SPECIFICATIONS
MODEL
Heat Input
Appliance Type
Appliance Cat
Adjusted for
Gas supply
Setting Pressure
Injector (1 piece)
NOx Class
Electrical Supply
Fuse Externally
Dimensions
Weight
Gas Connection
Protection
Model Identification:
Control Option Suffix
N7
L7
Model No.
WB10CE-N7
2.4 to 3.4m
WB10CE-L7
* For mounting heights outside the recommended distances consult your local Space-Ray Representative.
Ignition System (direct spark):
1.5 second pre-purge period
10 second trial for ignition period
15 second inter-purge period
3 tries for ignition
separate flame sensor
Flame Sensitivity: >0.7μA minimum
Approved installation angles are 0°, 15°, 30°, 45° and 60° degrees with heat shield installed.
Form 44201360
Oct 2019
WB10CE-N7
10.25 kW Hs / 9.23 kW Hi
(minimum 7.0 kW Hs / 6.3 kW Hi)
A
I
2H
G20 20mbar
60mbar maximum / 20mbar minimum
15.0 mbar (minimum 7.0 mbar)
No. 41
4
L = 1219.2mm W = 300mm H = 243.8mm
Gas Type
Description
G20
Two Stage SIT 843 Gas Valve – High/Low Fire
G31
Two Stage SIT 843 Gas Valve – High/Low Fire
Recommended*
Mounting Height
@ 5 º
@ 0 º
to 30 º
2.15 to 2.7m
1
60mbar maximum / 37mbar minimum
230V ~ 50Hz 25W
3A
21.8kg
RP - ½ (BSPT)
IP23
@ 30º
to 60 º
2.15 to 2.44
12
WB10CE-L7
10.25 kW Hs / 9.23 kW Hi
(minimum 7.0 kW Hs / 6.3 kW Hi)
A
1
I
3P
G31 37mbar
26.7 mbar (minimum 12.5 mbar)
No. 51
4