Profibus-Dpv1 Mode; Comparison Between Dpv1 And Dpv0 Slave - Siemens SIMATIC ET 200M Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

Commissioning and Diagnostics
6.1.4

PROFIBUS-DPV1 Mode

The ET 200M fulfills the requirements of DPV1. If you want to use the DPV1
functions, the DP master must of course also fulfill the requirements of DPV1 (see
the documentation for the DP master).
The table below shows you the new functions of the PROFIBUS-DPV1
slave compared to a PROFIBUS-DPV0 slave:
Table 6-4

Comparison between DPV1 and DPV0 slave

Parameterization and configuration with device master file
Cyclic data exchange
Acyclic data exchange
(read/write data record):
S
Free access to parameters in
field device
field device
S
Reparameterization of application process
3
Diagnostics
S
Module diagnosis
S
Module status
S
Channel-specific diagnosis
Interrupts
S
Diagnostic interrupt
S
Process interrupt
S
Module removal/insertion interrupt
Other functions
S
Time synchronization
S
Time stamping
S
Clock synchronism
1 The assignment of the functions to the interface module versions is given in Sections 9.1 and 9.2.
2 If parameterization is performed using HW Config, S7-specific features are set for some functions.
3 One interrupt can be used per diagnostic frame. With DPV1 (and S7-DP) an interrupt consists of a slave
diagnosis which is accompanied by an acknowledgment mechanism which does not exist in DPV0.
4 Without device master file or with device master file revision 2
5 With device master file revision 2
6 As of device master file revision 3
7 Only if the device master file has been imported and if the DPV1 mode is selected in HW-Config.
8 With S7-DP the interrupts are not reported when the CPU is in the STOP mode.
9 As of device master file revision 4
10 Time stamping is currently only available in the S7 system environment.
6-8
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1
Function
2
Class 1 services
(parameter
assignment master,
e.g. PLC)
Class 2 services
(e.g. PG/OP)
DPV0
DPV1
slave
slave
4
6
X
X
X
X
X
X
X
X
X
5
7
X
X
5
7
X
X
8
X
8
X
X
9
X
10
9
X
Distributed I/O Device ET 200M
EWA-4NEB780600602-06