WARNING Installation and service must be performed by a qualified service technician. Read instructions before installing and operating. Keep instructions in a safe place. Disconnect electrical power before beginning installation. Follow all required site-spe- cific lockout/tagout procedures. Installation and application must adhere to local codes established by the authorities having jurisdiction.
• Hawk 4000 V2 1 - Hardware Required: Prometha™ requires the addition of four major components to allow data collection from the PLC and transmission of that data to the cloud via LTE cellular connection. • Cellular Enable Gateway Device •...
ProtoNode/CB-PT panel to house the Prometha™ components; the existing Ethernet switch provides the connection point for each Hawk network device. The DT (Data Transfer) Panel option incorporates all of the Prometha™ hardware in a single stand- alone panel and is available with or without an Ethernet switch.
™ Prometha Installation 4 - Installation Procedure - Hawk Panel, Master Panel, or PT Panel 4.1 - Power Supply Mount the power supply on the DIN rail with the 12VDC output terminal on OUTPUT 12VDC top and the 120VAC input terminals on the bottom. See dimensions and clearances below.
™ Prometha Installation 4.2 - Data Transfer Gateway Mount the gateway on the DIN rail with the coaxial antenna connectors at the top and the power supply connection at the bottom. INPUT VOLTAGE 12VDC GATEWAY DIMENSIONS 1.3"W x 4.6"H x 3.3"D INSTALLATION CLEARANCES 2"...
™ Prometha Installation 4.5 - Ethernet Switch An Ethernet switch is required for installations where the PLC Ethernet port is already in use. The 880-10069-000 kit includes the necessary installation hardware: • Fuse holder • 2A fuse • End anchors •...
™ Prometha Installation 7 - Ethernet Connections Shown below are the CAT5e cable connections for various installation options. Single Boiler - Hawk Panel Single Boiler - PT Panel 750-441...
™ Prometha Installation 8 - Troubleshooting Mini-DisplayPort Before powering up the system, connect a portable monitor to the MiniDisplay port on the Gateway. Con- nect monitor power to one of the USB ports on the Gateway. The Cleaver-Brooks IoT screen provides information on system status and can serve as a diagnostic tool in case of connection problems.
™ Prometha Installation 8.2 - Hawk Connection In the event of a problem with the Hawk control system connection: • Confirm gateway Ethernet cable is plugged into the top Ethernet port of the gateway. • Confirm PLC Ethernet cable is plugged into the Hawk PLC or an Ethernet switch on the Hawk network. Do not plug the Ethernet cable into the 1769-SM2 module in the Hawk PLC I/O rack or, for older Hawks, the 1761-NET-ENI module.
™ Prometha Installation 8.3 - C-B Cloud Connection In the event of an error message indicating an issue with the C-B cloud connection (2), call C-B Sup- port and provide Host Name information (1). 750-441...
Prometha™ - Base Hardware PART NUMBER DESCRIPTION 833-05980-000 Gateway 997-11724-000 Antenna 832-04115-000 Power Supply 750-00441-000 O&M Manual 880-10068-000 - Supplemental Prometha™ Installation Kit PART NUMBER DESCRIPTION 826-00111-000 Ethernet Cable, 7' 950-00555-000 Red #16 Wire 950-00557-000 White #16 Wire 950-00561-000 Green #16 Wire...
™ Prometha Installation 10 - Tag Lists Read-only tags for Prometha™ compatible devices Hawk ICS Point Name Data Type Drive Fault Modbus Com Error Low Water BC Alarm Boiler Limits Open High Stack Temp Alarm High Stack Temp SD External Interlock...
™ Prometha Installation Hawk 1000 Point Name Data Type Drive Fault Modbus Comm Error Lo Water Burner Control Alm Boiler Limits Open Hi Stack Temp Alm Hi Stack Temp Shutdown External Interlock I/O module fault Steam Sensor Fail Air Actuator Out Of Pos Alm...
™ Prometha Installation Hawk 4000 Point Name Data Type Drive Fault Modbus Comm Error Lo Water Burner Control Alm Boiler Limits Open Hi Stack Temp Alm Hi Stack Temp Shutdown External Interlock I/O module fault 10 Steam Sensor Fail 11 Air Actuator Out Of Pos Alm...
™ Prometha Installation Hawk 4000 V2 Point Name Data Type Drive Fault Modbus Comm Error Lo Water Burner Control Alm Boiler Limits Open Hi Stack Temp Alm Hi Stack Temp Shutdown External Interlock I/O module fault 10 Steam Sensor Fail...
Page 35
™ Prometha Installation Hawk 4000 V2 (continued) 202 VFD EtherNet Comm Error 203 Slot 8 Ch 4 Analog Input Selected 204 Slot 8 Ch 5 Analog Input Selected 205 Slot 8 Ch 6 Analog Input Selected 206 Slot 8 Ch 7 Analog Input Selected...
Page 36
™ Prometha Installation Hawk 4000 V2 (continued) 253 Water Temp Shell/Outdoor Temp 254 Feedwater Temp/Econ Water Out Temp 255 Stack Temp After Econ/Return HW 256 Economizer Water In Temp 257 AI Slot8Ch0 Value/2Stg Econ Temp IN 258 AI Slot8Ch1 Value/2Stg Econ Temp OUT...
Page 37
™ Prometha Installation Hawk 4000 V2 (continued) 304 Boolean Bits to MP 305 PLC Module Fault Num to MP 306 ActuatorModbus[1].RdData.ErrCode to MP Air 307 ActuatorModbus[2].RdData.ErrCode to MP F1A1 308 ActuatorModbus[3].RdData.ErrCode to MP F1A2 309 ActuatorModbus[4].RdData.ErrCode to MP Air2 310 ActuatorModbus[5].RdData.ErrCode to MP F2A1 311 ActuatorModbus[6].RdData.ErrCode to MP F2A2...