DURAG D-LX 200 Operating Instructions Manual

DURAG D-LX 200 Operating Instructions Manual

Compact flame monitor
Hide thumbs Also See for D-LX 200:
Table of Contents

Advertisement

D−LX 200
D−LX 720
Compact Flame Monitor
Before starting any work, please read the Operating instructions!
Artikelnr.:
1 119 619
GmbH · Kollaustraße 105 · 22453 Hamburg · www.durag.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D-LX 200 and is the answer not in the manual?

Questions and answers

Summary of Contents for DURAG D-LX 200

  • Page 1 D−LX 200 D−LX 720 Compact Flame Monitor Before starting any work, please read the Operating instructions! Artikelnr.: 1 119 619 GmbH · Kollaustraße 105 · 22453 Hamburg · www.durag.de...
  • Page 2 US market. Documentation to ANSI Z535 is available on request. Order addresses can be found on page 159;  or parts thereof may not be reproduced or distributed without express permission from DURAG GmbH, irrespective of how this is done, in what language or by what medium, electronic or mechanical;...
  • Page 3: Table Of Contents

    Contents Contents General Information on Operating instructions ..................9 Explanation of Symbols ......................10 Limitation of liability ........................12 Information regarding warranty ....................12 Spare parts ..........................12 Customer service ........................13 Copyright ............................ 13 Trademarks ..........................13 Safety instructions General safety instructions ......................
  • Page 4 Drop-down menus ........................145 16.5 Fault messages ........................149 16.6 Structure of the stored data sets ..................... 149 Appendix II: Modbus 17.1 General information ......................... 153 17.2 DURAG Modbus DataMap ...................... 155 DURAG GROUP company addresses D−LX 200, D−LX 720...
  • Page 5 Contents Index of illustrations Figure 3.1: Ex-type label Compact Flame Monitor D−LX 200 ............. 31 Figure 5.1: Type label D−LX 200, D−LX 720 ..................50 Figure 5.2: Explanation of terms on the type label D−LX 200, D−LX 720 .......... 51 Figure 5.3: Type label D−LX 200 Ex, D−LX 720 Ex ................
  • Page 6 Contents Index of tables Table 3.1 Zone classification DURAG--equipment ................24 Table 3.2 DURAG-equipment EPL ...................... 25 Table 3.3 Permitted seals / 84Ex-equipment..................27 Table 3.4 Permitted seals / 87Ex-equipment..................28 Table 5.1: Default settings D−LX 200, D−LX 720 ................48 Table 5.2: Suitability of the device versions (spectral range) ...............
  • Page 7 D−LX 200 D−LX 720 Compact Flame Monitor General Information on Operating instructions Explanation of Symbols Limitation of liability Information regarding warranty Spare parts Customer service Copyright Trademarks...
  • Page 9: General

    Order addresses can be found on page 159;  or parts thereof may not be reproduced or distributed without express permission from DURAG GmbH, irrespective of how this is done, in what language or by what medium, electronic or mechanical; ...
  • Page 10: Explanation Of Symbols

    1 General Explanation of Symbols To make the text of this Operating instructions easily understandable, elements such as safety instructions, warnings, tips, keypad symbols, addresses etc. are represented differently. Warnings in this Operating instructions are identified with symbols. Instructions are introduced with key words that highlight the extent of the hazard. All instructions must be unconditionally and carefully observed to avoid accidents, injury and material damage.
  • Page 11 1 General General warning sign Hot surface Electric current Moisture Electrostatically explosive atmosphere endangered components (ESD) Other symbols used Apart from the warning notices and safety instructions, the following general instructions and associated pictograms are used to draw particularly important information to your attention: Before starting any work, please read the Operating instructions! Instructions relating to environmental protection...
  • Page 12: Limitation Of Liability

    1 General  A (→) indicates that the following term is explained in the glossary. × × in a list indicates that something must not be done or that something is not suitable.  Unless otherwise stated, all measurements are in mm ...
  • Page 13: Customer Service

    Information about responsible offices and partners can be obtained at any time over the Internet. See the manufacturer addresses listed on page two, or DURAG GROUP company addresses on page 159. Copyright This Operating instructions must be kept confidential. It is intended exclusively for personnel employed to use the Compact Flame Monitor.
  • Page 14 1 General D−LX 200, D−LX 720...
  • Page 15 D−LX 200 D−LX 720 Compact Flame Monitor Safety instructions General safety instructions Hazards due to electrical equipment Hazard due to hot, aggressive or explosive gases Hazard to the device due to purge air failure Designated use Avoidance of consequential damage in the event of a system fault Qualified personnel...
  • Page 17: Safety Instructions

    They serve to avert dangers to life and limb of users and maintenance personnel and to prevent damage to property. General safety instructions The DURAG Compact Flame Monitor D−LX 200, D−LX 720 is in accordance with the current state of technology and the recognised technical safety regulations, hazards can nevertheless arise.
  • Page 18: Hazards Due To Electrical Equipment

    Cables must be routed so as to exclude the possibility of a risk of accident by persons stumbling over them or hanging from them. We recommend a power supply that guarantees reliable isolation between the primary and secondary circuits (e.g. the DURAG D-NG 24/05). CAUTION! Damage to electronic components due to electrostatic discharge (ESD) Electronic components are becoming increasingly small and complex.
  • Page 19: Hazard To The Device Due To Purge Air Failure

    2 Safety instructions  The Compact Flame Monitor is mounted directly at the boiler. In the case of systems with a low danger potential (ambient pressure, low temperatures, no health hazard), mounting/removal can occur during system operation. The applicable provisions and safety regulations for the system must be complied with and any necessary and appropriate protective measures taken.
  • Page 20: Qualified Personnel

