Pipework Connection ..........................30 Water Treatment ............................ 31 Pipework Arrangement .......................... 32 Connection Types and Sizes ......................... 32 Cooler Connections ..........................32 Refrigerant Relief Valve Piping ......................32 Ductwork Connection ..........................33 Electrical Connection ..........................33 Power Wiring ............................33 YORK INTERNATIONAL...
Page 3
Program and Setup Keys ....................... 102 1. INTRODUCTION and PHYSICAL DESCRIPTION ................ 103 General ..........................103 Keypad and Display ......................103 Unit (Chiller) ON / OFF Switch ....................103 Microprocessor Board ......................103 Ancillary Circuit Boards ......................104 YORK INTERNATIONAL...
Page 4
Remote Cooling Setpoints Key ..................... 135 Chilled Liquid Temperature Control ..................135 Compressor Capacity Loading Sequence ................136 “Fuzzy Logic” “Loading” Anticipatory Control ............... 137 “Load Limiting” Anticipatory Control ..................137 Compressor Unloading and Shutdown Sequence ............... 137 YORK INTERNATIONAL...
Page 5
Scheduled Maintenance ......................... 150 Chiller/Compressor Operating Log ....................151 Maintenance Requirements ......................152 Maintenance Requirements for YORK J,K and P Reciprocating Compressors ......153 General Periodic Maintenance Checks – Standard Units ............. 154 SPARE PARTS ............................ 155 Recommended Spares ........................155 Recommended Compressor Oils ....................
NOT be installed inside the micro panel. NO external wiring is allowed to be run through the micro panel. All wiring must be in accordance with YORK’s published specifications and must be performed ONLY by qualified YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals.
Center. See Commissioning, page 42. types of air conditioning installations. • Only genuine YORK-approved spare parts, oils and The unit is intended for cooling water or glycol solu- refrigerants must be used. Recommendations on tions and is not suitable for purposes other than those spare parts can be found on page 155.
This manual, and any other document supplied with the personnel. unit, are the property of YORK, which reserves all rights. They may not be reproduced, in whole or in part, with- Electrical out prior written authorization from an authorized YORK representative.
CB2 (System 2) can also be used to stop the respective system in an emergency. When operated, each removes the electrical supply from the control system, thus shut- ting down the unit. YORK INTERNATIONAL...
Fire Extinguishing Data Non-flammable. Containers Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated. Fire Fighting Self-contained breathing apparatus and protective clothing must be worn in fire conditions. Protective Equip. YORK INTERNATIONAL...
Page 12
General Chiller Information and Safety FORM 150.52-NM2 (1001) MATERIAL SAFETY DATA Section 1 – PRODUCT NAME AND INFORMATION Product (Trade Name and Synonyms): YORK “C” Oil Chemical Name: Semi-Synthetic Hydrocarbons Chemical Family: Mineral Oil Formula: Proprietary CAS#: Proprietary Section 2 – COMPONENTS AND HAZARD STATEMENT This product is non-hazardous.
Page 13
The information in this material safety data sheet should be provided to all who use, handle, store, transport, or are otherwise exposed to this product. YORK believes the information in this document to be reliable and up to date as of the date of publication, but makes no guarantee that it is.
Page 14
General Chiller Information and Safety FORM 150.52-NM2 (1001) MATERIAL SAFETY DATA REFRIGERANT OIL DATA: SAFETY DATA YORK “E” OIL Classification Non-hazardous. Irritant - may aggravate any existing skin disorders. Wash hands and any other contacted skin with In Contact With Skin soap and water after handling.
Design is in accordance with applicable sections of INTRODUCTION ASME Pressure Vessel Code, NFPA 70 (National Elec- YORK Millennium YCAR chillers are complete fac- trical Code), U.L. and cU.L. Standards, and ASHRAE/ tory-packaged units designed for water or water-glycol ANSI-15 Safety Code for Mechanical Refrigeration.
A magnetic plug is included terminal boxes are raintight. Starting is by either part- in the oil stream. YORK “C” Oil is used for standard winding or across the line. R-22 applications; YORK “E” Oil is used for high am- bient (>40.6°C [105°F]) R-22 applications.
• Automatic reset after power failure and control panels are housed in NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged, • Automatic system optimization to match operating latched and gasket sealed outer doors equipped with conditions YORK INTERNATIONAL...
