Connection BCI OCI410
Connect the BCI OCI410 without other extension with the USB interface at your PC,
follow the example design below.
LMO39...
OCI410
RJ11

Figure 3: Connection BCI OCI410

Connection interface OCI400...
Put the interface OCI400... in the connector at lockout reset button of LMO39...
Interface diagnostics works only if the AGK20... lockout reset button extension
is not fitted
Connect the interface OCI400... without other extension to the interface at your
PC, follow the example design below
LMO39...
OCI400
RS232

Figure 4: Connection interface OCI400...

1.6

Electrical connection of flame detectors

It is important to achieve practically disturbance- and loss-free signal transmission:
Never run detector cables together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
Observe the permissible length of the detector cables (see Technical data)
Insulation resistance
– Soiled detector holders reduce the insulation resistance, thus supporting
creepage currents
Earth the burner in compliance with the relevant regulations; earthing the boiler
alone does not suffice