York ECO HFC-410A User Manual
York ECO HFC-410A User Manual

York ECO HFC-410A User Manual

Packaged rooftop air-conditioning units

Advertisement

FORM 100.50-EG5 (108)
TM
Packaged Rooftop
Air-Conditioning Units
(Simplicity Elite with HFC-410a refrigerant)
00873VIP
ASHRAE
90.1
50 THROUGH 65 TONS
COMPLIANT
MEA
231-02-E

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ECO HFC-410A and is the answer not in the manual?

Questions and answers

Summary of Contents for York ECO HFC-410A

  • Page 1 FORM 100.50-EG5 (108) Packaged Rooftop Air-Conditioning Units (Simplicity Elite with HFC-410a refrigerant) 00873VIP ASHRAE 90.1 50 THROUGH 65 TONS COMPLIANT 231-02-E...
  • Page 2: Introduction

    Lower total cost of ownership • High effi ciency Eco rooftop units are optimized for HFC-410a refrigerant. YORK provides the FIRST standard product offering that meets the latest ASHRAE 90.1 energy effi ciency requirements. • Accurate ventilation control ensures that no more than the proper amount of ventilation air is utilized.
  • Page 3: Table Of Contents

    Table of Contents Introduction ...2 Features and Benefi ts ...4 Application Data ...8 Nomenclature ...13 Physical Data...14 Altitude and Temperature Corrections ...17 Cooling Performance Data ...19 Supply Fan Data ...23 Component Static Pressure Drops ...24 Exhaust Fan Data ...25 Electrical Data ...26 Controls ...28 General Arrangement Drawings ...32 Unit Weights ...36...
  • Page 4: Features And Benefi Ts

    Features and Benefi ts AIRFLOW CONFIGURATIONS Variable-Air-Volume – Eco units are available for single-zone variable-air-volume (VAV) applications. Supply fans are controlled to the supply duct static pressure setpoint, which can be reset via a BAS, or through an analog voltage input on the unit controller for optimized duct static pressure control.
  • Page 5: Filter Options

    COMMUNICATIONS BACnet MSTP (RS-485) Communications – This communication is available via optional Modlinc Gate- way. Communications to the unit are through a twisted pair, and the wire terminations are on the primary unit control board. Modbus RTU Communications – This communication is standard on every Eco unit and can be used in lieu of the BACnet communications (only one can be used...
  • Page 6: Evaporator Section

    CONDENSER FEATURES AND OPTIONS Scroll Compressors – Reliable, effi cient, trouble-free operation is the true measure of a packaged rooftop’s value. That’s why YORK Eco Packaged Rooftop Air Conditioners use established scroll compressor technology to deliver dependable, economical per- formance in a wide range of applications.
  • Page 7 ACCESSORIES Filter Switch – An optional dirty fi lter alarm can be pro- vided that will provide an alarm when the fi lters require cleaning. Magnahelic Filter Pressure Gauge – On units equipped with downstream fi ltration, a magnahelic fi lter gauge is included and visible on the exterior of the unit.
  • Page 8: Application Data

    In cases where space is limited, please call your local YORK representative for additional information. NOTE: 1. Under certain conditions these clearances may be encroached upon.
  • Page 9: Unit Orientation

    If the application calls for horizontal supply and return air, YORK can ship it from the factory as a horizontal unit. This option elevates the Supply Air need for fi...
  • Page 10: Traditional Overhead Vav Air Delivery System

    Exhaust/relief fans – In this application, a powered exhaust fan may be suitable, however careful consid- eration of the fan type is necessary. YORK offers a centrifugal powered exhaust fan to perform this function. Some manufacturers use a propeller exhaust fan, which cannot handle the static pressure requirements.
  • Page 11: Acoustical Considerations

    In the non-modulating exhaust system, the exhaust air- fl ow is constant whenever the exhaust fan is operating. This type of control should only be used to either assist a smoke purge system or when a system requires a constant volume of exhaust airfl ow. ACOUSTICAL CONSIDERATIONS The Eco unit is designed for lower sound levels than...
  • Page 12 FORM 100.50-EG5 (108) This page intentionally left blank JOHNSON CONTROLS...
  • Page 13: Nomenclature

    FORM 100.50-EG5 (108) Nomenclature JOHNSON CONTROLS...
  • Page 14: Physical Data

    Physical Data TABLE 3 – PHYSICAL DATA MODEL General Data Length without hood (inches) Width (inches) Height (inches) Compressor Data Quantity Type Unit Capacity Steps R410a Charge (SYS 1/2) (lb-oz) Supply Fan Quantity Type Size Motor Size Range (HP) Air Flow Range (CFM) Static Pressure Range (Total) Optional Supply Fan Quantity...
  • Page 15 TABLE 3 – PHYSICAL DATA (cont’d) MODEL Filters - 12" rigid 65%, 2" 30% prefilter (pre-fi lter position) Quantity Size (length x width) (in.) Total Filter Face Area (square feet) Filters - 12" rigid 95%, 2" 30% prefilter (pre-fi lter position) Quantity Size (length x width) (in.) Total Filter Face Area (square feet)
  • Page 16: Effi Ciency Ratings