Since the micro is sending a run signal to the contactor, it senses the low motor current below 10% FLA and shuts the system down. YORK INTERNATIONAL...
“Operating Current.” A current imbalance exceeding an unloaded It is recommended that a YORK Ser- level of 25% will result in the motor pilot circuit being vice Technician or the YORK factory de-energized.
English (°F and PSIG) and for each circuit, the fol- rent unload point, liquid temperature setpoint re- lowing items can be displayed: set signal from YORK ISN or building automa- tion system (by others), via: • Return and leaving chilled liquid, and ambient tem- •...
FORM 150.52-NM2 (1001) 14 of N.E.C., to isolate unit power supply for ser- • A YORK ISN Building Automation System can vice). Factory wiring is provided from the Termi- provide a Pulse Width Modulated (PWM) signal nal Block or Disconnect Switch to factory supplied...
Unrestricted airflow is per- Standard water chilling application range is 4°C to 13°C mitted through generously sized louvered openings. (40°F to 55°F) Leaving Chilled Water Temperature. To (Factory-mounted) YORK INTERNATIONAL...
11 12 13 14 15 BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATOR REFRIGERANT VOLTAGE/STARTER DESIGN/DEVELOPMENT LEVEL : 380-415/3/50 : YORK : Standard Unit : R-407C : Design Series A : Chiller : R-22 : Engineering Change : Air-Cooled or PIN Level...
Page 26
Product Description FORM 150.52-NM2 (1001) UNIT NOMENCLATURE NAMEPLATE ENGINEERING DATA (CONTINUED) YORK INTERNATIONAL...
If the unit is to be put into storage, prior to installation, Major damage must be reported immediately to your the following precautions should be observed: local YORK representative. MOVING THE CHILLER • Unit must be “blocked” so that the base is not permitted to sag or bow.
Data Section, identify each mount and its correct to the control panel using shielded cable. There location on the unit. should be a straight run of piping of at least five pipe YORK INTERNATIONAL...
1" N.P.T. connection can be obtained temperatures, should be protected using insulation and from YORK as an accessory for the unit. Alternatively, heater tape and/or a suitable glycol solution. The liquid a differential pressure switch sited across an orifice plate pump(s) must also be used to ensure liquid is circulated may be used, preferably of the high/low limit type.
COOLER CONNECTIONS Aerated, brackish or salt water is not recommended for Standard chilled liquid connections on all coolers are of use in the water system(s). YORK recommends that a the Victaulic Groove type. water treatment specialist is consulted to determine that the proposed water composition will not affect the evapo- rator materials of carbon steel and copper.
If the ducts from two or more fans are to be combined into a common duct, back-flow dampers should be fit- tion (not supplied by YORK). ted in the individual fan ducts. This will prevent recircu- lation of air when only one of the fans is running.
7.5 m (25 ft.) unless an optional input isolator kit is It is important to check that the cor- fitted. The optional input isolator kit uses 15VDC (not rect primary tapping has been used, 30VDC). and that it conforms to the site high voltage supply. YORK INTERNATIONAL...
12) for No.2 System. Remote Setpoint Offset – Current Timed contact closure of a suitable contact connected to terminals 13 and 16 (Figures 11 and 12) (PWM con- tacts) will provide remote offset of EMS% CURRENT LOAD LIMIT. YORK INTERNATIONAL...
Installation FORM 150.52-NM2 (1001) POWER AND CONTROL PANEL LAYOUTS 00416VIP FIG. 8 – POWER PANEL SECTION OPTIONS PANEL WITH TRANSFORMER YORK INTERNATIONAL...
Page 37
FORM 150.52-NM2 (1001) OPTIONS PANEL LAYOUT (TYPICAL) 00413VIP FIG. 8 – POWER PANEL SECTION OPTIONS PANEL WITH TRANSFORMER (CONTINUED) YORK INTERNATIONAL...
FORM 150.52-NM2 (1001) LOGIC SECTION LAYOUT WITH CONTROL PANEL LAYOUT 00415VIP FIG. 10 – LOGIC SECTION LAYOUT WITH CONTROL PANEL LAYOUT YORK INTERNATIONAL...