    Qualified personnel The operating company's personnel who are responsible for safety must ensure that work on DURAG devices or systems is only carried out by qualified specialist personnel, whose competence has been verified by responsible experts. In the event of unqualified work on the device or failure to comply with the warnings provided in this manual or attached to the device, physical injuries and/or damage to property can occur.
  • Page 21 D−LX 200 D−LX 720 Compact Flame Monitor Explosion protection Basics Classification of the equipment groups into categories 3.2.1 Zone classification 3.2.2 Ignition protection categories 3.2.3 Temperature classes 3.2.4 EPL Equipment Protection Level Equipment with pressure proof encapsulation „Ex d“ Ignition protection category "Ex n_" (Gas) Protection through housing “Ex t“...
  • Page 23: Basics

    Ex-devices. Should you require information that is not sufficiently covered in this document, please request the required information from the relevant agent of DURAG GmbH. Our Support and Service team will also gladly answer questions regarding products and applications from the DURAG GROUP.
  • Page 24: Classification Of The Equipment Groups Into Categories

    Equipment group II is divided into categories 1, 2, and 3 with a decreasing level of safety. DURAG-equipment is available in categories 2 (high degree of safety) and 3 (low degree of safety) for gaseous (G) and dusty (D) Ex-atmospheres.
  • Page 25: Equipment With Pressure Proof Encapsulation „Ex D

    Each zone can be assigned a precise Equipment Protection Level without an additional risk assessment. The following allocations for DURAG-equipment are relevant: Zone Zone 1...
  • Page 26: Ignition Protection Category "Ex N_" (Gas)

    3 Explosion protection WARNING! Danger due to explosive atmosphere! Explosions can endanger the health and safety of anyone present and cause considerable material damage. Gas atmosphere: In order not to inappropriately alter the gap dimensions:  Do not retro-fit the housings. ...
  • Page 27: Protection Through Housing "Ex T" (Dust)

    3 Explosion protection Protection through housing “Ex t“ (dust) This ignition protection category is used for equipment groups and categories II 2D (zone 21) and II 3D (zone 22). Equipment of this ignition protection category have a dust-tight housing (IP6X) and avoid hot surfaces that could ignite explosive dust.
  • Page 28: Table 3.4 Permitted Seals / 87Ex-Equipment

    3 Explosion protection A process that generates a strong charge is a procedure by which charge quantities are generated per time that are high in comparison with the charge dissipation and hence can accumulate. Typical procedures are e.g. running drivebelts, pneumatic bulk material conveyor or multiphase liquid flows. Experience shows that exclusively manual procedures do not generate a strong charge.
  • Page 29: Fm Markings

    FM Markings The FM standards apply to the type approval of Ex-equipment in North America. Correspondingly marked DURAG-equipment is approved for installation in so-called "hazardous (classified) locations". The articles of the National Electric Code (NEC) are the basis for classification.
  • Page 30 3 Explosion protection The requirements of the Compact Flame Monitor housings regarding internal explosions are met through constructive measures. In addition, the choice of corresponding components rules out that under normal circumstances lead to incidents caused by sparks in or on the equipment housing. WARNING! Danger due to explosive atmosphere! Explosions can endanger the health and safety of anyone present and cause...
  • Page 31: Safety With Ex-Equipment

    3 Explosion protection Safety with Ex-equipment Equipment with approval for the Ex- area may only be installed, commissioned and maintained by staff with knowledge of Ex-equipment! The technical knowledge regarding Ex-equipment must correspond to the region where the equipment is installed and/or maintained (ATEX, FM, CSA...). National assembly and construction regulations apply (e.g.
  • Page 32 3 Explosion protection Further information on the type label can be found in the following chapter and in chapter 5.8 from page 43. 3.9.1 Identification of ATEX zone(s) on the type label (ATEX compliance) Equipment for use in Ex−zone 1 or Ex−zone 21 can be identified for example from the following information on the type label: Equipment group II = Other areas with a risk of explosion (not mining)
  • Page 33 D−LX 200 D−LX 720 Compact Flame Monitor Functional safety Relevant Standard Functions of the flame monitor Generally valid parameters of the flame monitor Low and high demand mode of operation Low demand mode 4.5.1 Proof test for low demand mode of operation High demand mode...
  • Page 35: Functional Safety

    Safety Integrity Level (SIL) were performed. Within the product family D-LX 200/720 it is only valid for the variants D-LX 200…-20, D-LX 200…-40, D-LX 720…-20 and D-LX 720…-40. The safety relevant...
  • Page 36: Generally Valid Parameters Of The Flame Monitor

    4 Functional safety Generally valid parameters of the flame monitor Independent of the mode of operation of the flame monitor the following parameters are valid Assessment according to IEC 61508 1-7 Type according to IEC 61508-2 Type B Hardware fault tolerance (HFT) Applicable for operation up to SIL3 Low and high demand mode of operation...
  • Page 37 4.5.1 Proof test for low demand mode of operation You can perform the simple and the extended proof test (see below) yourself. Use the test kit for D-LX 200/720 for this purpose. Pay attention to the detailed operational manual for the test kit.
  • Page 38 T1 in years, as well as the interval T2 in years of demand of the safety- relevant function. For the calculation you can receive a form from DURAG. It allows the calculation of PFD in dependence of these factors. The following figure shows the calculation form for one example calculation.
  • Page 39: High Demand Mode

    4 Functional safety High demand mode For use in an application with high demand mode operation the following parameters are valid: Mode of operation High Demand Mode λ + λ 3061 FIT λ 2086 FIT λ 46 FIT 99.12% 2.7 x 10 Proof test interval 15 years The proof test interval is longer as the design life time of 10 years which is...
  • Page 41 D−LX 200 D−LX 720 Compact Flame Monitor Product description Instructions for delivery Items delivered / Version variants Accessories 5.3.1 Connection cable 5.3.2 Optional, factory settings Instructions about the product Designated Use, Applications Selection criteria for Compact Flame Monitor D−LX 200, D−LX 720 Conformity Identification of the product Type code...
  • Page 43: Product Description