    Physical Data TABLE 4 – EFFICIENCY RATINGS Model YPAL050 YPAL051 YPAL060 YPAL061 TABLE 5 – PHYSICAL DATA – UNIT EER Model YPAL050 YPAL051 YPAL060 YPAL061 TABLE 6 – PHYSICAL DATA - COMPRESSORS Compressors Utilized System 1 “Compr “Compr “Compr # 1” # 2”...
  • Page 17: Altitude And Temperature Corrections

    Altitude and Temperature Corrections The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The airfl ow rates listed in the standard blower perfor- mance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases.
  • Page 18: Altitude/Temperature Conversion Factor

    FORM 100.50-EG5 (108) FIG. 2. ALTITUDE/TEMPERATURE CONVERSION FACTOR JOHNSON CONTROLS...
  • Page 19: Cooling Performance Data

    Cooling Performance Data — TABLE 8 – COOLING PERFORMANCE DATA* - 50 TON (STANDARD CAPACITY) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 12000 14000 16000 18000 20000 22000 24000 12000 14000 16000 18000 20000 22000 24000 * Rated performance is at sea level.
  • Page 20: Cooling Performance Data - 051 Model

    Cooling Performance Data — TABLE 9 – COOLING PERFORMANCE DATA* - 55 TON (HIGH CAPACITY ) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 12000 14000 16000 18000 20000 22000 24000 12000 14000 16000 18000 20000 22000 24000 * Rated performance is at sea level.
  • Page 21: Cooling Performance Data - 060 Model

    Cooling Performance Data — TABLE 10 – COOLING PERFORMANCE DATA* - 60 TON (STANDARD CAPACITY ) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 12000 14000 16000 18000 20000 22000 24000 12000 14000 16000 18000 20000 22000 24000 * Rated performance is at sea level.
  • Page 22: Cooling Performance Data - 061 Model

    Cooling Performance Data — TABLE 11 – COOLING PERFORMANCE DATA* - 65 TON (HIGH CAPACITY ) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 12000 14000 16000 18000 20000 22000 24000 12000 14000 16000 18000 20000 22000 24000 Temperature of Air on Condenser Coil 85°F...
  • Page 23: Supply Fan Data

    Supply Fan Data TABLE 12 – 28" x 28" FORWARD-CURVED FAN Total Static Pressure (inches of water column) STD. AIR 12000 14000 16000 10.8 18000 12.7 20000 10.4 22000 12.9 17.6 24000 15.7 20.8 26000 19.1 24.5 TABLE 13 – 28" AIRFOIL FAN Total Static Pressure (inches of water column) STD.
  • Page 24: Component Static Pressure Drops

    Component Static Pressure Drops TABLE 14 – COMPONENT STATIC PRESSURE DROPS 050-061 MODELS Component 10,000 12,000 Evap Coil 50 Ton 0.19 0.24 Evap Coil 60 Ton 0.25 0.32 Return Air Bottom 0.05 Side 0.09 Rear 0.04 Filters 2" Throwaway 0.07 2"...
  • Page 25: Exhaust Fan Data

    18000 20000 22000 11.8 24000 15.1 26000 18.9 NOTE: For performance at operating points not included in these tables, consult your local YORK representative. JOHNSON CONTROLS Total Static Pressure (inches of water column) 10.1 11.1 14.1 16.4 17.6 FORM 100.50-EG5 (108) 15.1...
  • Page 26: Power Supply Voltage Limits

    Electrical Data ELECTRICAL SERVICE SIZING In order to use the electrical service required for the cool- ing-only Eco rooftop, use the appropriate calculations listed below from U.L. 1995. Based on the confi guration of the rooftop, the calculations will yield different MCA (minimum circuit ampacity), and MOP (maximum over- current protection).
  • Page 27: Supply And Exhaust Fan Motor Electrical Data - Odp

    TABLE 18 – SUPPLY AND EXHAUST FAN MOTOR DATA - ODP High Effi ciency Nominal Voltage Motor 208/3/60 230/3/60 460/3/60 14.0 13.8 21.7 20.0 10.0 28.2 26.0 13.0 41.0 38.0 19.0 53.0 48.0 24.0 66.0 62.0 31.0 84.0 72.0 36.0 106.0 98.0 49.0...
  • Page 28: Controls