Flow Switch System No. 1 Run System No. 1 Alarm Contacts System No. 2 Run Current Chilled Liquid Circulating Pump Start Temperature System No. 2 Print Alarm Contacts Chiller Run Isolator Auxiliary Interlock LD03502 FIG. 11 – CUSTOMER CONNECTIONS YORK INTERNATIONAL...
FORM 150.52-NM2 (1001) SECTION 5 – COMMISSIONING PREPARATION To add oil to a circuit, connect a YORK hand oil pump (Part No. 470-10654-000) to the 1/4" oil priming valve Commissioning of this unit should on the oil separator piping with a length of clean hose or copper line, but do not tighten the flare nut.
Page 43
Program the daily and holiday start/stop by pressing the cooler. Purge air from the top of the cooler using the plugged air vent mounted on the top of the cooler the ‘Set Schedule/Holiday’ key. (See Section 9 [7.3].) YORK INTERNATIONAL...
The units are designed to work independently, or in con- automatic. After an initial period at minimum capacity junction with, other equipment via a YORK ISN build- on the lead compressor, the control system will adjust ing management system or other automated control sys- the unit load depending on the chilled liquid temperature tem.
0315, 0345, 0365, 0385, 0415, 0435 0485, 0525, 0575, 0645, 0685 0485, 0525, 0575, 0645, 0685 Cooler pressure drops are approxi- mate. (A Flow Meter should be used to verify flow.) FIG. 13 – FLOW RATE AND PRESSURE DROP CHARTS YORK INTERNATIONAL...
PROPYLENE GLYCOL Mean Temperature Through Cooler Concentration W/W Excessive flow will cause damage to the cooler. Do not exceed maximum cooler GPM. Special care should be taken when multiple chillers are fed ˚C by a single pump. LD03504 YORK INTERNATIONAL...
Water Volume, liters Maximum Water Side Pressure, Bar Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, Bar 11.4 Maximum Chilled Water Flow Rate, Bar 37.9 37.9 37.9 37.9 37.9 Water Connections, inches 1 Optional 21 Bar Waterside available YORK INTERNATIONAL...
Page 50
85,808 EVAPORATOR, DIRECT EXPANSION Water Volume, gallons Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, gpm Maximum Chilled Water Flow Rate, gpm Water Connections, inches 1 Optional 300 PSIG Waterside available YORK INTERNATIONAL...
1. For leaving brine temperature below 4.4°C (40°F), contact your nearest YORK office for application requirements. 2. For leaving water temperature higher than 12.8°C (55°F), contact the nearest YORK office for application guidelines. 3. The evaporator is protected against freezing to -28.8°C (-20°F) with an electric heater as standard.
Page 57
SYSTEM #2 CHILLER COMPRESSOR DATA FAN DATA 11, 12 COMPRESSOR DATA FAN DATA 11,12 VOLTS MODEL PW-LRA X-LRA PW-LRA X-LRA YCAR (EA) (EA) (EA.) (EA) YCAR0315 YCAR0345 YCAR0365 YCAR0385 YCAR0415 YCAR0435 YCAR0485 YCAR0525 YCAR0575 YCAR0645 1173 YCAR0685 1173 1173 YORK INTERNATIONAL...
Field connections to factory-provided Non-Fused Disconnect Switch (Opt), or Ter- minal Block (Opt) in the Options Panel. Factory connections to Circuit Breakers in each of the two Power Panels. Optional Field Provided 115-1-60 Micro panel Supply LD04922 YORK INTERNATIONAL...
Field connections to Terminal Block or Non-Fused Disconnect Switch in the Op- tions Panel. Factory connec- tions to Terminal Blocks in each of the two Power Panels. Optional Field Provided 115-1-60 Micro panel Supply LD04923 YORK INTERNATIONAL...
LEGEND Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others LD04950A FIG.
LEGEND Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others LD04950B FIG.
Page 62
Any contacts connected to flow switch inputs or BAS inputs on terminals 13 - 19 or TB3, or any other terminals, must be suppressed with a YORK P/N 031-00808-000 suppressor across the relay/ contactor coil.
Page 63
Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others YORK INTERNATIONAL...
Page 64
Technical Data FORM 150.52-NM2 (1001) YCAR0315 – YCAR0685 WIRING DIAGRAM CONNECTION DIAGRAM – CONTROL CIRCUIT FIG. 19 – YCAR0315 – YCAR0685 WIRING DIAGRAM - CONNECTION DIAGRAM, CONTROL CIRCUIT YORK INTERNATIONAL...
