IT MAINS Installation on isolated mains source, that is IT mains. Maximum supply voltage allowed when connected to mains: 440 V. As an option, Danfoss offers recommended line filters for improved harmonics performance. See chapter Options and Spare Parts. 1.6 Disposal Do not dispose of equipment containing electrical components together with domestic waste.
3.5.2 Short-circuit Protection Use the Danfoss recommended fuses to protect service personnel or other equipment if there is an internal failure in the unit or short circuit on DC-link. If there is a short circuit on the motor or brake output, the drive provides full short-circuit protection.
Improved power factor and EMC performance can be achieved by installing optional Danfoss line filters. Danfoss power filters can also be used for load sharing. For more information about load sharing, see VLT® Micro DriveFC 51 Load Sharing application note.
N O T I C E The drive can also be programmed from a PC via RS485 com-port by installing the MCT 10 Set-up Software. This software can either be ordered using code number 130B1000 or downloaded from the Danfoss web site: www.dan- foss.com.
C A U T I O N INSTALLATION AT HIGH ALTITUDE For altitudes above 2000 m (6560 ft), contact Danfoss regarding PELV. Below 1000 m (3280 ft) altitude, no derating is necessary, but above 1000 m (3280 ft), decrease the ambient temperature or the maximum output current.
Page 36
Danfoss can accept no responsibility for possible errors in catalogs, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.