    Check that the shipment is complete and undamaged. Any transport damage must be immediately reported to the carrier and to the DURAG GROUP. For addresses see page 159. Items delivered / Version variants Items delivered for the standard system D−LX 200, D−LX 720: Deliverable variations are: D−LX 200 UA, D−LX 720 UA...
  • Page 44 5 Product description D−LX 200 UA/84Ex, D−LX 720 UA/84Ex Compact Flame Monitor, Ex version with UV photo-diode (= 190 nm to 520 nm) D−LX 200 UAF/84Ex, D−LX 720 UAF/84Ex Compact Flame Monitor, Ex version with UV photo-diode (= 280 nm to 410 nm) D−LX 200 IG/84Ex, D−LX 720 IG/84Ex Compact Flame Monitor, Ex version with IR photo-diode (= 780 nm to 1800 nm)
  • Page 45: Accessories

    5 Product description Accessories Ordering code D−LX 200 D−LX 720 Article no. Figure D-ZS 033 – I 1 101 520 Swivel mount with G 1¼ “ threaded connection D-ZS 112 1 115 222 Adapter for attaching D−LX 200 an G 1 “threaded connection D-ZS 133 –...
  • Page 46 5 Product description D-ZS 150 Interface converter for connecting an RS-485 device to a USB port, 1 115 263 configurable by DIL switch, with status LEDs, incl plug-in screw terminals and USB cable D-ZS 129-30 Bargraph indicator to represent 1 101 528 flame intensity (19“...
  • Page 47 D−LX 200 D−LX 720 Article no. Figure in m Connection cable (PVC, screened, with cable gland) 1 115 730 D-LX 200 CBL-V1C-PCG-03 1 115 064 D-LX 200 CBL-V1C-PCG-05 1 114 746 D-LX 200 CBL-V1C-PCG-10 1 115 436 D-LX 200 CBL-V1C-PCG-15...
  • Page 48: Instructions About The Product

    5 Product description Analogue output 0 - 20 mA 4 - 20 mA 1 sec. Safety time 2 sec 3 sec 5 sec. Table 5.1: Default settings D−LX 200, D−LX 720 With the FM approved versions -30 and -40 the maximum permitted safety time is 4 s, in other words the 5 s setting must not be used! Instructions about the product The Compact Flame Monitor D−LX 200, D−LX 720 is a safety device...
  • Page 49: Selection Criteria For Compact Flame Monitor D−Lx 200, D−Lx 720

    5 Product description  Operation with flue gas recirculation  Claus plants etc. The parameters stated in the Appendix: Technical data from page 113 in particular the ambient conditions, must be observed and adhered to ensure correct use of the D−LX 200, D−LX 720 and its variants! The D−LX 200, D−LX 720 has been developed, prepared, tested and documented in accordance with the appropriate safety standards.
  • Page 50: Conformity

    5 Product description Conformity The D−LX 200, D−LX 720 has been developed, prepared, tested and documented in accordance with the appropriate safety standards. If the handling and safety instructions described for configuration, assembly, use for the proper purpose and maintenance are complied with, no hazards normally arise from the device in respect of damage to property or the health of persons.
  • Page 51 5 Product description D-22453 Hamburg www.durag.de D-LX 200 UA-20/MP Part-No.: 111222 Ser.-No.: 1234567 IP65 Dat.: 13.10.11 U: 24Vdc/5W 4-20 mA -40...+85°C SZ/ST: 1s Fuse F1: MST 250, 500m A slow Pr od-ID-No: CE-0085BU0114 0085 Made in Germany Description Device type...
  • Page 52: Type Code

    5 Product description Figure 5.3: Type label D−LX 200 Ex, D−LX 720 Ex Information on the meaning of the details on the Ex-type label can be found in Figure 3.1 on page 31. Type code The type names have the form D-LX bbb ccc-dd/ee/ffff/ggg. Position Item Meaning...
  • Page 53 Plastic housing with plug-in cover, no explosion protection Aluminium housing, (only with /ffff=84Ex or 85Ex) Aluminium housing with plug-in cover, (only with /ffff=0000 or 87Ex or 86Ex), only from 2014 Stainless steal housing D-LX 200 (only with /ffff=84Ex) /ffff Applicability for special environment conditions No item...
  • Page 54: Information Regarding Warranty

    We point out that the contents of this device manual are not part of an earlier or existing agreement, commitment or a legal relationship or are meant to modify these. The warranty for the devices of the DURAG GROUP is generally 12 months from date of delivery. All obligations result from the respective sales contract, which also contains the complete and authoritative warranty provisions.
  • Page 55 D−LX 200 D−LX 720 Compact Flame Monitor Layout and function Functional description 6.1.1 Ultraviolet Flame Sensor 6.1.2 Infrared flame sensor 6.1.3 Self-monitoring 6.1.4 Error shutdown Device description...
  • Page 57: Layout And Function

    6 Layout and function 6 Layout and function This chapter explains the operational characteristics of the Compact Flame Monitor and how the relevant components interact. Functional description The Compact Flame Monitor D−LX 200, D−LX 720 comprises an optical flame sensor and a control unit in one housing. The flame sensor converts the light signal from the flame into an electrical signal, while the control unit ensures self-monitoring, evaluates the flame signal and communicates the result.
  • Page 58 6 Layout and function Figure 6.3: Functional diagram In both microcontrollers for control and monitoring of the safety-relevant flame monitor functions and self-monitoring, both the static and the dynamic flame signals, depending on the set switching threshold (frequency, intensity), are evaluated for the Flame ON or Flame OFF signal.
  • Page 59 6 Layout and function The filter is opaque in the visible spectral range, and therefore appears black to the human eye. The photo-diode is visible through the lens of the flame monitor. 6.1.2 Infrared flame sensor The IR radiation zone of a flame is extensive in many cases and very intensive relative to the UV radiation.
  • Page 60: Device Description