Page 65
FORM 150.52-NM2 (1001) LD04928 YORK INTERNATIONAL...
FORM 150.52-NM2 (1001) YCAR0315 - 0685 ELEMENTARY DIAGRAM STANDARD AND REMOTE EVAPORATOR UNITS – POWER CIRCUIT FIG. 29 – ELEMENTARY DIAGRAM, POWER CIRCUIT – STANDARD AND REMOTE EVAPORATOR UNITS YORK INTERNATIONAL...
Technical Data FORM 150.52-NM2 (1001) YCAR0315 - 0685 ELEMENTARY DIAGRAM STANDARD AND REMOTE EVAPORATOR UNITS – CONTROL POWER TRANSFORMER KIT LD04949 FIG. 30 – CONTROL POWER TRANSFORMER KIT YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 79
0415 3050 1144 1022 0415 3000 1149 1093 2438 1981 SYS. #1 SYS. #2 8" 8" POWER OPENING WATER INLET WATER OUTLET (FAR SIDE) (2) 57 DIA. RIGGING 1302 2108 HOLES (EACH SIDE) 2506 4499 LD03546 SIDE VIEW YORK INTERNATIONAL...
Page 80
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 81
43" 36" 96" 78" SYS. #1 SYS. #2 2" 8" 8" 7-1/4" POWER OPENING WATER OUTLET WATER INLET (FAR SIDE) (7" x 21") (2) 2-1/4" DIA. RIGGING 56-7/16" 83" HOLES (EACH SIDE) 37-1/2" 98-11/16" 177-1/8" SIDE VIEW LD03542 YORK INTERNATIONAL...
Page 82
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 83
3810 1168 1092 2438 1981 8" POWER OPENING WATER OUTLET (2) 57 DIA. RIGGING (FAR SIDE) HOLES (EACH SIDE) 2108 FOR MODELS 0435, 0485 1385 2718 FOR MODELS 0575, 0645 8" 2988 WATER INLET 5718 LD07033 SIDE VIEW YORK INTERNATIONAL...
Page 84
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 85
2" 8" 8" 7-1/4" POWER OPENING WATER INLET WATER OUTLET (FAR SIDE) (2) 2-1/4" DIA. RIGGING 83" FOR MODELS 0435 & 0485 54-1/2" HOLES (EACH SIDE) 107" FOR MODELS 0575 & 0645 117-5/8" 37-1/2" 225-1/8" SIDE VIEW LD07034 YORK INTERNATIONAL...
Page 86
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 87
CENTER OF GRAVITY (Copper) YCAR YCAR 0685 3912 1168 1034 0575 3810 1168 1092 2438 1981 8" 8" POWER OPENING WATER OUTLET (3) 57 DIA. RIGGING WATER INLET (FAR SIDE) HOLES (EACH SIDE) 2718 1382 2184 1900 6937 SIDE VIEW LD03570 YORK INTERNATIONAL...
Page 88
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 89
154" 46" 40.7" 0685 150" 46" 43" 36" 96" 78" 2" 8" POWER OPENING 8" 7-1/4" WATER OUTLET (3) 2-1/4" DIA. RIGGING (FAR SIDE) WATER INLET HOLES (EACH SIDE) 107" 54-7/16" 37-1/2" 86" 74-13/16" 273-1/8" SIDE VIEW LD03566 YORK INTERNATIONAL...
2 mm (1/8" between resilient washer and (1/4") shim between the upper load plate and verti- underside of channel cap plate. cal uprights. Lower the equipment on the blocking 10. Installation is now complete. or shimmed isolators. YORK INTERNATIONAL...
Low pressure vapor enters the compressor where pres- and further cooling takes place before returning to the sure and superheat are increased. The high pressure va- cooler. por is fed to the Air-cooled condenser coil and fans where FIG. 33 – REFRIGERANT FLOW DIAGRAM YORK INTERNATIONAL...
START-UP TECHNICIAN/ COMPANY: _______________________________ If it is necessary to add oil, connect a YORK oil pump to the oil charging valve on the compres- START-UP DATE : _________________________ sor, but do not tighten the flare nut on the delivery tubing.