    Morning warm-up, Economizer operation, Comfort, and Demand ventilation. For the maximum in system fl exibility, the YORK Eco² Packaged Rooftop Unit can be operated by either a typical 7-wire thermostat (2 cool/2 heat), a space tem- perature sensor, or stand-alone (VAV only).
  • Page 29: Economizer Operation

    the Return Air Temperature Setpoint, Morning Warm- Up ends when occupancy occurs (BAS, Intelli-Start, or contact closure), or when the Maximum Morning Warm- Up Time has expired. ECONOMIZER OPERATION The unit can be equipped with one of three types of optional economizers: dry-bulb, single-enthalpy, or com- parative-enthalpy.
  • Page 30 Controls (continued) proportionally controlled open and the Exhaust Fan is controlled ON. If the Building Pressure falls, the Exhaust Damper is proportionally controlled closed and the Ex- haust Fan is controlled OFF. The position of the Exhaust Damper in which the Exhaust Fan is controlled ON and OFF as well as the Building Pressure setpoint are user- selectable from the Rooftop Unit User Interface.
  • Page 31: Heating Operation

    is called from the thermostat, the Supply Fan will start. Ventilation functions (if equipped) will be permitted to run with an occupied signal. Economizer functions will operate with a “G” call and a call for cooling. HEATING OPERATION Thermostat Control If a 7-wire thermostat (2 Cool/2 Heat) controls the unit, all zone-temperature setpoint-control is maintained at TABLE 22 –...
  • Page 32: General Arrangement Drawings

    FORM 100.50-EG5 (108) General Arrangement Drawings BOTTOM SUPPLY / BOTTOM RETURN FIG. 3 – GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
  • Page 33: Side Supply/Rear Return Drawing

    FORM 100.50-EG5 (108) SIDE SUPPLY / REAR RETURN FIG. 4 – GENERAL ARRANGEMENT DRAWING LD08296 JOHNSON CONTROLS...
  • Page 34: Bottom Supply/Side Return Drawing

    FORM 100.50-EG5 (108) General Arrangement Drawings BOTTOM SUPPLY / SIDE RETURN FIG. 5 – GENERAL ARRANGEMENT DRAWING LD08370 JOHNSON CONTROLS...
  • Page 35: Curb Layout Drawing

    2. Curb confi guration for “bottom” return and “bottom” supply. 3, These drawings are not intended as construction documents for the fi eld-fabricated roof curbs. YORK will not be responsible for the unit fi t-up, leak integrity, or sound level for installation using fi eld-fabricated roof curbs.
  • Page 36: Unit Weights

    Unit Weights TABLE 23 – UNIT WEIGHTS Model Basic Unit* Economizers No Outside Air 25% Outside Air Fixed Position Maual Damper 25% Outside Air 2 Position Actuated Damper Full Modulation with Minimum Position Power Exhausts Fan, Motor, Modulating Damper and Hood Fan, Motor, VFD, Barometric Damper and Hood Gas Heat 375 MBH...
  • Page 37: Unit Corner Weights

    TABLE 25 – UNIT CORNER WEIGHTS Model Basic Unit Basic Unit w/ Econ. Basic Unit w/ Econ. & Heating Basic Unit w/ Econ. & Heating & Power Exhaust Model Basic Unit Basic Unit w/ Econ. Basic Unit w/ Econ. & Heating Basic Unit w/ Econ.
  • Page 38: Guide Specifi Cations

    Guide Specifi cations GENERAL Scope The requirements of the General Conditions, Supple- mentary Conditions, Division 1 and drawings apply to all work herein. Provide microprocessor-controlled, air-cooled, dou- ble-wall-construction, outdoor packaged rooftop air conditioning product of the scheduled capacities and performance as shown and indicated on the Drawings, including but not limited to: 1.
  • Page 39 Warranties Equipment shall include the manufacturer’s warranty not less than eighteen months from the date of shipment. Extended parts warranty [optional] shall be included for an additional one [fi ve] years Extended parts and labor warranty [optional] shall be included for an additional one [fi ve] years EQUIPMENT Product Specifi...
  • Page 40 Guide Specifi cations 2. Barometric Relief Damper: Building air exhaust shall be accomplished through barometric relief damp- ers installed in the return-air plenum. The dampers open relative to the building pressure. The opening pressure shall be adjustable. 2. On/Off, Fan-Powered Exhaust: A DWDI Class I or II forward-curved centrifugal exhaust fan shall be provided to exhaust building return air to relieve building static pressure.
  • Page 41 The intermediate pans shall have drop tubes to guide condensate to the main drain pan. Supply Fan Section 1. Fan: The fan section shall be equipped with a single double-width, double-inlet (DWDI), forward-curved [airfoil optional] centrifugal type wheel for horizontal discharge.
  • Page 42 Guide Specifi cations mechanically expanded into the end sheets. Coils are confi gured in a V-bank confi guration, with indi- vidual fl at coils rotated from the vertical plane for protection from hail damage for each condensing circuit. Condensing coils shall have a subcooler for more effi...
  • Page 43 EXECUTION Installation General: Installing contractor shall install rooftop unit(s), including components and controls required for opera- tion, in accordance with rooftop unit manufacturer’s writ- ten instructions and recommendations. Rooftop units shall be installed as specifi ed. 1. Unit(s) specifi ed shall include a protective covering membrane for such equipment being shipped by truck, rail, or ship.
  • Page 44 P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA Copyright © by Johnson Controls 2007 www.york.com ALL RIGHTS RESERVED Form 100.50-EG5 (108) Supersedes: Nothing...

This manual is also suitable for:

Eco 2 050Eco 2 051Eco 2 060Eco 2 061

Table of Contents