    6 Layout and function 6.1.4 Error shutdown If an error is detected in the safety-relevant software and hardware components during internal self-monitoring of the flame monitor, an error shutdown and internal lockout must be triggered. The relays of the flame signal and readiness for operation signal drop out and the Fault (Error) LED in the front panel illuminates, while the Power LED starts to flash (for meaning of LEDs see page 65).
  • Page 61 6 Layout and function Figure 6.5: D−LX 200 Ex… Characteristics of the Compact Flame Monitor:  Consequent dual-channel micro-controller system (Chan. 1 and Chan. 2) for controlling and monitoring safety-relevant flame monitor functions with continous self-monitoring,  A switch-over for the range selection is possible by switching the flame monitor to a different set of parameters (intensity and frequency switching threshold, gain characteristic curve), ...
  • Page 62 6 Layout and function Description Front part of the housing with circuit boards Gasket M4 x 130 screw M72x3 union nut G 1¼" front part thread, optional: (→) NPT 1¼“ female M4 locking screw (screwable from inside) Hood G 1½" purge air connection, optional: (→) NPT 1½“ female Cable gland for connection cable (optional) /MP3 plug connection for device versions Plug-in cover...
  • Page 63 6 Layout and function Description Front part of the housing with circuit boards Gasket M4 x 130 screw Hood Cable gland for connection cable Fibre optic adapter optional) /MP3 plug connection for device versions Plug-in cover M3 x 10 screw Figure 6.7: Exploded drawing D−LX 720 D−LX 200, D−LX 720...
  • Page 64 6 Layout and function Description Ex-middle section (with circuit boards!) Quad-ring (sealing ring) Lens insert module M 72 x 3 union nut Front part thread G 1 ¼", optional :NPT 1 ¼" female M4 locking screw (screwable from inside) Ex-hood G ½"...
  • Page 65: Table 6.1: Meaning Of The Leds

    6 Layout and function The LEDs displayed in the inspection window on the rear side of the device have the following meanings: Intensity (green) The intensity of the flame is higher than ➀ the switching threshold as set for intensity. Switch Error (red) For at least one of the adjustable parameters, the setting for the switch...
  • Page 66 6 Layout and function D−LX 200, D−LX 720...
  • Page 67 D−LX 200 D−LX 720 Compact Flame Monitor Installation, commissioning Safety Transportation Installation 7.3.1 Instructions for selecting a suitable installation location 7.3.2 Attaching the flange Opening the Ex-device housing Closing the Ex-housing hood Electrical connection 7.6.1 Cable and screen Installation, purge air supply Commissioning Dismantling and disposal of the D−LX 200...
  • Page 69: Installation, Commissioning

    7 Installation, commissioning 7 Installation, commissioning In this section, we explain the key points for installing the Compact Flame Monitor and how to connect the electronics and the purge air. Safety WARNING! High voltage. Danger of fatalities due to electrical current! Coming into contact with live parts poses a direct risk of fatalities.
  • Page 70: Transportation

    7 Installation, commissioning CAUTION! The supply with purging air must also be reliably secured when the plant is in shutdown. The purge air is necessary for the protection of systems installed to the burner. Components are shielded from hot and/or aggressive gases and dust by it.
  • Page 71 7 Installation, commissioning For optimum alignment with the flame, various adjustable ball flanges from the D-ZS 033 can be delivered (see Figure 7.2). Dimensional drawing of the swivel mount D−ZS 033−I Figure 7.2: Dimensional drawing of swivel mount (optional for D−LX 200) D-ZS 033-I) Key: Item Qty.
  • Page 72: Opening The Ex-Device Housing

    7 Installation, commissioning Opening the Ex-device housing Figure 7.3: Safety screw 1. Loosen the safety screw (hex socket) with a few anti-clockwise turns. A captive screw is used, in other words it cannot be completely unscrewed in this direction. Figure 7.4: Release the housing hood 2.
  • Page 73 7 Installation, commissioning Figure 7.5: Remove the housing hood 3. Carefully pull back the housing hood in a straight line to the back. The housing hood may be swung out of the axis only when the circuit boards are completely free (see Figure 7.7).
  • Page 74: Closing The Ex-Housing Hood

    7 Installation, commissioning Figure 7.7: When pulling the housing hood, do not slip it onto the circuit boards. 4. Hold on well to the housing hood when pulling as it is unexpectedly heavy! Do not let the heavy housing hood slip onto the circuit boards; the circuit boards are not designed to support the weight of the housing hood.
  • Page 75 7 Installation, commissioning Figure 7.9: Move the housing hood along the longitudinal axis when pushing 1. Push the housing hood in a straight line from behind. To do this move the housing hood along the longitudinal axis of the device. Do not rest the heavy housing hood on the circuit boards;...
  • Page 76: Electrical Connection

    7 Installation, commissioning Figure 7.11: Correctly closed housing This is then the case when the safety screw is directly next to the red point of the Ex-middle section. If the external thread sits correctly in the internal thread, the housing hood is easy to unscrew.
  • Page 77 In order to exclude possible disturbances due to transient currents on the protective conductor (e.g. currents from an ignition device to protective conductor potential), DURAG D-ZS 117-I insulators can be inserted between the sighting tube and the flame monitor. D−LX 200, D−LX 720...
  • Page 78 7 Installation, commissioning In this case the tube or hose line for the purge air connection of the flame monitor must also comprise non-conductive material. After assembly and connection as set out in the dimension drawings and connection plans, the compact flame monitor D−LX 200, D−LX 720 is ready for operation as soon as the power is connected.
  • Page 79 7 Installation, commissioning CAUTION! Electrical safety After installation of the Compact Flame Monitor the earth cable must be connected separately for Ex-devices! For copper earth cables a suitable connecting part must be used. As an option, the D−LX 200, D−LX 720 can be fitted with a plug connection (this option is not available for hazardous areas).
  • Page 80: Installation, Purge Air Supply