Disch Press Unld = _______________ kPa (PSIG) ant in the liquid indicator; and, usually no more than 13.8 kPa (2 PSIG) variation in suction pres- Suction Press Cutout = ____________ kPa (PSIG) sure for any given set of operating conditions. YORK INTERNATIONAL...
Assure that superheat is set at 7 - 8°C Add charge as needed to increase subcooling, and re- (2 - 15°F). move charge as necessary to reduce subcooling. When- ever removing charge, be sure to recover it in an ap- proved container. YORK INTERNATIONAL...
Temp = ____ ____ ____ ____ °C (°F) Superheat = ____ ____ ____ ____ °C (°F) Proper subcooling and superheat will assure optimum performance and reliability of the system. Checks should always be made when commissioning a chiller, and on a yearly basis. YORK INTERNATIONAL...
This key is used for display and programming of the chiller operational settings and limits. This switch shuts down the entire chiller when placed in the OFF position. The switch must be ON for the chiller to operate. YORK INTERNATIONAL...
External interface is available for control of the chiller to turn the entire chiller OFF, if desired. The switch via a YORK ISN System or YORK Remote Control must be placed in the ON position for the chiller to op- Center.
The boards convert 0 - 12VDC logic processor will not be active and the micro cannot keep levels outputs from the Microprocessor Board to track of time, although all other functions will operate 115VAC levels used by the contactors, valves, etc. YORK INTERNATIONAL...
17% of the average motor current in one rent, unbalanced current, and single phasing. of the phases, the Motor Protector will recognize it and shut the system down. YORK INTERNATIONAL...
Micro Panel FORM 150.52-NM2 (1001) 29119A SIDE VIEW 29121A 29121A TOP VIEW TOP VIEW DISPLAY SWITCH PUSHED TO LEFT INDICATES “ON” 29120A SIDE VIEW FIG. 35 – MOTOR PROTECTOR YORK INTERNATIONAL...
Remote Reset Curr = 105% FLA - {(4sec - 1 sec) X (75%FLA)} Never bypass a flow switch. This will 10 sec cause damage to the chiller and void = 105% - 225%FLA sec any warranties. 10 sec = 82.5% FLA YORK INTERNATIONAL...
Page 108
22°C (40°F), the temperature offset would equal: pressor (50Hz models) across the in- ductive coil. ° Reset Temp = (4 sec - 1 sec) X 40 10 sec Reset Temp = 120 ° F sec 10 sec = 12 ° F (6 ° YORK INTERNATIONAL...
NOTE : Dimple is positioned at top edge Dip Switch Set (8 switches) System Switches S2 = System 1 S3 = System 2 S2 to S5 S4 = System 3 S5 = System 4 FIG. 36 – COMPONENT LAYOUT YORK INTERNATIONAL...
The message Each compressor has its own heater. The heater will be will disappear when the compressor shuts off. off whenever the compressor is running. YORK INTERNATIONAL...
Under some circumstances, a pumpdown cal equipment) and the alarm circuit may occur when a compressor is called should fail to function, YORK will not to come on for cooling. If this occurs, the be liable for damages. compressor will restart to provide cool- ing after the pumpdown is complete and 1.20 RUN STATUS (CHILLER)
4. If all compressors are waiting to start (Anti-recycle timers have not timed out), the micro will assign the lead to the compressor with the shortest anti- recycle time in an effort to provide cooling quickly. YORK INTERNATIONAL...
Control Center) has turned the unit OFF through These messages are described in detail in this section, the RS-485 port. with examples of each display. In each example "#" is used as applicable to represent the system number where messages apply to individual systems. YORK INTERNATIONAL...
Page 115
The display shows the time before the respective Range, the Chiller ON/OFF switch is ON, remote cy- compressor can start. This display will only appear af- cling devices are closed, and system switches permit. ter the anti-recycle timers have timed out. YORK INTERNATIONAL...
The U13 RTC chip on the Microprocessor Board should Anticipation controls monitor discharge pressure, motor be replaced as soon as possible with YORK part # 031- current and suction temperature for each compressor 00955-000. Otherwise, the chiller will shutdown and...
L I M I T I N G Any time that a Unit Fault occurs, the shutdown will be S Y S S U C T L I M I T I N G logged into the HISTORY BUFFER. YORK INTERNATIONAL...
