Reference Manual Original Instructions Power Supply - 24V, 10 A, 240 W, Three-phase Input Catalog Number 1606-XLE240E-3...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Terminology and Abbreviations Term Definition PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol.
• Easy fuse tripping due to high overload current • Input-transient blanking circuit included • Minimal inrush current surge • Three input fuses included • Current sharing feature for parallel use • Full power between -25 °C...+60 °C (-13 °F...+140 °F) Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 5
Without DIN rail (2.44 x 4.88 x 4.60 in.) Weight 750 g (1.65 lb) Without DIN rail Figure 1 - Main Approvals UL 60950-1 IND. CONT. EQ. page 20 for a complete list of approvals. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
• The isolation of the device is designed to withstand impulse voltages of overvoltage category 3 according to IEC 60664-1 for corner grounded delta systems, the overvoltage category level is reduced to level 2. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 7
2 cm (7.87 in.) below the device. • The device is designed to operate in areas between 5% and 95% relative humidity. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Figure 2 - Input Voltage Range Figure 3 - Turn-on Behavior, Definitions Rated input Input < 1s range Voltage - 5% Output Voltage Start-up Rise delay Ti me 185V 260V 323V 576V 3x700Vac Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
0.5 A 1.5 A energy ° ° Figure 6 - Typical Input Inrush Current Behavior at Nominal Load and 25 C (77 F) Ambient Temperature Input current 1A/DIV Input voltage 500V/DIV Output voltage 20ms/DIV Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
(1) This current is also available for temperatures up to 70 °C (158 °F) with a duty cycle of 10% and/or not longer than 1 minute every 10 minutes. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Figure 9 - Hold-up Time versus Input Voltage Figure 10 - Shut-down Behavior, Definitions Hold-up Time at 24Vdc L1 L2 L3 100ms Input Voltage - 5% Output Voltage Hold-up Time Input Voltage 440 3x480Vac Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Figure 12 - Losses versus Output Current at 24V, typ., Operation 3-phase Operation Figure 13 - Efficiency versus Input Voltage at 24V, 10 A, typ., Losses versus Input Voltage at 24V, 10 A, typ., 3-phase 3-phase Operation Operation Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Single Use Guaranteed adjustment range: 24…28V Factory set: 24.1V DC ok Jumper for Parallel Use, Single Use Allen-Bradley QUALITY DC-OK Relay Contact (push-in terminals) 1606-XLE POWER SUPPLY 1606-XLE240E-3 18WM IND.CONT.EQ. Input 3AC 380-480V Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Figure Figure 15 - Daisy Chaining of Outputs Figure 16 - Using Distribution Terminals Distribution Terminals Power Power Power Power Supply Supply Supply Supply Load Load Output Output Output Output max 25A! continuous Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 h or only for 100 h. For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
(2) this device must accept any interference received, including interference that can cause undesired operation. (1) Tested with constant current loads, non-pulsing. Switching Frequency Description Main converter 60k Hz…140k Hz Output load and input voltage dependent Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
It is recommended that either the + pole, - pole, or any other part of the output circuit shall be connected to the earth/ground system. This helps to avoid situations in which a load starts unexpectedly or can be turned off when unnoticed earth faults occur. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
June 8th, 2011, on the restriction of the use of certain hazardous substances in electrical and electronic equipment. REACH Directive Directive 1907/2006/EU of the European Parliament and the Council of June 1st, 2007, regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals (REACH). Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
(1) The DIN rail height must be added to the unit depth to calculate the total required installation depth. Dimensions are in millimeters. Figure 20 - Front View Figure 21 - Side View Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
The 1606-XLERED dual redundancy module can be used to build 1+1 or N+1 redundant systems. The device is equipped with two input channels each 10 A nominal, which are individually decoupled by using diode technology. The output can be loaded with nominal 20 A. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips for resistive loads. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 24
The following test results indicate the maximal wire length for a magnetic (fast) tripping. The wire length is always two times the distance to the load (+ and – wire). Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 25
4. Verify that the output current of the power supply is below the allowed charging current of the battery. 5. Use only matched batteries when placing 12V types in series. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 26
The Parallel Use mode regulates the output voltage in such a manner that the voltage at no load is approximately 4% higher than at nominal load. Do not exceed 60 °C (140 °F) or the ambient temperature. Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 27
For 1+1 redundancy the ambient temperature is not allowed to exceed 70 °C (158 °F). Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 28
For 1+1 redundancy the ambient temperature is not allowed to exceed 60 °C (140 °F). Figure 34 - 1 + 1 Redundant Configuration for 10 A Load Current and Redundancy Modules 1606-XLERED 1606-XLERED Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 29
Using two legs of a 3-phase system is not included in the agency approval. Therefore, additional investigation might be necessary during the approval process of the final system. Figure 36 - Operation on Two Phases Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 30
The load is placed outside the box. The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm (0.39 in.). Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 31
Allowed Output Current at 24V OU TPU T 7.5A Power Supply INPU T +70°C Ambient Temperature Figure 42 - Mounting Orientation B (Upside Down) Allowed Output Current at 24V 7.5A +70°C Ambient Temperature Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Page 32
Figure 44 - Mounting Orientation D (Horizontal cw) Allowed Output Current at 24V 6.5A +70°C Ambient Temperature Figure 45 - Mounting Orientation D (Horizontal ccw) Allowed Output Current at 24V 6.5A +70°C Ambient Temperature Rockwell Automation Publication 1606-RM002A-EN-P - March 2019...
Need help?