup menu with your web browser. Select the “Log File Export”...
Page 38
HubLite will automatically remove log files from its flash memory once the EMB HubLite has confirmed that the file was received by the database HubLite. If you are using the EMB HubLite with a standalone mode, you can use FTP or Enertrax DL to delete log files from the flash memory.
Page 39
The URL for the page will be shown on that dialog. Simply copy/paste this URL into your link. The EMB HubLite can provide Modbus device data in XML format. This feature, coupled with browser based AJAX (Javascript) can provide a very powerful tool to allow the creation of custom web pages.
16 MECHANICAL DRAWINGS The EMB HubLite uses a plastic enclosure that is approximately 4 in x 4.25 in x 2 in deep. The EMB HubLite has 4 mounting holes for use with a #6 screw. The drawing above shows the relative...
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option.