This is accessible by pressing the STATUS key. 115VAC Under Voltage Cutout: U N I T F A U L T 1 1 5 V A C U N D E R V O L T A G E YORK INTERNATIONAL...
Failure to repair the cause of the fault by operation at low refrigerant charge or restricted re- while manually allowing repetitive re- starts may cause further expensive damage to the system. YORK INTERNATIONAL...
A fault lockout will result if matic printout. This is not a cause for safety thresholds are exceeded three times in a 90 concern, unless oil pressure faults, liq- minute period. uid slugging, or motor overheating continuously occur. YORK INTERNATIONAL...
The Display keys and the data available from each is as saturated suction temperature, suction superheat, load follows: stage, and cooler inlet refrigerant temp. Examples of these displays are as follows, where # is the appropriate system number. YORK INTERNATIONAL...
4.4 to 11.1°C (40 to 52 °F). may cause serious damage to the chiller. Selecting this mode also auto-programs the Low Chilled Liquid Cutout at 2°C (36°F) and the Suction Pressure Cutout at 3 bar (44 PSIG). YORK INTERNATIONAL...
The following keys can be scrolled using the Function pushed in Key: Chilled Liquid Temps, System # Data, Motor Current and Options. “CLOSED” Position: LD03511B Right side of switch pushed in LD03511A FIG. 39 – ENLARGED PHOTOGRAPH OF DIP SWITCHES ON MICROPROCESSOR BOARD YORK INTERNATIONAL...
“rate control” ted from the microprocessor to the remote printer. As and “temperature deviation from setpoint” to determine the data is transmitted it is erased from the memory. when loading should occur. YORK INTERNATIONAL...
Page 127
EMS PWM Temp. Reset Enabled S O F T W A R E V E R S I O N CUR/TEMP – EMS PWM Current Limiting and C . R 0 9 . 2 3 . 0 1 Temperature Reset Enabled YORK INTERNATIONAL...
102.8 °F similar printouts for the appropriate number of systems: SAT SUCTION TEMP 31.7 °F SUCTION SUPERHEAT 11.2 °F YORK INTERNATIONAL CORPORATION COMPRESSOR LOAD STAGE MILLENNIUM RECIP CHILLER COOLER INLET REFRIG 23.6 °F LIQUID LINE SOLENOID HOT GAS BYPASS SOLENOID...
This message indicates the fault that caused the shut- This display shows the Low Ambient Cutout pro- down; in this case, a high motor current in System 2 grammed at the time of the fault. was the cause of the shutdown. YORK INTERNATIONAL...
Page 130
Full Load Amps. A M B I E N T A I R T E M P 7 2 . 6 ° F This message indicates the outdoor Ambient Air Tem- perature at the time of the fault. YORK INTERNATIONAL...
ON = Energized / OFF = De-Energized (OFF) at the time of the fault. S Y S F A N S T A G E This message indicates the stage of condenser fan op- eration on the system. See Section 8.4 for details of fan staging. YORK INTERNATIONAL...
Page 132
Micro Panel FORM 150.52-NM2 (1001) SAMPLE PRINTOUT OF FAULT HISTORY DATA SYSTEM 2 DATA YORK INTERNATIONAL CORPORATION MILLENNIUM SCREW CHILLER COMPRESSORS STATUS RUN TIME 0- 0-15-26 D-H-M-S SAFETY SHUTDOWN NUMBER 1 MOTOR CURRENT 104 AMPS 87 %FLA SHUTDOWN @ 3:56 PM 28 AUG 00...
If example, pressing the key when the cursor is on “PM” this is not done, the new values entered will be lost and changes it to “AM”. the original values will be returned. YORK INTERNATIONAL...
(44.0°F) The Setpoints keys are used to program the required range) chilled water liquid temperature for the application. This is accomplished by programming the “Setpoint” and 6.0°C the acceptable deviation (+ or - Range) This deviation (42.0°F) YORK INTERNATIONAL...
After pressing the Enter key, the display will continue 30-second unload timer determines when the micro may to show the message until another key is pressed. adjust the chiller capacity to keep the chilled liquid tem- perature within the control range. A fuzzy logic load- YORK INTERNATIONAL...
