SECTION 1 4-MicroVersaTrip® Plus and M icroVersaTrip® PM Trip U nits
The MVT-Pius/MVT-PM is a sol id-state d i rect-acting
self-powered trip device system . The system consists of
the MVT- Plus/MVT- PM programmer, current sensors and
a flux sh ifter trip device. Figure 1 1 0 shows location of
features on programmer. See user manual GEH -5891 A.
1 4.1 TRIP UNIT
MicroVersaTrip® Plus Trip Unit
M icroVersaTrip® Plus trip un its util ize a digital , LCD
display with a four-button keypad to provide local set-up
and readout of tri p settings. A 3-phase ammeter and trip
ind icators are standard, as is a clear plastic cover with
provisions for seal ing to allow tamper resistant instal la
tion. The trip unit digital ly measures the current waveform
in each phase to determine the true RMS value of the
current, regardless of the waveshape. MicroVersaTri p®
Plus tri p units provide accurate, pred ictable overload and
short circuit protection for d istri bution systems that in
clude ac and de variable speed d rives, rectifiers, ind uction
heating, and other loads that cause high harmonic distor
tion as well as standard circuit. They provide maxi mum
breaker-to-breaker selectivity and custom load protec
tion. Short time and g round fault functions include the
flexibility of coordination with or without an l2t ramp and
are also avai lable with high range instantaneous.
MicroVersaTrip® PM Trip Unit
The M icroVersaTrip® PM trip unit adds power manage
ment system capability, advanced metering, and protective
relays to the basic functions of the MicroVersaTri p® Plus.
MicroVersaTrip® PM tri p units communicate d i rectly on
the G E POWER LEADER'" com mun ications bus.
FIG. 1 1 0
Power Requirements
A small amount of power is necessary to energize the
liq uid crystal disp lay (LCD) during setup , for viewing
breaker status, and for metering d isplays. MicroVersaTrip®
PM trip units require external 24 Vdc control power for
operation .
The four sources of such power are the
following.
•
Flow of current
- Breaker current sensors provide
sufficient power to energize the LCD when at least
20% of the sensor's ampere rating is flowing.
•
24 Vdc control power-
PM tri p units are supplied with external 24 Vdc power
that, whenever present, energizes the LCD. Some
breaker models that are configured for MicroVeraTri p
Plus trip un its may b e optionally equ i p ped t o accept
an external 24 Vdc supply.
•
Micro VersaTrip Test Kit -
Kit, Cat No. TVRMS, contains a 24 Vdc power supply.
The LCD is energized whenever the test kit jack is
pl ugged into the test receptacle on the rating plug.
•
Micro Versa Trip battery pack
M icroVersaTri p® battery pack contains a 24 Vdc power
source and a jack. The LCD is energized when the
jack is plugged into the rating p lug test receptacle.
Breakers with M icroVersaTrip®
The MicroVersaTrip@ Test
- T h e p o rt a b l e