2-29. E: 95. Compressor motor control error (Outdoor unit)
Wired remote
Indicator
controller
Check point 1. Check Noise from Compressor
Turn on Power and check operation noise.
→ If an abnormal noise show, replace compres-
sor.
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
52.)
→ Upon correcting the removed connector or mis-wiring, reset the power.
Check point . Replace main PCB
If Check point do not improve the symptom, change main PCB.
Check point . Replace compressor
If Check point do not improve the symptom, change compressor.
2-29. E: 95. Compressor motor control error (Outdoor unit)
Error code
↓
↓
↓
↓
End