NO.C004 Air conditioning unit communications cable port schematic
Air Conditioner Indoor Unit Wiring Port Layout Diagram
Air conditioner model: 42 kW NetCol5000-A042
Technical requirements:
1. Use a 3x16 AWG cable (BOM number: 25030361).
2. Crimp cord end terminals (BOM number: 14170097) at both ends of the
cable.
3. Connect the cable to ports 1, 2, and 3 of the signal terminal X302.
Air Conditioner Outdoor Unit Wiring Port Layout Diagram
Technical requirements:
1. The signal cable between indoor and outdoor units is an RS485
communications cable.
2. Crimp cord end terminals at both ends of the cable.
3. Connect the communications cable to ports 3, 4, and 5 of the outdoor
unit signal terminal.
4. Black corresponds to 3, white corresponds to 4, and green corresponds
to 5.