Download Print this page
Azbil MY3000 00 Series Specifications & Instructions
Azbil MY3000 00 Series Specifications & Instructions

Azbil MY3000 00 Series Specifications & Instructions

Control motor

Advertisement

Quick Links

„ Overview
Control motor, Model MY3000_ _ _00, actuates a
control valve or a damper when combined with a
linkage.
When being combined with a control valve, it is
mounted with the Model Q455_ valve linkage.
When being combined with a damper, it is mounted
with the Model Q605_ damper linkage.
The following control motor types are available,
classified by control method.
• The control motor with built-in nominal 135 Ω
feedback potentiometer exerting proportional control
when combined with the digital controller (Model
WY5111, etc.)
• Nominal 135 Ω resistance input type exerting
proportional control when combined with the electric
proportional controller such as Neostat (Model
TY900_Z) , insertion type temperature controller
(Model TY9800)
• 4-20 mA DC input type exerting proportional control
when combined with the digital controller such as
Infilex GC (Model WY5111) , Models R15, R35, R36
• 2-10 V DC input type exerting proportional control
when combined with the digital controller such as
Infilex AC (Model WY5117)
• ON/OFF or floating type that exerts floating control
when combined with a digital controller
„ Features
• A variety of control input signals available
• Durable and low power consumption
• Valves and dampers in varied sizes can be actuated
using the linkage.
• The auxiliary switch unit can be installed easily.
IMPORTANT
• If you want to use this product combined with a third
party's controller, please contact Azbil corporation.
Control Motor
1
Specifications/Instructions
© 2003–2018 Azbil Corporation All Rights Reserved.
AB-6387

Advertisement

loading
Need help?

Need help?

Do you have a question about the MY3000 00 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Azbil MY3000 00 Series

  • Page 1 • Valves and dampers in varied sizes can be actuated using the linkage. • The auxiliary switch unit can be installed easily. IMPORTANT • If you want to use this product combined with a third party's controller, please contact Azbil corporation. © 2003–2018 Azbil Corporation All Rights Reserved.
  • Page 2: Safety Precautions

     Azbil Corporation. Failure to do so may result in electric shock Azbil Corporation bears no responsibility for or device failure. any result, or lack of result, deriving from the Be sure to ground this product with a ground customer's use of the product.
  • Page 3 Operation range SW1 to SW4: Variable from 5 % (fully closed) to 95 % (fully open) Can be changed by setting the dials A to D. Required to maintain IP54. If the applied current exceeds 100 mA, please contact Azbil Corporation.
  • Page 4 AB-6387 „ Specifications (1/2) Item Specification Power supply Model MY3000F0200, 24 V AC ± 15 %, 50/60 Hz Model MY3000F0400, Model MY3000E0200, Model MY3000G0200, Model MY3000V0200, Model MY3000D0200 Model MY3000G9200 100–240 V AC (85–264 V AC) , 50/60 Hz Power consumption Model MY3000F0200, Operating Approx.
  • Page 5 AB-6387 (2/2) Item Specification Operating conditions Rated operating conditions Ambient -20–60 °C temperature Ambient 5–95 % RH humidity Transport and storage Ambient -20–70 °C conditions temperature (in packed state) Ambient 5–95 % RH humidity Installation Location Indoor use Note: Salt air, corrosive gas, flammable gas, and organic solvent must be avoided. Outdoor use Note: Salt air, corrosive gas, flammable gas, and organic solvent must be avoided.
  • Page 6 AB-6387 „ Dimensions 16.5 104.5 128.5 149.6 20.5 Figure. 1 Dimensions (mm) „ Parts Indication Cover setscrews Cover Screws for fixing the cover. Plastic cover to protect interior Three screws are provided in total. of the main body. Body Knockout hole Hole for wiring port.
  • Page 7: Precautions For Installation

    AB-6387 „ Installation z When using with the damper  CAUTION When this product is used with the damper, use the Install, wire, and use this product under the damper linkage (Models Q605A, Q605D, or Q605E) . conditions specified by this manual. ...
  • Page 8: Wiring Method

    AB-6387 „ Auxiliary Switch Unit (Optional) z How to maintain IP54 (dust-proof,  WARNING splash-proof) Before beginning setup work, be sure to turn In order to maintain IP54 performance, use a off the power to this product.  Failure to do so may result in electric shock waterproof connector or a water-resistant plica or device failure.
  • Page 9 AB-6387 Terminal block (4) Turn it The auxiliary switches operate at the mark on the Auxiliary counterclockwise (6) switch unit setting dials (A, B, C, D) . After setting the auxiliary switches, check that they operate as intended. The operation range of the auxiliary switches is as follows: Setting range: valve position from 5 % to 95 % Repeatability of operation range: less than ±3 %...
  • Page 10 AB-6387 „ Terminals Connection z Nominal 135 Ω feedback potentiometer z 4–20 mA DC input (Model MY3000F0200, Model MY3000F0400) (Model MY3000G0200, Model MY3000G9200) CLOSE OPEN CLOSE OPEN Open Open Open Open ~ ⊥ + - ~ 24 V AC power F.G.
  • Page 11 AB-6387 „ Wiring Examples z Nominal 135 Ω feedback potentiometer z 4–20 mA DC input (Model MY3000F0200, Model MY3000F0400) (Model MY3000G0200, Model MY3000G9200) Power transformer (Model AT72-J1) ~ ① 100/200 V AC ~ ⊥ ② ③ *1 ④ ⑬ CLOSE +...
  • Page 12 AB-6387 „ Advanced Wiring Examples z Nominal 135 Ω resistance Input (Model MY3000E0200) Minimum opening setting Using relay, interlock Power transformer Power transformer (Mode AT72-J1) (Mode AT72-J1) ~ ~ 100/200 V AC 100/200 V AC ~ ~ ⊥ ⊥ CLOSE(0) CLOSE *...
  • Page 13 AB-6387 z 4–20 mA DC input z 2–10 V DC input (Model MY3000G0200, Model MY3000G9200) (Model MY3000V0200) Input signals are shared Input signals and power are shared 1 ~ 1 ~ ⊥ ⊥ Isolator Model WY5117 Isolator ⑬  + +...
  • Page 14 • Once every six months or so, visually check that the product operates smoothly. if a trouble occurs as described in Table 2, take appropriate measures according to the symptom. Although the measures are taken, if the trouble cannot be recovered, please contact Azbil Corporation. Table 1 Inspection items and inspection method...
  • Page 15 AB-6387 „ Disposal Dispose of this product as industrial waste in accordance with your local regulations. Do not reuse all or any part of the product.
  • Page 16 AB-6387 * ACTIVAL is a trademark of Azbil Corporation. * Infilex is a trademark of Azbil Corporation. Building Systems Company 1-12-2 Kawana, Fujisawa, Kanagawa 251-8522 JAPAN http://www.azbil.com/ AB-6387 Rev. 5.0 Apr. 2018 Specifications are subject to change without notice. (J: AI-6387 Rev. 3.1)