    7 Installation, commissioning 7.6.1 Cable and screen The Compact Flame Monitor D−LX 200, D−LX 720 is designed for switching 24 V⎓ voltages via the operation readiness contact and the flame contact. The contacts can generate sparks when switching a load, which, in the case of long line lengths, can affect other switching circuits.
  • Page 81 7 Installation, commissioning recommended that the thermal insulator D-ZS 117 I (see page 45) is screwed on between the flame monitor and sighting tube and/or D-ZS 033-I swivel mount. It should however always be ensured that the Compact Flame Monitor does not exceed the maximum operating temperature of +85°C.
  • Page 82: Commissioning

    7 Installation, commissioning Purge air connection 1/2" screw fastening with female pipe thread commissioning Figure 7.17: Purge air connection When using a fibre optic system, the purge air supply of the D−LX 720 is ensured via the supply for the fibre optic adapter. Information regarding its assembly and installation can be found in the description of the optional D−LL 703/704 fibre optic system.
  • Page 83: Dismantling And Disposal Of The D−Lx 200

    7 Installation, commissioning WARNING! Danger of injury through insufficient qualifications! Incorrect handling and operation can result in serious injury and material damage. Only allow work to be performed by appropriately trained specialists (see Chapter 2.7 from page 20). Particular care must be taken to ensure that the warnings on operator protection and measuring system protection specified in this Manual are known and adhered to.
  • Page 84 7 Installation, commissioning The symbol on the product or its packaging indicates this product cannot be treated as normal household waste. It must be taken to a collection point for the recycling of electrical and electronic devices. Your contribution to the correct disposal of this product protects the environment and the health of your fellow men.
  • Page 85 D−LX 200 D−LX 720 Compact Flame Monitor Adjusting the flame monitor Range selection Adjusting the thresholds Setting the amplification characteristics curve Setting the Modbus address Setting procedure 8.5.1 Objective of the setting 8.5.2 Adjustment by means of analogue output/LED 8.5.3 Setting using D−LX 200 InformationCentre Safety time Modbus...
  • Page 87: Adjusting The Flame Monitor

    Should you have further questions regarding the evaluation software, please use our Support and Service. The addresses and telephone numbers for your DURAG agent can be found on page 159 (DURAG GROUP company addresses). DANGER! Danger from electrical operating resources...
  • Page 88: Range Selection

    8 Adjusting the flame monitor both switches must always (simultaneously, within 8s) be switched and moved to the same position. The D−LX 200, D−LX 720 has thresholds for the intensity (Intens.) and flame flicker frequency (Freq.). The thresholds are operated by means of rotary switches.
  • Page 89: Adjusting The Thresholds

    8 Adjusting the flame monitor Adjusting the thresholds Along with the usual threshold for flame intensity (Figure 8.3) D−LX 200, D−LX 720 also has the possibility of using the different flicker frequencies for the flame and background light (Figure 8.4) for deciding between flame OFF and flame ON.
  • Page 90 8 Adjusting the flame monitor Chan. 2 Chan. 1 No. 3 Figure 8.2: Front panel D−LX 200 The rotary switches that are located above each other (Figure 8.2: Rotary switches with identical hatching) must be re-set to the same setting within 8 seconds.
  • Page 91: Setting The Amplification Characteristics Curve

    8 Adjusting the flame monitor Figure 8.4: Setting the flicker frequency [Hz] of the flame With the threshold of the flicker frequency, switch position 0 (zero) means a deactivation of the threshold. The detection of periodic signals is deactivated. With a switch position > 0 (zero) a threshold is established. The measured flicker frequency of a flame must exceed this threshold in order for a flame ON signal to be given (see Figure 8.4).
  • Page 92 8 Adjusting the flame monitor With the S3 and S4 MODE switches (both on circuit board No. 2) 8 different gain characteristic curves can be pre-selected (Figure 8.5: V1-V8) for different combustion ratios. The steeper the selected gain characteristic curve, the higher the amplification of the flame monitor and the more sensitive the reaction to radiation from the flame.
  • Page 93: Setting The Modbus Address

    8 Adjusting the flame monitor Amplification characteristics Switches S3 and S4 Range A Range B curve Switch setting Switch setting DIP position* V7** the DIP positions 1 and 2 (greyed out) must not be changed under any circumstances! (see chapter 8.6 page 99) Default delivery settings Table 8.1: Setting the gain characteristic curve on MODE switches S3 and S4 When setting the gain characteristic curve, always ensure that the MODE...
  • Page 94: Setting Procedure

    8 Adjusting the flame monitor With regard to this, refer to the information and instructions regarding the setting of the Modbus slave address in chapter 8.7.2 from page 101 onwards. Setting procedure The factory settings as delivered (for thresholds and gain characteristic curves) can be adjusted by the operator if they should prove to be inadequate for the current application.
  • Page 95 8 Adjusting the flame monitor 8.5.2 Adjustment by means of analogue output/LED Before commencing adjustment work on the Compact Flame Monitor (after disconnecting the power to the device!) loosen and remove the four recessed- head screws and push the hood back. CAUTION! Before removing the hood the power to the device must be disconnected! ...
  • Page 96 8 Adjusting the flame monitor Start Basic setting (rotary/gain switch) Gain characteristic curve = V8 all rotary switches = 0 Burner "OFF" (Background radiation monitoring) "Reduce" Current output gain characteristic curve < 5/8 mA (see gain characteristic " Flame " LED OFF curve settings) (Background radiation adaptation) Has the...
  • Page 97 8 Adjusting the flame monitor If possible, make the adjustments to the flame monitor in such a way that the flame monitor indicates 0 or 4 mA with Flame OUT and 20 mA with Flame ON. The flame monitor must in any case prevent the simulation of a flame in all operating states and different firing conditions.
  • Page 98 8 Adjusting the flame monitor Start Basic setting (rotary/gain switch) Gain characteristic curve = V8 all rotary switches = 0 Burner "OFF" (Background radiation monitoring) "Reduce" Flame Intensity gain characteristic curve < 25 % (see gain characteristic " Flame " LED OFF curve settings) (Background radiation adaptation) Has the...
  • Page 99: Safety Time

