8.2 INPUTS/OUTPUTS

8.2INPUTS/OUTPUTS
a) ACTUAL VALUES DISPLAY
For these first tests, the
TUS
VIRTUAL INPUTS
1.
Turn on this input and check that the display shows this state.
2.
Turn off this input and check that the display shows this state.
Under the
A1 STATUS
1.
Close the contact connected to this input and check that the display shows this state.
2.
Open the contact connected to this input and check that the display shows this state.
b) USER INPUT A SETPOINT SET TO "ALARM"
1.
Set all inputs 1 through 14, both contact and virtual, to the de-asserted state.
2.
Enter (example) settings under subheading
USER INPUT A NAME
USER INPUT A SOURCE
USER INPUT A FUNCTION
USER INPUT A RELAYS (3-7)
USER INPUT A DELAY
3.
For
INPUT ASSERTED LOGIC
3.1.
Check that there is no logic input diagnostic message on the display.
3.2.
Set the monitored contact for the logic input programmed in setpoint
Note that the corresponding virtual input will have no affect.
3.3.
Check that the diagnostic message, either User Input A or the name programmed in setpoint User Input A
Name, appears on the display with the Auxiliary LED and relay activated. Check in the Event Recorder that the
selected function has been invoked.
3.4.
Set the monitored contact for the logic input programmed in setpoint
Again note that the corresponding virtual input will have no affect.
3.5.
Check that the diagnostic message is removed from the display with the Auxiliary LED and relay deactivated.
3.6.
Repeat Steps 3.1 through 3.7 for all functions programmed to be asserted by a Contact Close input.
4.
For
INPUT ASSERTED LOGIC
4.1.
Check that there is no logic input diagnostic message on the display.
4.2.
Set the monitored contact for the logic input programmed in the
state. Note that the corresponding virtual input will have no affect.
4.3.
Check that the diagnostic message, either User Input A or the name programmed in setpoint User Input A
8
Name, appears on the display with the Auxiliary LED and relay activated. Check in the Event Recorder that the
selected function has been invoked.
4.4.
Set the monitored contact for the logic input programmed in setpoint User Input A Source to the closed state.
Again note that the corresponding virtual input will have no affect.
4.5.
Check that the diagnostic message is removed from the display with the Auxiliary LED and relay deactivated.
4.6.
Repeat steps 4.3 through 4.7 for all functions programmed to be asserted by a Contact Open input.
5.
For
INPUT ASSERTED LOGIC
5.1.
Check that there is no logic input diagnostic message on the display.
5.2.
Set the monitored virtual input for the logic input programmed in setpoint message
on state. Note that the corresponding contact input will have no affect.
8-4
Courtesy of NationalSwitchgear.com
setpoints should be programmed as "Closed | Von". Under the
INPUT 1 (14) ASSERTED LOGIC
subheading,
LOGIC INPUT 1 (14)
HARDWARE INPUTS
CONTACT 1 (14) STATE
S3 LOGIC INPUTS
: "User Input A"
: "Input 1"
: "Alarm"
: "3----"
: "0.00 s"
setpoints set to "Contact Close",
setpoints set to "Contact Open":
setpoints set to "Virtual On":
750/760 Feeder Management Relay
8 COMMISSIONING TESTS

8.2.1 LOGIC/VIRTUAL INPUTS 1 TO 14

subheading:
USER INPUT A
USER INPUT A SOURCE
USER INPUT A SOURCE
USER INPUT A SOURCE
USER INPUT A SOURCE
A1 STA-
to the closed state.
to the open state.
setpoint to the open
to the