Beok Controls TDS23M Manual

Beok Controls TDS23M Manual

Lcd screen thermostat

Advertisement

TDS23M LCD SCREEN THERMOSTAT
I. Product Summary:
TDS23M series thermostats are luxurious programmable thermostat with
square screen display.It is applied to temperature control of industrial,
commercial and domestic room, and start of control heating appliance,
especially used in the floor heating systems.
II. Technical Parameter:
Power Supply
Current Load
Power Consumption
External Material
Sensing Element
Set Temp. Range
Floor Set Temp. Range
Accuracy
Dimension
Ambient Temp.
Storage Temp.
Timing Error
Mod-bus
III. Main Functions and Characteristics
1.Popular square LCD screen display with blue backlight.
2.Power-off memory function.
3.Real-time data save function.
. 4 5+2 or 6+1or 7days six periods program schedule.
5.Selectable 80mmx80mm European hidden box.
6.Precise comfort control keeps temperature within1°C of the level you set.
7.With Rs485 communication
IV. User Interface Explanation
V. Model Definition
WP: For Water Heating System, 3A
EP: For Electric Floor Heating System, 16A
For example: TDS23M-EP
VI. Model Spec
TDS23M-EP
TDS23M-WP
200 ~ 240V 50 ~60Hz
≤3A(water heating)
≤16A(electric heating)
<0.3W
PC+ABS (flame retardant)
NTC
5-60℃
5-99℃
±1℃
86x86x13.3mm
0-45℃,5-95%RH(Non-condensing)
-5~55
<1%
Rs485
TDS23M-WP
Modbus
Memory
Function
Function
Optional
Optional
VII.Wiring Digram
TDS23M-EP
VIII. Operation Instruction
1. Setting Power on/off
Press
to turn on/off the power.
2. Setting Temperature
Press
to set the temperature.
3. Setting the Clock
Press
to set minute, hour and week.
Press
for adjusting.
4. Setting the Manual Mode.
Manual mode means non-programmable mode.
Press
then
will display in the screen, it is in manual mode.
Press
to set the temperature.
Press
to set minute, hour and week.
5. Setting the Child Lock
Long press
to enter into child lock mode,
Long press
again, the child lock will be disappeared.
6. Setting the Programmable Mode.
Press and hold
into programmable mode. LooP and 12345 will display.
Press
to select the control way: 5+2 or 6+1 or 7 days programmable.
12345 display in the position of week means 5+2;
123456 display in the position of week means 6+1;
1234567 display in the position of week means 7 days programmable.
Press
to select the periods.
Press
to change the temperature;
Press
to do time adjustment.
Press
to change the time;
Press
again to select the weekend's temp.
If you want to make temporary adjustment in any period,
press
then
will flash. When finish the setting, all will confirm
automatically.
Press
to switch operation between manual mode and programmable
mode.
Period
Period Icon Defaulted Time Defaulted Temp.
1
2
3
Week
4
5
6
1
Weekend
2
Remark:
(1) The defaulted temperature of period3 and period4 is the same as
period2. Please change it according to the request.
(2) When setting temperature is 00, this period is power off.
(3) How to check floor temp?
During power on, press and hold
check floor temp.. OUT TEMP will display.
Press
again to display room temp..
TDS23M-WP
will display.
6:00
20℃
8:00
15℃
11:30
15℃
12:30
15℃
17:30
22℃
22:00
15℃
8:00
22℃
23:00
15℃
then press the button of power to

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TDS23M and is the answer not in the manual?

Questions and answers

Summary of Contents for Beok Controls TDS23M

  • Page 1 VII.Wiring Digram TDS23M-EP TDS23M-WP I. Product Summary: TDS23M series thermostats are luxurious programmable thermostat with VIII. Operation Instruction square screen display.It is applied to temperature control of industrial, commercial and domestic room, and start of control heating appliance, 1. Setting Power on/off especially used in the floor heating systems.
  • Page 2 6. Advanced Setting 8, Floor temperature measurement, register address 07: Floor temperature measurement (low byte), data range : 0-199, relative temperature 0-99.5degree. In the state of power-off, long press and hold then press into advanced settingmode. Then press to set relative item. 9, Time_ Hour, Time_Minute, register address 08: Hour (high byte), data range 0-23, 24 hours;...
  • Page 3 Please read this manual for complete instructions on installing and operating your thermostat. If you require further assistance, please feel free to contact us. LCD Screen Thermostat TDS23M In the box you will find: Model TDS23M-EP TDS23M-WP √ √ Thermostat √ √ User Manual √...

Table of Contents

Save PDF