Advanced Setting Menu
SETTING DESCRIPTION
000
Hardware Version
001
Firmware Version
002
Temperature - Room
003
Temperature - Roof Cavity
004
Screen Brightness - Maximum
005
Screen Brightness - Minimum
006
Boost Time
007
Recycle Enable
008
Recycle Speed
009
Recycle Temperature - Maximum
010
Recycle Temperature - Minimum
011
Temperature Set - Threshold
012
Temperature Set - Differential
013
Reserved
014
Reserved
015
Dew Point - Start
016
Dew Point - Control Level
017
Filter Used Percentage
018
Filter Reset
1. If your roof cavity or room temperature readings are inaccurate, use these settings to calibrate them.
2. If RECYCLE
is enabled and the roof cavity sensor reading goes above the maximum recyle temperature setting or goes below the minimum recycle
temperature setting, then recycle mode will activate.
3. To reset the filter change 018 setting value to 10 and press SELECT
12
RANGE
N/A
N/A
-10°C - 10°C
-10°C - 10°C
0 - 100%
0 - 100%
0 min – 60 min
0 - 1
0 - 100%
Recycle Min. Temp - 50°C
0°C - Recycle Max. Temp
0°C - 5°C
0°C - 20°C
N/A
N/A
-5°C - 5°C
0 - 5
0 – 100%
0 - 100
.
DEFAULT
3.1
3.4
-2.5°C
0°C
80%
20%
20 min
1
1 = enabled
0%
30°C
5°C
1.5°C
5°C
N/A
N/A
0°C
1
0%
0
NOTE
1
1
2
2
3