Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety®...
PNOZ s3 PNOZ s3 safety relay The safety relay provides a safety-related interruption of a safety circuit. The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with E-STOP pushbuttons Safety gates Light beam devices For your safety...
PNOZ s3 Safety features The relay meets the following safety requirements: The circuit is redundant with built-in self-monitoring. The safety function remains effective in the case of a component failure. The correct opening and closing of the safety function relays is tested automatically in each on-off cycle.
PNOZ s3 Manual start: Unit is active once the input circuit is closed and then the start circuit is closed. Monitored start with falling edge: Unit is active once – the input circuit is closed and then the start circuit is closed and opened again. –...
PNOZ s3 Calculation of the max. cable length l in the input circuit: lmax / km = max. overall cable resistance (see technical details) lmax / km = cable resistance/km Use copper wire that can withstand 60/75 °C. Sufficient fuse protection must be provided on all output contacts with capacitive and in- ductive loads.
Page 7
PNOZ s3 Connection Supply voltage Supply voltage Input circuit Input circuit Single-channel Dual-channel Emergency stop without detection of shorts across contacts Emergency stop with detection of shorts across contacts Safety gate without detection of shorts across contacts Safety gate with detection of shorts across contacts Light beam device or safety 24 V DC...
PNOZ s3 Start circuit/feedback loop Start circuit/feedback loop Start circuit Feedback loop Automatic start 13 (23) 14 (24) Manual/monitored start 13 (23) 14 (24) Semiconductor output *Connect together the 0V connections on all the external power supplies Operation The unit is ready for operation when the Power LED is permanently lit. LEDs indicate the status and errors during operation: LED on LED flashes...
Page 9
PNOZ s3 Status indicators Power Supply voltage is present. Input circuit at S12 is closed. Input circuit at S22 is closed. Safety contacts are closed and semiconductor output Y32 carries a high signal. Reset 24 V DC is present at S34. Error indicators All LEDs off Diagnostics: Short across contacts/earth fault;...
PNOZ s3 Fault Diagnostics: Power-up blocked due to short-term interruption at S12; input cir- cuits not operated simultaneously Remedy: Open both input circuits, S12 and S22, simultaneously and then close again. Fault Diagnostics: Power-up blocked due to short-term interruption at S22; input cir- cuits not operated simultaneously Remedy: Open both input circuits, S12 and S22, simultaneously and then close again.
PNOZ s3 Service life graph The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is negli- gible. Example Inductive load: 0,2 A Utilisation category: AC15 Contact service life: 2,000,000 cycles Provided the application requires fewer than 2,000,000 cycles, the PFH value (see techni-...
PNOZ s3 Technical Details General 750103 751103 Approvals CCC, CE, GOST, KOSHA, TÜV, CCC, CE, GOST, KOSHA, TÜV, cULus Listed cULus Listed Electrical data 750103 751103 Supply voltage Voltage 24 V 24 V Type Voltage tolerance -15 %/+10 % -15 %/+10 % Output of external power supply 2,5 W 2,5 W...
Page 13
PNOZ s3 Relay outputs 750103 751103 1 kA 1 kA Max. short circuit current IK Utilisation category In accordance with the standard EN 60947-4-1 EN 60947-4-1 Safety contacts, AC1 at 240 V 240 V Max. current 6,0 A 6,0 A 0,01 A 0,01 A Min.
Page 14
PNOZ s3 Times 750103 751103 Delay-on de-energisation With E-STOP typ. 10 ms 10 ms With E-STOP max. 20 ms 20 ms With power failure typ. 40 ms 40 ms With power failure max. 60 ms 60 ms Recovery time at max. switching frequency 1/s After E-STOP 100 ms...
Page 15
PNOZ s3 Mechanical data 750103 751103 Mounting position Mechanical life 10,000,000 cycles 10,000,000 cycles Material Bottom Front Cross section of external conduc- tors with screw terminals 1 core flexible 0,25 - 2,50 mm², 24 - 12 AWG – 2 core with the same cross sec- 0,25 - 1,00 mm², 24 - 16 AWG –...
European Parliament and of the Council. The complete EC Declaration of Con- formity is available on the Internet at www.pilz.com/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ostfil- dern, Germany Operating Manual PNOZ s3...
Page 17
+49 711 3409-444 represented by our subsidiaries support@pilz.com and sales partners. Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de...