    In the interests of safety, adjustments to the flame monitor should only be made by correspondingly trained staff. DURAG offers appropriate training courses in this respect. Under no circumstances must switch settings 1 and 2 (regarding safety time) on DIP switches S3 and S4 (see Figure 8.6 and Table 8.1 on page 92) be...
  • Page 100: Modbus

    Therefore this description does not present complete information about all aspects of the Modbus protocol. General information regarding Modbus and the DURAG Modbus can be found in the separate DURAG Modbus manual and on-line at (http://www.modbus.org/). The (→) RS-485/485/field bus interface of the D−LX 200, D−LX 720 is for provision of parameters and settings, and the enquiring on the current status.
  • Page 101: Table 8.3: X2 Jumper Setting

    8 Adjusting the flame monitor 8.7.1 Hardware and general conditions The Compact Flame Monitor D−LX 200; D−LX 720 is fitted with an RS485/Modbus interface. The RS485/Modbus data connection is established via terminals 7 (RS485 A) and 8 (RS485 B) and the pre-assembled connection cable via the pink (RS485 A) and grey (RS485 B) cores.
  • Page 102 8 Adjusting the flame monitor For setting the amplification characteristics curve and the Modbus address (option) you have to remove the hood completely. For this you have to unscrew the four hexagon socket screws in the front end of the hood When delivered the Modus slave address is pre-set to "1".
  • Page 103: Table 8.4: Setting The Mode Switch S5

    8 Adjusting the flame monitor Modbus ADDR 6 … Modbus ADDR 9 … Modbus ADDR 64 DIP position 7 is reserved! Delivery pre-setting Table 8.4: Setting the MODE switch S5 The analogue output range indicated on the type label must match the one set for the device! D−LX 200, D−LX 720...
  • Page 104 8 Adjusting the flame monitor D−LX 200, D−LX 720...
  • Page 105 D−LX 200 D−LX 720 Compact Flame Monitor Maintenance Customer Service Information Safety Maintenance intervals Maintenance work Fault 9.5.1 Fault messages 9.5.2 Warning with different switch settings 9.5.3 Harmonic Detection...
  • Page 107: Maintenance

    Customer Service Information If desired the maintenance can also be undertaken by DURAG GmbH. We will gladly explain the advantages of a maintenance contract for your company to you. Also the commissioning of the D−LX 200, D−LX 720 can be performed by DURAG.
  • Page 108: Maintenance Intervals

    9 Maintenance CAUTION! Damage to electronic components due to electrostatic discharge (ESD) Electronic components are becoming increasingly small and complex. Their susceptibility to damage from electrostatic discharge is increased accordingly. To protect these components, measures must be undertaken to prevent electrostatic discharge for all work performed at the open device (ESD protection).
  • Page 109: Fault

    8 x or more internal fault Note the number of times the light flashes; Contact DURAG Service; On-site repair is probably not possible. Table 9.1: Fault messages Activating the reset button on the rear of circuit board no. 3 acknowledges the fault status and, as a rule, allows the flame monitor to continue functioning after a restart.
  • Page 110 9 Maintenance the "Switch Error" LED on the rear of the device illuminates red (see Figure 8.2 on page 90) Should the difference occur for longer than 8s than an error shutdown is triggered (see also Table 6.1 on page 65). 9.5.3 Harmonic Detection The D−LX 200, D−LX 720 can undertake (→) harmonic detection for safety purposes.
  • Page 111 D−LX 200 D−LX 720 Compact Flame Monitor Appendix: Technical data 10.1 Technical data for the basic device 10.2 Technical data for versions for hazardous areas 10.3 Technical data of the sighting tube connection, purge air connection 10.4 Factory Settings (Default) 10.5 Technical data of the integrated flame sensor 10.6...
  • Page 113: Appendix: Technical Data

    10 Appendix: Technical data 10 Appendix: Technical data 10.1 Technical data for the basic device approx. 80 x 80 x 250 mm approx. 80 x 80 x 175 mm Dimensions (incl. purge air connection) (without purge air connection) Weight approx. 1.2 kg Permitted ambient temperature -40 °C to +85 °C Permissible atmospheric...
  • Page 114: Technical Data For Versions For Hazardous Areas

    (incl. purge air connection) Weight approx. 3,2 kg Depends on device Permitted ambient temperature see chapters 3.6.1, 3.6.2 and 3.7.6, 3.7.7 Identification D-LX 200 ../84Ex see chapters 3.6.1 D-LX 200 ../87Ex see chapters 3.6.2 D-LX 200 ../85Ex see chapters 3.7.6 D-LX 200 ../86Ex see chapters 3.7.7...
  • Page 115: Technical Data Of The Sighting Tube Connection, Purge Air Connection

    10 Appendix: Technical data 10.3 Technical data of the sighting tube connection, purge air connection Sighting Tube Connection G 1¼“ Internal thread · optional:: NPT 1¼“ female Purge air connection G ½“ Internal thread · optional: NPT ½“ female Table 10.3: Technical data for the basic device 10.4 Factory Settings (Default) 4 - 20 mA Flame intensity current output...
  • Page 116: Appendix: Plans And Drawings D−Lx 200, D−Lx

    11 Appendix: Plans and drawings D−LX 200, D−LX 720 11 Appendix: Plans and drawings D−LX 200, D−LX 720 11.1 Wiring diagram D−LX 200, D−LX 720 Figure 11.1: Wiring diagram D−LX 200, D−LX 720 CAUTION! Only reaction-free components may be used at the "operationally ready" contact output, such as relays or contactor coils via external fuses.
  • Page 117: Wiring Diagram D−Lx 200

    11 Appendix: Plans and drawings D−LX 200, D−LX 720 11.2 Wiring diagram D−LX 200… /MP3, D−LX 720… /MP3 Figure 11.2: Wiring diagram D−LX 200… /MP3, D−LX 720… /MP3 CAUTION! Only reaction-free components may be used at the "operationally ready" contact output, such as relays or contactor coils via external fuses. These measures ensure protection against contact-fusing in accordance with EN 298.
  • Page 118: Dimensional Drawings

