Page 1
PNOZ m EF 8DI4DO Configurable, safe small controllers PNOZmulti 2 Operating Manual-1002661-EN-05...
Page 2
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Technical details ........................Safety characteristic data ......................Classification according to ZVEI, CB24I ................... Supplementary data ......................Permitted ambient temperature Tamb dependent on the total current Isum ......Order reference ........................10.1 Product ............................. Operating Manual PNOZ m EF 8DI4DO 1002661-EN-05...
Page 4
Contents 10.2 Accessories ..........................Operating Manual PNOZ m EF 8DI4DO 1002661-EN-05...
Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ m EF 8DI4DO. It is valid until new docu- mentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Page 6
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ m EF 8DI4DO 1002661-EN-05...
Expansion module PNOZ m EF 8DI4DO Jumper Unit features Application of the product PNOZ m EF 8DI4DO: Expansion module for connection to a base unit from the PNOZmulti 2 system. The product has the following features: Can be configured in the PNOZmulti Configurator...
Example: Protected inside space or control cabinet with protection type IP54 and corres- ponding air conditioning. The product PNOZ m EF 8DI4DO can be used in furnaces in accordance with EN 298. The following is deemed improper use in particular...
Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ m EF 8DI4DO | 10 1002661-EN-05...
Calculation of the maximum reaction time between an input switching off and a linked out- put in the system switching off is described in the document "PNOZmulti System Expan- sion". Block diagram Operating Manual PNOZ m EF 8DI4DO | 11 1002661-EN-05...
Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm 22,5 (0.88") Operating Manual PNOZ m EF 8DI4DO | 12 1002661-EN-05...
Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ m EF 8DI4DO | 13 1002661-EN-05...
Connection Supply voltage Supply voltage Input circuit Single-channel Dual-channel Example: E-Stop without detection of shorts across contacts Example: E-Stop with detection of shorts across contacts Connection examples for the input circuit Operating Manual PNOZ m EF 8DI4DO | 14 1002661-EN-05...
Page 15
Feedback loop Redundant output Contacts from external contactors O0 (O2) O1 (O3) Connection examples for feedback loop Operating Manual PNOZ m EF 8DI4DO | 15 1002661-EN-05...
Proceed as described in the operating manual for the base unit. NOTICE For the commissioning and after every user program change, you must check whether the safety devices are functioning correctly. Operating Manual PNOZ m EF 8DI4DO | 16 1002661-EN-05...
No supply voltage Expansion module PNOZ m EF 8DI4DO running without error. Expansion module PNOZ m EF 8DI4DO is in a STOP condition. Internal error on the expansion module PNOZ m EF 8DI4DO or on the overall system. Expansion module is in a safe condition.
Permitted current range 0,000 - 2,500 A Residual current at "0" signal 0,05 mA Max. transient pulsed current 12 A Max. capacitive load 1 µF Max. internal voltage drop 500 mV Operating Manual PNOZ m EF 8DI4DO | 18 1002661-EN-05...
Page 19
Rated insulation voltage 30 V Rated surge voltage 2500 V Mechanical data Mounting position horizontally on mounting rail DIN rail Top hat rail 35 x 7,5 EN 50022 Recess width 27 mm Operating Manual PNOZ m EF 8DI4DO | 19 1002661-EN-05...
Page 20
Stripping length with spring-loaded terminals 9 mm Dimensions Height 101,4 mm Width 22,5 mm Depth 120 mm Weight 105 g Where standards are undated, the 2018-09 latest editions shall apply. Operating Manual PNOZ m EF 8DI4DO | 20 1002661-EN-05...
A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Operating Manual PNOZ m EF 8DI4DO | 21 1002661-EN-05...
Supplementary data Supplementary data Permitted ambient temperature Tamb dependent on the total current Isum Operating Manual PNOZ m EF 8DI4DO | 23 1002661-EN-05...
751 004 Set screw terminals 1 set of screw terminals 750 004 Terminator, jumper Product type Features Order no. PNOZ mm0.xp connector Jumper yellow/black to connect the modules, 10 pieces 779 260 left Operating Manual PNOZ m EF 8DI4DO | 24 1002661-EN-05...
Page 25
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...
Need help?
Do you have a question about the PNOZ m EF 8DI4DO and is the answer not in the manual?
Questions and answers