The Load Timer will reset to 60 seconds, ture rises above the high end of the Control Range and and the Unload Timer to 30 seconds. YORK INTERNATIONAL...
If saturated suction temperature is less than 110 - 101% of the internal limit of 4°C (24°F) for water chill- ing or setpoint – 6°C (11°F) for brine chilling – the respective system will not be allowed to load. YORK INTERNATIONAL...
M O N S T A R T 0 6 : 0 0 site time period. Press ENTER to advance to the day of S T O P 0 5 : 3 0 the month. YORK INTERNATIONAL...
Page 140
The Holiday Schedule is only per- Programming the DAILY SCHED- formed once, then erased from ULE will not affect on the holiday memory. This avoids the need for schedule. reprogramming after the holiday, as most special Holiday Schedule requirements occur only occasionally. YORK INTERNATIONAL...
30 minutes. The following status mes- See also Section 9 (2.5). sage will be observed when in the Manual Override Mode: M A N U A L O V E R R I D E YORK INTERNATIONAL...
Failure to properly desired language. program these values may cause damage to the Chiller or operating Pressing the Enter key repeatedly allows scrolling problems. through the programmable displays. YORK INTERNATIONAL...
Typically, the unload point should be set 1.4 to 1.7 bar (20 - 25 PSIG) below the discharge pressure cutout set- 33.3 – 20 New Cutout = 44 x = 1.2 bar (17.6 PSIG) ting. The micro will accept a range of programmable 33.3 YORK INTERNATIONAL...
Page 144
-17°C (1°F) for more than To program the High Ambient Cutout, key in the re- a short time. quired setting and press the Enter key to store the value into memory and scroll to the next display. YORK INTERNATIONAL...
Page 145
If the programmable limit is set between 100% and 105% 600 seconds is recommended. of full load current, this safety will protect against ex- YORK INTERNATIONAL...
Page 146
In most cases, automatic lead/lag is selected to allow the micro to attempt to balance run time between the system. Details of manual and automatic lead / lag operation are outlined in Section 9 (1.21). YORK INTERNATIONAL...
FAN 7 FAN 9 FAN 2 FAN 4 FAN 6 FAN 8 FAN 10 YCAR 0315 YCAR 0415 YCAR 0575 0345 0435 0645 0365 0485 0685 0385 0525 LD07267 FIG. 40 – CONDENSER FAN LAYOUT FOR DXRT 2-COMPRESSOR UNITS YORK INTERNATIONAL...
10 - 15 minutes. The oil level should be between the YORK shall not be liable for costs incurred to return upper half of the bottom sightglass and below the top of the unit to satisfactory condition.
Return 025-29964-000 Other spare parts vary depending on the unit model. Contact your local YORK Sales and Service Center for information and please quote the unit model number and serial number. When ordering spare parts, we will require the follow-...
Check mains supply is stable and within allowable UNDERVOLTAGE Poor mains supply voltage. limits. displayed. Check for voltage dip on compressor start. Chiller FAULT: Liquid line solenoid valve leaking. Replace solenoid valves. PUMPDOWN FAIL Compressor valves. Perform top head overhaul. displayed. YORK INTERNATIONAL...
Page 157
See also SYS # DSCH above design conditions. LIMITING. Check condenser oil cleanliness. SYS # SUCT LIMITING Low suction pressure has Check charge (low subcooling). displayed (Compressor activated unloading/limiting Check for high chilled liquid flow. suction unloading) YORK INTERNATIONAL...
Test Point ............Microboard J11-9/3 System 1: ............Microboard J13-7/1 System 2: ............Microboard J14-7/1 Oil Pressure: System 1: ............Microboard J13-8/3 System 2: ............Microboard J14-8/3 Discharge Pressure: System 1: ............Microboard J15-8/3 System 2: ............Microboard J15-7/1 YORK INTERNATIONAL...
BUYER’S SOLE AND EXCLUSIVE REMEDY IN Except for reciprocating replacement compressors, which THE EVENT OF A DEFECT IN WORKMANSHIP YORK warrants for a period of one year from date of OR MATERIALS. IN NO EVENT SHALL YORK’S shipment, YORK warrants reconditioned or replacement...
Need help?
Do you have a question about the MILLENNIUM YCAR0315 and is the answer not in the manual?
Questions and answers