Connection BCI OCI410
Connect the BCI OCI410 without other extension with the USB interface at your PC,
follow the example design below.
LMO39...
OCI410
RJ11
Figure 3: Connection BCI OCI410
Connection interface OCI400...
∂
Put the interface OCI400... in the connector at lockout reset button of LMO39...
Interface diagnostics works only if the AGK20... lockout reset button extension
is not fitted
∂
Connect the interface OCI400... without other extension to the interface at your
PC, follow the example design below
LMO39...
OCI400
RS232
Figure 4: Connection interface OCI400...
1.6
Electrical connection of flame detectors
It is important to achieve practically disturbance- and loss-free signal transmission:
∂
Never run detector cables together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
∂
Observe the permissible length of the detector cables (see Technical data)
∂
Insulation resistance
– Soiled detector holders reduce the insulation resistance, thus supporting
creepage currents
∂
Earth the burner in compliance with the relevant regulations; earthing the boiler
alone does not suffice
Basic Documentation LMO39...
1 Safety notes
ACS410
PC software
USB2.0
7154z02e/0212
ACS410
PC software
7154z01e/0212