9
Messages
Enter the item No. to display the desired message(s). Pressing
you to the main menu.
1
General messages
Display general device messages.
Press
(OK) to acknowledge.
F4
2
Alarms
Display the current alarm messages. If no alarms are present, the message "No
alarms" is seen.
Press
(OK) to acknowledge.
F4
3
Alarmmask
Display the current alarm mask.
6

"Settings" menu

In this menu you can edit various parameters which are then saved automatically in the
non-voltatile memory of the TZID-C/TZID-C200 positioner.
The following parameters cannot be called up on the communicator:
- Travel counter
- Travel counter limit
- Stroke counter
- Stroke counter limit
- Hysteresis
Moreover, it is not possible to initiate a setpoint jump or configure a user-defined
characteristic curve via the communicator. Use the PC configuration program.
The following parameters are only updated when the communicator is
switched off and on again:
- Tolerance band
- Shut off value
- Setpoint range
- Alarmmask
- Control parameters
- Auto conf mode
The parameters listed on the next pages can be edited via the communicator. Select the
digit to be changed with
decrease the flashing number. You can also enter the new number via the numerical
keys.
42/18-75 EN
or
(selected digit flashes). Press
"Settings" menu
"Settings" menu
(HOME) will return
F3
or
to increase or
7