VERIS INDUSTRIES
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
Wiring ExamplE
CONTROLLER
DI
(Status)
DO
(Relay
Coil)
CONTROL
POWER
Find Quality Products Online at:
CURRENT MONITORING
™
H735
DANGER
NOTICE
CONTACTOR
Fan or Pump
Motor
GlobalTestSupply
www.
INSTALLATION GUIDE
Installer's Specifications
Sensor Power
Insulation Class
Frequency Range
Relay Coil
Relay Contact
Temperature Range
Humidity Range
Amperage Range
Output
Hysteresis
Off-State Leakage
Safety
Do not use the LED status indicators as evidence of applied voltage.
The product design provides for basic insulation only.
quick install
1.
Disconnect and lock out power.
2.
Install the mounting bracket to the back of the electrical enclosure, no closer than
1/2" (12mm) to an uninsulated conductor.
3.
Slide the conductor to be monitored through the sensing hole of the current
switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or
above 135 Amps.
4.
Wire the output connections to the DDC controller or switched load. Note:
Contacts are solid state and work like dry contacts. When the switch is closed, less
than 1 Ω is present. When the switch is open, more than 1 MΩ are present.
5.
Reconnect power.
6.
Calibrate the sensor (see Calibration section).
DimEnsions
Removable/Adjustable Mounting Bracket
0.7" Dia
(19 mm)
0.2" x 0.15"
slot (2x)
.com
735
TM
Induced from monitored current
600VAC rms (UL)
24VAC/DC 10mA
5A@250VAC/DC, 3A@30VDC, 1/6 hp
-15° to 60°C (5° to 140°F)
10-90% RH non-condensing
1-135A continuous
N.O. 0.1A@30VAC/DC, polarity insensitive
10% of setpoint, typical
UL 508, CAT III
0.9"
(23 mm)
3.0"
(75 mm)
2.8"
(68 mm)
1.1"
(27 mm)
3.8"
(95 mm)
4.2"
(106 mm)