The switching devices have a high withstand
rating (Table 1.1). The high-speed, stored-energy switch-
ing mechanism guarantees a transfer time of
less than 5 cycles.
1.3 TRANSFER SWITCH CATALOG NUMBER
IDENTIFICATION
Transfer switch equipment catalog numbers provide a
significant amount of relevant information that pertains
to a particular piece of equipment. The catalog number
identification table (Table 1.2) provides the required
interpretation information. An example is offered to ini-
tially simplify the process.
Table 1.2 Transfer Switch Catalog Number Explanation
Positions 1-2
Configuration
Closed Transition Automatic
Transfer Switch
Position 7
Switching Device
Arrangement
Fixed Mount Insulated Case
Switches both Power Sources
Fixed Mount Insulated Case
Breakers both Power Sources
Fixed Mount Insutated Case
Breaker Normal Power Source,
Insulated Case Switch
Emergency Power Source
Fixed Mount Insulated Case
Switch Normal Power Source,
Insulated Case Breaker
Emergency Power Source
* Available only on units rated 600 through 1200A without Option 17C
Position 3
Switching Device
Orientation
CT
Vertical
V
Position 8
Positions 9-12
Number
Ampere
of Poles
Rating
A
Two
2
0600
0800
Three
3
1000
B
1200
Four
4
1600
2000
C
2500
3000
4000
D
Example: Catalog number (circled numbers correspond
to position headings in Table 1.2):
The catalog number CTVISPA31000XSU describes a
to
CT V I
closed transition automatic transfer switch with the
switching devices mounted vertically in the enclosure.
The intelligence represented by the IQ Transfer is a
microprocessor-based logic package. The System
Power Breaker (SPB) is used as the switching device
and is a 3-pole insulated case switch for each source.
The continuous current rating of this equipment is 1000
amperes and applicable at 480 VAC, 60Hz. The transfer
switch equipment is enclosed in a NEMA 1 enclosure
and is UL listed.
Position 4
Control Panel
IQ Transfer
I
Position 13
Voltage/
Frequency
120VAC/60Hz
A
208VAC/60Hz
B
600VAC/60Hz
E
220VAC/50 or 60Hz
G
380VAC/50Hz
H
600VAC/50Hz
K
230VAC/50Hz
M
401VAC/50Hz
N
415VAC/50Hz
O
240VAC/60Hz
W
480VAC/60Hz
X
365VAC/50Hz
Z
I.B. ATS-CP01
to
to
12
SP A 3 1000 X S U
Positions 5-6
Switching Device
SPB
Systems Power Breaker
Position 14
Position 15
Enclosure
Type
No Enclosure
K
UL Listed
Type 1
S
Type 3R
R
Type 4*
L
Type 4X*
D
Type 12*
J
13
15
14
SP
Listing
U
Effective 5/98