Self-Testing/Self-Diagnostic EmergencyModels
All models ordered with the Dual-Lite Spectron
self-testing/self-diagnostic electronics system provide:
■ Visual indication of AC power status
■ Visual indication of all self-diagnostic test cycles
■ Visual indication of unit malfunctions including:
■ Battery fault
■ Charger fault
■ Transfer Fault
■ Lamp fault
Bi-Color LED Status Indicator
Self-testing/self-diagnostic units are provided with a
single, bi-color LED which serves as a combination AC
power, self-test and service alert status indicator. During
normal operation, the green status LED will be constantly
illuminated, indicating the presence of AC power. During
all automatic or manual self-test cycles, the green Status
LED will blink at a one cycle per second rate indicating
"Test In Progress". If a fault condition is detected during
any automatic or manual self-test cycle, upon completion
of test, the red status indicator will provide a "service alert
code" – see table below.
Service Alert Code
Description
One blink ON/pause
Battery not connected
Two blinks ON/pause
Battery fault
Three blinks ON/pause
Charger fault
Four blinks ON/pause
Transfer circuit fault
Five blinks ON/pause
Lamp failure
EMERGENCY MODEL
TROUBLESHOOTING
AC-On Light does not illuminate
• Check AC wiring connections
Emergency LEDs do not work
• Battery is shipped disconnected. Connect leads from
battery to charger PCB and charge before testing.
• Make sure connections to LED board are properly
seated.
• Check wiring connections.
Maintenance
Exit signs should be tested and maintained in accordance
with National Electrical Code and NFPA 101 Life Safety
Code requirements. It is recommended that exit signs be
tested for a minimum of 30 seconds once a month and 90
minutes once a year.
The automatic monthly tests of the Spectron units satisfy
this requirement. The required annual test can be initiated
manually with the test switch, as required by the safety
code.
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A. [EC 090204002]
©
Manual Test
Using the unit test switch, users can initiate different
duration test cycles based on the following table:
To Initiate Action:
Test Cycle
Press switch once
1 minute
Press switch twice
90 minute
Pressing test switch at any time after a test cycle has
begun cancels the remainder of test and returns the unit
to normal operation. (NOTE: Batteries are often shipped
in a discharged state – this is normal – battery requires
charging. Allow several hours of charge before testing
unit.)
Spectron units also provide:
Brownout protection – unit transfer to emergency mode
with low AC input voltage.
Time Delay Re-transfer – unit will remain in emergency
mode for additional time after AC power is restored.
RECYCLING INFORMATION
All aluminum components are recyclable.
All cartons contain recycled materials.
Please recycle.
NOTICE:
Emergency exit signs contain rechargeable batteries
which must be recycled or disposed of properly.
Use CAUTION when handling batteries.
LED REPLACEMENT
(Contact factory)
93022482 A 9/09
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following.
READ AND FOLLOW ALL SAFETY
1. Do not let power supply cords touch hot surfaces.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will not readily be subject to tampering by
unauthorized personnel.
4. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
5. Do not use this equipment for other than its intended purpose.
6. Service of this equipment should be performed by qualified service personnel.
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects and/or
other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
93021636
93021638
93021640
93021641
93021643
93021644
93021645
93021646
93024663
Wet Location/NEMA 4X Die-Cast Aluminum LED Exit Sign
Installation, Operation and Maintainance Instructions
INSTRUCTIONS
INSTALLER:
SEWL Series
93021636