ABB PSTX30 Applications Manual page 16

Waste water pump
Table of Contents

Advertisement

4.4
Recommended change of
parameter values
This chapter describes the recommended parameter
values. For more information about the parameters
for the PSTX softstarter see: 1SFC132081M0201 -
Softstarters Type PSTX30...PSTX370, Installation and
Commissioning Manual.
4.4.1
05 Slow speed (pump cleaning
reverse)
Menu
Parameters
u
See Figure 15 for navigation.
3
These are the recommended settings for Slow speed:
1.
Set the parameter 05.03 Slow speed reverse to
Fast Jog
2.
Set the parameter 05.04 Slow speed reverse
strength to 100%
Parameters:
Parameter
05.03 Slow speed reverse
05.04 Slow speed rev
strength
4.4.2
08 Sequence start (pump cleaning
forward)
Menu
Parameters
u
start
See Figure 15 for navigation.
These are the recommended settings for Sequence start:
1.
Set the parameter 08.01 Sequence mode to
Start several motors
Set the parameter 08.02 Ie seq 1 to Rated
2.
current of the motor
3.
Set the parameter 08.03 Start mode seq 1 to Full
voltage start
Parameters:
Parameter
08.01
Sequence mode
08.02 Ie seq 1
08.03 Start mode seq 1
Set-up | Application manual: Waste water pump |
16
Complete list
05 Slow speed
u
u
Description
Sets the speed of the Pump cleaning reverse.
It should be set to the maximum speed, which
is 33% or the nominal motor speed.
Sets the torque for Pump cleaning reverse. It
should be set to the highest possible, which is
100%.
Complete list
08 Sequence
u
u
Description
Enables sequence start of motors which is
necessary to have different starts for normal
soft start of pump and Pump cleaning
forward start.
Sets the nominal current for the motor. For
good performance, it is important that the
nominal current is set to the correct value.
For Inside Delta connection, this parameter
shall be set to 58% of the nominal motor
current.
Sets the desired start mode for Pump
cleaning forward. For maximum effect during
the start select full voltage start.
Setting range
Fast jog, Jog,
Creep
10 ... 100%
Setting range
Off, Start several
motors
Depending on
softstarter size
Voltage ramp,
Tourque ramp,
Full voltage start
1SFC132104M0201
Default
Recommended
Value
value
Jog
Fast jog
50%
100%
Default
Recommended
value
Value
Off
Start several
motors
Depending
Rated current of
on
the motor
softstarter
size
Voltage
Full voltage start
ramp

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pstx370