NuAire SINGLEPAK SP125 Installation And Maintenance Manual
NuAire SINGLEPAK SP125 Installation And Maintenance Manual

NuAire SINGLEPAK SP125 Installation And Maintenance Manual

In line single fan

Advertisement

SINGLEPAK
In Line Single Fan
Rating plate
Mounting
feet supplied
Fig. 1 General view of fan unit

Introduction

The Singlepak range of In Line singlefans are rectangular in sec-
tion and manufactured in galvanised steel. The fan units and the
matching ancillaries are fitted with circular spigots. Fans are
available with duties up to 0.95m
extract or air input.
Integral backdraught shutters fitted as standard. Access panels
top and bottom simplify installation and maintenance.
Units are supplied complete with heavy gauge steel mounting
feet. Singlepak may be installed at any angle except vertically
blowing downwards and inverted horizontally.
QSP (Quiet Singlepak) unit cases have fire resistant acoustic
lining.
Fan is easily serviced after removal of the access panel. Each
assembly is electrically terminated in a connector box inside the
unit casing. Supply cable enters unit through cable grommet
provided on case side.
The motors have thermal overload protection and sealed for life
bearings. Forward curved centrifugal impellers are fitted.
A matching range of ancillaries including silencers, filters and
heaters is available.
Auto Transformer or Electronic speed controls are available. A
run on timer is avauilable giving automatic operation when
linked to a light switch or similar source.
Handling
Always handle the units carefully to avoid damage and distor-
tion. If mechanical aids are used to lift the unit, spreaders should
be employed and positioned so as to prevent the slings, webbing
etc. making contact with the casing.
Mounting
The method of mounting used is the total responsibility of the
installer.
Note that the unit is supplied with flange holes, see fig. 1. The
mounting feet (supplied) can be attached at any of these points
and the unit may be installed at any angle.
Removable
access panel
Removable
Connection
access panel
terminal box
3
/s. and are suitable for air

Installation

and Maintenance
Nuaire Limited
Western Industrial Estate, Caerphilly,
Mid Glamorgan. CF83 1XH United Kingdom
Telephone 029 2088 5911
Facsimile No. 029 2088 7033
Email: info@nuaire.co.uk
www.nuaire.co.uk
Contents
............................................... 1
...............................................
Testing after Installation ............................ 1
Dimensions ................................................... 2
Motor Details ..............................................
Electrical Diagrams .................................
Maintenance .............................................
Replacement of parts ................................
Certification .................................................
Installation
Units should always be positioned with sufficient space to allow
removal of the access covers and subsequent removal of fan and
motor assemblies etc.
Note: when the unit is mounted horizontally the correct orien-
tation must be observed as indicated by direction labels on the
side of the unit case. Note Do not install the unit inverted.
Speed Controls and
Remote Fan Failure Indicator.
These controls may be mounted onto any firm surface using the
fixing holes provided in the base. Drill and plug the mounting
surface, positioning the control or indicator so that the cover
screws remain accessible. This is particularly important if a bat-
tery of controls is being installed. Fix the unit using suitable
woodscrews (not supplied). For wiring purposes, the control or
indicator cover has knock out slots for cable entry to suit up to
20mm conduit.

Testing after Installation

Ensure that the Singlepak unit and Control / Remote Fan
Failure Indicator, as relevant, are fitted.
Switch on and check that the Singlepak unit runs satisfactorily.
If a NuAire Transformer speed control has been installed check
that the correct speed variation is obtained.
For electronic type speed controls follow the installation set-up
procedure provided with the control.
Switch off. If a Run-on Timer (230 RTIM) is fitted, check that
the fan continues to run.
Time the run-on period, which is adjustable between 5 and 30
minutes nominal.
Timer controls are set at the works to the shortest period.
Leaflet No. 671024
NOVEMBER 2001
Page
1
3
4
6
6
8
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SINGLEPAK SP125 and is the answer not in the manual?

Questions and answers

Summary of Contents for NuAire SINGLEPAK SP125

  • Page 1: Table Of Contents

    Switch on and check that the Singlepak unit runs satisfactorily. be employed and positioned so as to prevent the slings, webbing If a NuAire Transformer speed control has been installed check etc. making contact with the casing. that the correct speed variation is obtained.
  • Page 2: Dimensions

    Installation and Maintenance SINGLEPAK IN LINE FAN Dimensions Mounting Top and bottom panels foot fixing removable for access to positions. internal components. Four angle mounting feet provided with each unit. Ancillaries codes Dimensions & Weights Unit Code Case overall Spigot Unit Code Matching Matching...
  • Page 3: Motor Details

    Watts Electrical Note (See also electrical wiring diagrams) SP125 2040 0.70 0.80 If a NuAire control has been supplied, wire the control to the QSP125 Singlepak unit and also to the mains supply. SP200 1260 0.58 0.80 Refer to the diagrams when wiring to the Singlepak use the QSP200 terminal block provided in the terminal box inside the casing.
  • Page 4: Electrical Diagrams

    Singlepak Heaters Three single phase stages To Heater control circuit (by others) (SH-400) 230v 50Hz 1 ph AC supply Singlepak Heatwers 3 Phase For 3 phase, multi-stage wiring information, please telephone NuAire Technical Sales 02920 858200 Typical stage switching (by others)
  • Page 5 Installation and Maintenance SINGLEPAK IN LINE FAN Singlepak with Electronic speed control types: ESC1-3A ESC1-6A ESC1-10A Fan unit 230v 50Hz 1 ph AC supply Motor Singlepak with Auto transformer speed control types: SPCON-1.5 SPCON-3.5 SPCON-7.5 Fan unit 230v 50Hz 1 ph AC supply Motor Not suitable for use with...
  • Page 6: Maintenance

    Refit the assembly to the unit then replace the access covers. Controls Service If NuAire controls and or remote indicators are fitted, remove the covers and carefully clean out the interiors as necessary. Check for damage. Check security of components. Refit the As a manufacturer NuAire provides you with factory trained access covers.
  • Page 7 NuAire Limited, Western Industrial Estate, Caerphilly, Mid Glamorgan, CF8 1XH. United Kingdom. DECLARATION OF INCORPORATION Telephone: 029 2088 5911 Fax: 029 2088 7033 Email: info@nuaire.co.uk & INFORMATION FOR SAFE www.nuaire.co.uk INSTALLATION, OPERATION & MAINTENANCE NOVEMBER 2000 We declare that the machinery named below is intended to be assembled with other components to constitute a system of machinery.