Omron V680S Connection Manual

Omron V680S Connection Manual

Rockwell automation controllogix 1756-l71 ethernet/ip connection guide
Hide thumbs Also See for V680S:

Advertisement

Rockwell Automation
ControlLogix 1756-L71
EtherNet/IP Connection Guide
OMRON Corporation
RFID System V680S
V680S RFID System
Cat. No. P242I-E-02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the V680S and is the answer not in the manual?

Questions and answers

Summary of Contents for Omron V680S

  • Page 1 Rockwell Automation ControlLogix 1756-L71 EtherNet/IP Connection Guide OMRON Corporation RFID System V680S V680S RFID System Cat. No. P242I-E-02...
  • Page 2 About Intellectual Property Right and Trademarks Microsoft product screen shots reprinted with permission from Microsoft Corporation. Windows is a registered trademark of Microsoft Corporation in the USA and other countries. EtherNet/IP is a registered trademark of ODVA. EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
  • Page 3: Table Of Contents

    Table of Contents Related Manuals ....................1 Remarks ........................ 2 Overview ....................... 4 Applicable Devices and Support Software ............5 4.1. Applicable Devices ..................5 4.2. Device Configuration ..................6 Connection Procedure..................7 5.1. EtherNet/IP Communications Settings ............7 5.2. Work Flow .....................
  • Page 4: Related Manuals

    Safety Precautions, Precautions for Safe Use, and Precaution for Correct Use of manuals for each device which is used in the system. Cat. No. Model Manual name RFID System V680S Series User’s Manual Z353 V680S-HDM[][]-EIP (EtherNet/IP) Logix5000 Controllers General Instructions...
  • Page 5: Remarks

    (4) It is prohibited to copy, to reproduce, and to distribute a part of or whole part of this document without the permission of OMRON Corporation. (5) This document provides the latest information as of November 2016. The information in...
  • Page 6 The following notation is used in this document. Precautions for Safe Use Indicates precautions on what to do and what not to do to ensure using the product safely. Precautions for Correct Use Indicates precautions on what to do and what not to do to ensure proper operation and performance.
  • Page 7: Overview

    3. Overview This document describes the procedure for connecting the RFID System of OMRON Corporation (hereinafter referred to as OMRON) to the ControlLogix PLC of Rockwell Automation (hereinafter referred to as Controller) on EtherNet/IP and provides the procedure for checking their connection.
  • Page 8: Applicable Devices And Support Software

    For details on the above products (other than communication connection procedures), refer to the manuals for the corresponding products or contact your OMRON representative. Precautions for Correct Use You can connect devices with the versions listed in Section 4.2 or higher versions.
  • Page 9: Device Configuration

    4.2. Device Configuration The hardware components to reproduce the connection procedure of this document are as follows: ControlLogix Personal computer RFID System (RSLogix5000, V680S OS:WindowsXP) LAN cable Switching Hub W4S1-05C Manufacturer Name Model Version OMRON Switching Hub W4S1-05C OMRON RFID System...
  • Page 10: Connection Procedure

    5. Connection Procedure This section describes how to connect the Controller on the EtherNet/IP network using ETHERNET-MODULE Generic Ethernet Module with the RFID System. 5.1. EtherNet/IP Communications Settings The Controller settings are shown below. Controller / Ethernet Bridge RFID System IP address 192.168.1.1 192.168.1.200...
  • Page 11: Work Flow

    5.2. Work Flow Take the following steps to make the tag data link connection settings for EtherNet/IP. Set up the RFID System. 5.3 Setting up the RFID System ↓ Set the parameters of the RFID System. 5.3.1 Parameter Setting ↓ Set up the Controller.
  • Page 12: Setting Up The Rfid System

    Parameter Setting Set the parameters of the RFID System. Additional Information For details on the RFID System setup and operation refer to the RFID V680S Series User’s Manual (Cat. No. Z353). Connect the RFID System over Ethernet to the controls system and PC.
  • Page 13: Setting Up The Controller

    5.4. Setting up the Controller Set up the Controller. 5.4.1. Starting RSLogix5000 and Configure the Controller Start RSLogix500 Software, and create a new project Open RSLogix 5000 and select File- New. The New Controller window will appear. Enter the controller Type, Revision, Name, and Chassis Type.
  • Page 14 A new empty project is created. Add the Ethernet module to the control system by selecting the 1756 Backplane under Configuration then Right Click - New Module. In Select Module Type window, add the Ethernet Bridge. 1756-ENBT Then select Create to add to the backplane.
  • Page 15 This opens the New Module window. Enter Name, Ethernet Address, and Module Definition. Name: EtherNetIP_Module IP Address: 192.168.1.1 In the Module Definition window, enter the Series and Revision information. Click OK. In this application: Series: A Revision: 3.9 In the pop-up window select Yes.
  • Page 16: Setting Up The Network

    In the Select Module Type window, Create Ethernet – Module Generic Ethernet Module In the New Module window, enter Name, Comm Format, Address/ Host Name, and Connection Parameters (see below.) In this application: Name: V680S Comm Format: Data – SINT IP Address: 192.168.1.200...
  • Page 17 Configuration: Assembly Instance: 1 Size: 0 (8-bit) NOTE: For additional information regarding assembly instance and size, see RFID System V680S Series User’s Manual, Section 5. Host Communications Specifications. In the Module Properties Report, Check the box “Use Unicast Connection over Ethernet/IP”,...
  • Page 18: Going Online And Transferring The Project Data

    5.6. Going Online and Transferring the Project Data Go online with the controller and transfer the project data. Precautions for Correct Use Please confirm that the LAN cable has been connected before proceeding to the following steps. If it is not connected, turn OFF the power to the devices, and then connect the LAN cable. To go online with the Controller select Communications –...
  • Page 19 When the controller is online, the Controller OK LED is solid green, this means that controller is operating normally...
  • Page 20: Checking The Ethernet/Ip Communications

    If the I/O OK LED is solid green, the controller is communicating with the RFID System Open Module Properties Report: EtherNetIP_Module (ETHERNET – Module 1.1) by right clicking on ETHERNET-MODULE V680S. Check that the Status is Running and that there are no faults in the module.
  • Page 21 Expand out Tag names by clicking the + symbol next to each tag name. In the first byte of the created Input Tag (V680S: I Data), there is a value of 1. This means that the RFID System is READY.
  • Page 22 For additional information regarding RFID Commands see RFID System V680S Series User’s Manual, Section 5. Host Communications Specification, Command Details. In the Input Tag (V680S: I Data) the data is received.
  • Page 23: Revision History

    6. Revision History Revision Date of revision Revision reason and revision page code Nov. 30, 2016 First edition Second edition Nov. 20, 2018...
  • Page 24 OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu Authorized Distributor: Controllers & I/O •...

This manual is also suitable for:

V680s-hmd-64-eip

Table of Contents