    11 Appendix: Plans and drawings D−LX 200, D−LX 720 11.3 Dimensional drawings D−LX 200 Figure 11.3: Dimensional drawing D−LX 200 D−LX 200, D−LX 720...
  • Page 119 11 Appendix: Plans and drawings D−LX 200, D−LX 720 D−LX 720 Figure 11.4: Dimensional drawing D−LX 720 D−LX 200, D−LX 720...
  • Page 120 11 Appendix: Plans and drawings D−LX 200, D−LX 720 D−LX 200 Ex Figure 11.5: Dimensional drawing D−LX 200 Ex D−LX 200, D−LX 720...
  • Page 121 11 Appendix: Plans and drawings D−LX 200, D−LX 720 D−LX 720 Ex Figure 11.6: Dimensional drawing D−LX 720 Ex D−LX 200, D−LX 720...
  • Page 122: Appendix: Declaration Of Conformity

    12 Appendix: Declaration of Conformity 12 Appendix: Declaration of Conformity D−LX 200, D−LX 720...
  • Page 123 12 Appendix: Declaration of Conformity D−LX 200, D−LX 720...
  • Page 124 12 Appendix: Declaration of Conformity D−LX 200, D−LX 720...
  • Page 125: Appendix: Certificates

    13 Appendix: Certificates 13 Appendix: Certificates For many countries national approvals of the flame monitor are available. But not all device alternatives are available with all approvals. Detailed information on the approvals you get from your sales representative. Some certificates are listed exemplary below: ...
  • Page 126 DVGW Certificate 13 Appendix: Certificates D−LX 200, D−LX 720...
  • Page 127 ATEX Zone 1. 21 13 Appendix: Certificates D−LX 200, D−LX 720...
  • Page 128 ATEX Zone 1. 21 13 Appendix: Certificates D−LX 200, D−LX 720...
  • Page 129 ATEX Zone 2. 22 13 Appendix: Certificates D−LX 200, D−LX 720...
  • Page 130: Appendix: Glossary

    14 Appendix: Glossary 14 Appendix: Glossary Background radiation influence signal transmission with digital trans- mission technology. Radiation from static emitters, like incandescent boiler components, can be DIP switches modulated by combustion air currents or are small switches which are used (e.g. flue plumes.
  • Page 131 14 Appendix: Glossary become a de facto standard in industry, standardised American as it is an open protocol. Federal Communications Commission A master (e.g. a PC) and several slaves (FCC) and the connectors and jacks used (e.g. measurement and control systems) for this purpose.
  • Page 132 14 Appendix: Glossary D−LX 200, D−LX 720...
  • Page 133: Appendix: Index

    15 Appendix: Index 15 Appendix: Index Data bus 130 Designated Use 48 Device description Adapter 45 D−LX 200 60 Adjusting the thresholds 89 D−LX 720 60 Adjustment (s) 87 Dimensional drawings Amplification characteristics curve 91, 93 D−LX 200 118 Applications 48 D−LX 200 Ex 120 approvals 50 D−LX 720 119...
  • Page 134 15 Appendix: Index Explosion protection 23 Location, suitable 70 Equipment Protection Level 25 Software D−LX 200 InformationCentre 139 Instructions Ignition protection categories 24 Temperature classes 25 for delivery 43 Zone classification 24 for environmental protection 11, 84 on warranty 12 Insulator 77 Intensity setting 90 Fault 109...
  • Page 135 15 Appendix: Index for the basic device 113 Integrated flame sensor 115 Personnell, qualified 20 Pre-settings 115 Plug connection 79 Purge Air Connection 115 Point, red 76 Sighting tube connection 115 Pre-settings 115 Terminal box 45 Printed circuit board, numbering 88 Thermal insulator 81 Protection type 76 with potential separation 45...
  • Page 137 D−LX 720 Compact Flame Monitor Appendix II: D−LX 200 InformationCentre PC-Version 16.1 System requirements 16.2 Installation 16.3 Start 16.4 Drop-down menus 16.5 Fault messages 16.6 Structure of the stored data sets Appendix II: Modbus 17.1 General information 17.2 DURAG Modbus DataMap...
  • Page 139: Appendix Ii: D−Lx 200 Informationcentre Pc-Version

    RS232 to RS485 (2-wire) converter is required. 16.2 Installation To install the software, the Setup.Exe is started in the folder "D-LX 200 Installer". The program should be installed in the folder "C:\Programs\D-LX 200\" if possible, and is ready for execution when installation is complete.
  • Page 140 16 Appendix II: D−LX 200 InformationCentre PC-Version Figure 16.1: Start display InformationCentre The "D-LX 200 connected" message shows if the connection has been made correctly. If this is the case, the field is green. If it stays red, even though D−LX 200,...
  • Page 141 16 Appendix II: D−LX 200 InformationCentre PC-Version If the connection is successfully established, the program changes to the following display: Figure 16.3: Display views InformationCentre The actual data transfer from the D−LX 200, D−LX 720 is commenced using the "Start" button. By using the "Rec" button, data recording can be activated/terminated.
  • Page 142 16 Appendix II: D−LX 200 InformationCentre PC-Version 16.3.1 Flame Information The "Flame Information" window displays the graphs "Intensity", "Frequency" and "Analogue Output". Figure 16.4: Flame Information window Intensity The "Intensity" value is the integral alternating component of the flame signal with the amplification factor included.
  • Page 143 16 Appendix II: D−LX 200 InformationCentre PC-Version 16.3.2 Flame Sensor Signal The view shows the current setting of the internal amplifier stage (ACvu and DCvu), the wave form of a measuring cycle (AC signal) and the DC signal (direct current signal of the flame / diffused light of the flame radiation). The DC signal is only for information and does not affect the decision regarding Flame ON/OFF.
  • Page 144: Table 16.1: System Settings

