Fault-tolerant Solutions in PCS 7
3.3 Solutions for communication
Redundant components
The following components are configured redundantly:
● Electrical or optical network with Ethernet switches
● Switches, fiber optic cables and electrical connections
● Ring structures based on switches from the SCALANCE series.
You can find additional information on the switches used with PCS 7 in the section "Network
components (Page 46)".
Additional information
● Section "How to configure the redundant terminal bus on the basis of the Parallel
Redundancy Protocol (Page 107)"
● Section "How to configure the redundant terminal bus on the basis of the INTEL TEAM
mode (Page 108)"
● Documentation
● Manual
● Operating instructions
● Configuration manual
● Operating instructions
● Operating instructions
SCALANCE X204RNA EEC"
● Operating instructions
● Online help for SOFTNET IE RNA
3.3.3.4
Redundant, fault-tolerant terminal bus based on the Parallel Redundancy Protocol (PRP)
The section below describes the basic structure of a redundant fault-tolerant terminal bus using
the SIMATIC NET SOFTNET-IE RNA software. This software is based on the Parallel
Redundancy Protocol (PRP) as specified in IEC 62439-3.
Each PC station is connected to 2 separate redundant networks with two network adapters
each. The communications processes on the redundantly connected PC stations are organized
by the SIMATIC NET SOFTNET-IE RNA software.
The SIMATIC NET SOFTNET-IE RNA software package is required on each redundantly
connected PC station.
You can find additional information on this in the section "How to configure the redundant
terminal bus on the basis of the Parallel Redundancy Protocol (Page 107)".
The following diagram illustrates a sample configuration based on the SIMATIC NET
SOFTNET‑IE RNA software:
54
PCS 7 Released Modules
SIMATIC Net Twisted Pair and Fiber-Optic Networks
SIMATIC NET; Industrial Ethernet Switches SCALANCE X-400
SIMATIC NET; Industrial Ethernet Switches SCALANCE X-400
SIMATIC NET; Industrial Ethernet Switches SCALANCE X-200
SIMATIC NET; Industrial Ethernet; "SCLANCE X204RNA,
SIMATIC NET; PG/PC - Industrial Ethernet; SOFTNET‑IE RNA
Fault-tolerant Process Control Systems (V8.1)