Wiring design

4-1.General

• All field wiring insulation rating must comply with NEC and local codes.
• Do not connect 208/230 V power to the terminal blocks for control cables (U1, U2, U3, U4); otherwise, the unit may
break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.
• Prepare an exclusive power supply for the air conditioner.

4-2.Outdoor unit power supply

Circuit breaker
Outdoor unit data
Model name
Capacity
MCY-
type
MAP0367HS-UL
36
MAP0487HS-UL
48
MAP0607HS-UL
60
Disconnect per NEC
and local codes.
Power supply
Voltage Range
Phase and
Nominal
Min.
frequency
Voltage
(V)
1Ph 60 Hz
208/230 V
187
1Ph 60 Hz
208/230 V
187
1Ph 60 Hz
208/230 V
187
Compressor
Fan Motor
Max.
(kW)
(kW)
(V)
253
3.75
0.10 x 2
253
3.75
0.10 x 2
253
3.75
0.10 x 2
22
MCA
MOCP
Recommended
(A)
(A)
breaker size
36.3
60
40
36.3
60
40
36.3
60
40