    Switch / Value value) frequency threshold Gain Characteristic View of the gain characteristic curve Firmware Fimware Version/Revision of the D-LX 200 View of the interface used and Connection Setting of the used modbus slave address Analogue Output Analogue output 0..20mA 4..20mA...
  • Page 145: Drop-Down Menus

    16 Appendix II: D−LX 200 InformationCentre PC-Version 16.4 Drop-down menus 16.4.1 File The "File" menu is divided into 5 sub-menus "SelectFile", "FileSetting", "ReadFile", "Export to XLS" and "Exit" (see Figure 16.7). Figure 16.7: "File" Menu SelectFile Under "SelectFile" the path and the data file can be saved where data is to be stored.
  • Page 146 16 Appendix II: D−LX 200 InformationCentre PC-Version Via the "ReadFile" menu option stored data can be played back. For this a separate control window opens that helps you to navigate the file (Figure 16.9). The button allows you to chose between automatic and manual operation.
  • Page 147 ErrorLog" and "Adjust CurrentOutput". Service The "Service" function is undocumented and reserved for specially trained DURAG service personnel. Read ErrorLog The "Read ErrorLog" allows all error logs (fault reports) of the D−LX 200, D−LX 720 to be read and stored in a text file.
  • Page 148 16 Appendix II: D−LX 200 InformationCentre PC-Version Figure 16.12:"Adjust CurrentOutput" sub-menu The analogue output range indicated on the type label must match the one set for the device! D−LX 200, D−LX 720...
  • Page 149: Fault Messages

    16 Appendix II: D−LX 200 InformationCentre PC-Version 16.5 Fault messages In the case of an error shutdown an extra window is opened which displays the error number and, if applicable, the error explanation message. The program continues to update the data. As the D−LX 200, D−LX 720 have entered the so-called error state (red "Error"...
  • Page 150 16 Appendix II: D−LX 200 InformationCentre PC-Version 128 AD Values free 32 8Bit Parameter Param(01) AD value minimum Param(02) AD Value maximum Param(03) AD value mean value Param(04) Free Param(05) DC-Signal MC2 Param(06) DC-Signal MC1 Param(07) Max. Frequency Param(08) Intensity 16Bit (High-Byte) Param(09) Intensity 16Bit (Low-Byte) Param(10)
  • Page 151: Table 16.2: Data Set Structure

    16 Appendix II: D−LX 200 InformationCentre PC-Version Param(19) FLW-Status Information MC2 Param(20) Free Param(21) Free Param(22) Free Param(23) Harmonic detection 00..50 Param(24) Free Switch setting/Limits Range A Param(25) Frequency [A] Frequency [A] Switch setting/Limits Range B Param(26) Frequency [B] Frequency [B] FLW-ConfigInfo Param(27) SSL-B...
  • Page 153: Appendix Ii: Modbus

    17 Appendix II: Modbus 17 Appendix II: Modbus 17.1 General information Slave Address Function Code Data 2 bytes 1 byte 1 byte 0 up to 252 byte(s) CRC Low, CRC Hi Table 17.1: Modbus RTU Message Frame from 1 to 247 from 248 to 255 Broadcast address Slave individual addresses Reserved...
  • Page 154: Table 17.5: Modbus Function Code(0X03..0X04) Read 16Bitregisters Response

    17 Appendix II: Modbus Response Slave Address 1 Byte 0, 1..254 FunctionCode 1 Byte 0x03…0x04 Byte count of… 1 Byte 2 x N* …Input Registers N* x 2 Bytes Register Value Value 2 Bytes SA, FC DATA *N = Quantity of Registers Table 17.5: Modbus Function Code(0x03..0x04) Read 16BitRegisters Response Modbus FunctionCode(0x10) Write Multiple 16BitRegisters (for details see Modbus-Specification)
  • Page 155: Durag Modbus Datamap

    9600bps[0]/19200bps[1] Table 17.8: Modbus RTU:Register and Address-Information The parameters and Modbus register described below for the D−LX 200, D−LX 720 flame monitor can be found in the "device-specific" address area of the DURAG Modbus Data Map. D−LX 200, D−LX 720...
  • Page 156: Table 17.9: Modbus Rtu Register And Device-Specific Address Information

    17 Appendix II: Modbus Note* Register Register Modbus Register Content Parameter Description Anzahl Adr.[dec/hex] DEVICE SPECIFIC AREA Data set Identifier 2049 0..65000 0801 Analogue amplification MC1&MC2 2050 MC1: ACvu | DCvu MC2: ACvu | DCvu 0802 DC-Signal MC1 2051 0..255 0803 DC-Signal MC2 2052...
  • Page 157 17 Appendix II: Modbus *Explanations of the parameters Analogue amplification AC amplification (ACvu) DC amplification (DCvu) [0..8] [0..3] Switching threshold Frequency [0..15] Intensity [0..15] G Amplification characteristics curve Gain Characteristic for Range A and B respectively (→) Safety time These parameters contain the set safety times 1,2,3,5 seconds as BCD values, the current Safety Time Flame Status is also given.
  • Page 158 17 Appendix II: Modbus M AD value Min/Max RMS Delivers the maximum/minimum as well as the mean value (RMS) from the digitised flame sensor raw signal information of the current data set which is portrayed by the 128AD value (compare with note N) AD value This register contains 128 AD values with the digitised flame sensor raw signal information...
  • Page 159: Durag Group Company Addresses

    18 DURAG GROUP company addresses 18 DURAG GROUP company addresses Kollaustr. 105 Tel. +49 (0)40 55 42 18 – 0 DURAG GmbH 22453 Hamburg Germany Fax +49 (0)40 58 41 54 E-Mail: info@durag.de DVN – DURAG DVO – DURAG DVS – DURAG DVW –...
  • Page 160 GmbH · Kollaustraße 105 · 22453 Hamburg · www.durag.de...

This manual is also suitable for:

D-lx 720

Table of Contents

Save PDF