SPECiAL iNfOrmATiON General information SPECiAL iNfOrmATiON OPErATiON - The appliance may be used by children over General information 8 years of age and persons with reduced The chapters "Special information" and "Operation" are intended physical, sensory or mental capabilities or a for both users and qualified contractors.
OPErATiON Safety Other symbols in this documentation Safety Note Intended use General information is identified by the adjacent symbol. Observe the application limits listed in chapter "Specification / f Read these texts carefully. Data table". The appliance is intended for domestic use. It can be used safely Symbol meaning by untrained persons.
OPErATiON Appliance description Appliance description Material losses During the defrost cycle, the fan is switched OFF and Minimum software versions the heat pump circuit is reversed. The heat required for defrosting is drawn from the buffer cylinder. For opera- The following minimum software versions are necessary for op- tion without a buffer cylinder, observe chapter "Menu / eration of the heat pump: Menu description / SETTINGS / HEATING / STANDARD...
OPErATiON maintenance and care Maintenance and care fault Cause remedy There is a loss of Water drips from the safety Use the inspection port pressure in the valve. to check whether water Material losses heating system. is passing from the safety valve hose into the conden- Only qualified contractors may perform maintenance sate pan.
iNSTALLATiON Safety iNSTALLATiON - Connection set AS-WP 2 Preparation Safety Only a qualified contractor should carry out installation, commis- sioning, maintenance and repair of the appliance. General safety instructions We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the appliance are used.
iNSTALLATiON Preparation Safety clearances as required by the safety Installation on a mounting bracket concept Note The safety clearances to the light wells apply to the fol- WARNING Injury lowing mounting brackets: Refrigerant is heavier than air. In the case of leaks, es- - MK 1 mounting bracket caping refrigerant can enter rooms beneath the instal- - T-support SK 1...
iNSTALLATiON Preparation Minimum clearances 9.3.1 Minimum clearances with cascades Note f If the appliance is installed close to light wells, it is ≥1000 ≥500 ≥500 essential that you observed the safety clearances to those light wells (see chapter "Safety clearances as required by the safety concept").
iNSTALLATiON Preparation 9.3.2 Installation in coastal areas f Protect all pipe fixings and external wall ducts with anti-vi- bration insulation. Note When routing the condensate hose, observe chapter "In- stallation / Condensate drain". Siting >500 m f When siting the appliance, observe the air discharge direc- tion.
Page 11
iNSTALLATiON Preparation Installation on foundations MK 1 mounting bracket Note The mounting bracket cannot be used in combination with the connection sets (AS-WP 1 and AS-WP 2). A 100 B 300 C Depth of frost line 1 Heating flow 2 Heating return 3 Condensate drain conduit A Depth of frost line 4 Foundation B 245...
Page 12
iNSTALLATiON Preparation 9.6.2 Installation on strip foundation Note To secure the appliance against toppling over, it can also Strip foundation be fixed to the foundations with screws. f Use the accessories with which the appliance was secured to the transport pallet. f Hook two brackets respectively into the lateral slots on the front and back.
iNSTALLATiON Preparation Buffer cylinders f Observe the structural limits of the T-support used. f See the dimensioned connection drawing for the correct spacing between holes (see chapter "Specification / Dimen- Material losses sions and connections"). A buffer cylinder with diffusion-proof insulation is essen- tial to enable cooling by means of fan convectors.
iNSTALLATiON installation 10. Installation fuse protec- Assignment Cable cross-section tion 1x B 25 A Compressor 2.5 mm² when routing above the surface 4.0 mm² when routing in a wall Note Alternatively: The device is designed in such a way that it can be po- 1x B 16 A Compressor 2.5 mm²...
iNSTALLATiON installation f When sizing the heating circuit, observe the internal pressure the screw cap by hand will secure the pipe in the connector and differential (see chapter "Specification / Data table"). push the O-ring against the pipe to seal it. Making the push-fit connection 10.3 Flow and return connection The connector must be in its relaxed position before the pipe is...
iNSTALLATiON installation 10.5 Oxygen diffusion Note The appliance offers frost protection for the connection Material losses lines in regular operation. Do not use open vented heating systems. Use oxygen In the event of prolonged power failure or when shutting diffusion-proof pipes in underfloor heating systems with down, drain the DHW side of the appliance.
iNSTALLATiON installation 10.7 Condensate drain 10.6.2 Filling the heating system f Fill the heating system via the drain (see chapter "Specifica- A condensate drain connector is factory-fitted to the defrost pan tion / Dimensions and connections"). to enable any condensate to drain off. f After filling the heating system, check the connections for leaks.
iNSTALLATiON Electrical connection 11. Electrical connection Note The leakage current of this appliance can be > 3.5 mA. Note f Please observe the instructions for the heat pump manager. The connection must only be made by a qualified contractor and in accordance with these instructions. You must have permission to connect the appliance from the rel- evant power supply utility.
