SYSTEM COMPONENT ADDRESSING
I/O MODULE
Module addressing
To carry out the addressing, connect to bus only 1 module at a time.
1.
Set the system and put it into communication with all devices
2.
Disconnect bus (C) of module A
3.
Access to the parameter scripture mask via modbus (see sideway)
4.
Point the IO module provisionally addressed at 7 (B)
5.
At parameter 788 of module write 8
6.
Point the IO module just addressed at 8 (B)
7.
At parameter 788 check with a reading test, if the answer is 8
8.
Connect the bus (C) of the module A
*
If the module is the last element of the network connect a termination
resistance 120 Ω 1/4 W ( customer care)
C
230V
-
+
1 2 3 4 5 6 7
8 9
11 12
A
1
2
3
4
13 14 15 16 17 18 19 20 21 22 23 24
RS485
230V
-
+
1 2 3 4 5 6 7
8 9
11 12
B
1
2
3
4
13 14 15 16 17 18 19 20 21 22 23 24
1
select
*
2
select
select
4
select