Page 19
iNSTALLATiON Electrical connection XD02 connection: Electric emergency/booster heater (NHZ) f Connect the electric emergency/booster heater:. If the heating water temperature falls below 15 °C while defrost- ing, the emergency/booster heater is switched on. If on special systems you can ensure that no defrosting will occur, you need not connect the emergency/booster heater.
iNSTALLATiON Electrical connection Terminal assignment f Secure the cover with the screw and serrated washer. f Connect the cables according to the following diagram. f Connect the following components to the heat pump manag- er in accordance with the technical guides: - Circulation pump for the heat consumer side - Outside temperature sensor - Return sensor (only for operation with buffer cylinder)
iNSTALLATiON Commissioning 12. Commissioning A WPM heat pump manager is required to operate the appliance. All necessary adjustments prior to and during operation are made on this device. Only a qualified contractor should carry out the settings in the heat pump manager commissioning instructions, commission the appliance and instruct the operator in its use.
Page 22
iNSTALLATiON Commissioning 12.3.1 Function test without buffer cylinder Minimum flow rate has been reached No further measures required. Note f Reset the parameters to their original values. If the appliance is operated solely through the WPM heat Parameter Setting pump manager, and an external pump that is not con- MINIMUM PUMP RATE (COMMISSIONING / CHARGING trolled by the WPM is used as a heating circuit pump, you PUMP CONTROL / STANDBY / TYPE OF CONTROL)
iNSTALLATiON Settings Delivery head test - Fully open thermostatic or zone valves in a lead room (e.g. living room and bathroom). Δp * ≥ (V × (Δp + Δp ) + Δp We do not recommend installing thermostatic or zone valves in the lead room.
iNSTALLATiON Appliance handover 13.4 Other settings Version 1: reduced night mode f For operation with or without a buffer cylinder, observe the You can reduce the sound power level of the appliance through information in the WPM instructions and the BUFFER OPER- its output or through the fans.
iNSTALLATiON maintenance 16. Maintenance 17.1 Checking the IWS DIP switch settings Carry out the following steps to make the IWS accessible. WARNING Electrocution f Prior to commencing any service or cleaning work, isolate the appliance across all poles from the power supply.
iNSTALLATiON Troubleshooting Factory setting 17.1.1 Closing the terminal area Compressor mode with electric emergency/booster heater WP - Typ f Check whether the DIP switch is set correctly. Compressor mode with an external second heat generator Material losses In this case, do not connect the electric emergency/boost- er heater.
iNSTALLATiON Troubleshooting The following table shows the meaning of the LEDs on the IWS. LED indicator meaning Red LED flashes Single fault. The appliance is shut down and re- starts after 10 minutes. The LED goes off. Red LED illuminates More than 5 faults within 2 hours run. The appli- ance is shut down permanently and only restarts following a reset on the IWS.
iNSTALLATiON Specification 18.2 Wiring diagram XD02 XD06 XD03 XD01 ON L XE20 XE20 XE20 XE20 RF05 RF05 RF05 1 Turn 1 Turn 1 Turn X11.1 X11.2 Verdichter ON X11.3 Abtauventil N Abtauventil L X11.4 BT55 Ölsumpfheizung N Ölsumpfheizung L T > X11.5 Begleitheizung N RF06...
Page 31
iNSTALLATiON Specification XD05 “+” XE20 X11.1 X12.1 Lüfter Drehz. Lüfter +10V Lüfter 0...10V Lüfter GND X11.2 X12.2 Verdichter ON Heißgastemperatur GND X11.3 Heißgastemperatur Abtauventil N Heizungsrücklauftemperatur GND Abtauventil L Heizungsrücklauftemperatur Außenlufttemperatur GND X11.4 Außenlufttemperatur Ölsumpfheizung N Verdichtereintrittstemperatur GND Ölsumpfheizung L Verdichtereintrittstemperatur X11.5 Rekuperatoreintrittstemperatur GND...
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point. The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511). WPL-A 05 HK 230 Premium WPL-A 07 HK 230 Premium...
Page 36
Specification WPL-A 05 HK 230 Premium WPL-A 07 HK 230 Premium Electrical data Max. power consumption without emergency/booster heater Rated voltage, compressor Control unit rated voltage Rated voltage, emergency/booster heater Compressor phases 1/N/PE 1/N/PE Control unit phases 1/N/PE 1/N/PE...
Page 37
GUARANTEE | ENVIRONMENT AND RECYCLING Guarantee The guarantee conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only grant- ed if the subsidiary has issued its own terms of guarantee.
Need help?
Do you have a question about the WPL-A 05 HK 230 Premium and is the answer not in the manual?
Questions and answers