gefran ADV200 WA Functions Description And Parameters List page 24

Field oriented vector ac drive
Table of Contents

Advertisement

Example 2: Speed ref 1 = + 400 rpm
Menu
PAR
Description
5.21
650
Speed ref 1 src
5.22
652
Speed ref 2 src
Selection of the origin (source) of the drive speed reference signals. The values that can be used as speed
references can be selected from those listed in the "L_MLTREF" selection list.
When assigning the reference via terminals, signals with ±10V, 0 ...10V, 0... 20 mA and 4 ... 20 mA can be
used.
Menu
PAR
Description
5.23
654
Speed ref invert src
Selection of the origin (source) of the signal that inverts the speed reference output from the regulator. The ter-
minal that can be used for this function can be selected from among those listed in the "L_DIGSEL2" selection
list.
Menu
PAR
Description
5.24
660
Speed ref 1 mon
5.25
662
Speed ref 2 mon
The value of the relative speed reference is displayed.
Menu
PAR
Description
5.26
670
Speed ref top lim
Setting of the upper speed reference limit. If the speed reference exceeds the limits, the motor speed remains
at the set limit value in any case. Speed limits cannot be more than 200% of the value set in the Full scale
speed parameter (REFERENCES menu par. 680).
Menu
PAR
Description
5.27
672
Speed ref bottom lim
Setting of the lower speed reference limit. If the speed reference exceeds the limits, the motor speed remains
at the set limit value in any case. Speed limits cannot be more than 200% of the value set in the Full scale
speed parameter (REFERENCES menu par. 680).
Menu
PAR
Description
5.28
680
Full scale speed
Setting of the reference value for all speed percentage data (References, Speed adaptives ...) corresponding
to 100 % of the actual speed. This parameter can only be changed with the inverter blocked (Enable drive =
Disabled). The recommended setting for the value of this parameter is the motor rated speed. If altered, the
self-tuning procedure should be repeated.
Full scale speed does not define the maximum possible speed. In any case, the maximum
speed percentage value is ± 200 % of the Full scale speed value.
,
24
Speed ref = 400 rpm – 600 rpm = - 200 rpm
UM
Type
LINK
LINK
UM
Type
LINK
UM
Type
FF
INT16
FF
INT16
UM
Type
FF
INT32
UM
Type
FF
INT32
UM
Type
rpm
INT16
Speed ref 2 = - 600 rpm
FB BIT
Def
16/32
640
16/32
642
FB BIT
Def
16
6000
FB BIT
Def
0
0
FB BIT
Def
CALCI
FB BIT
Def
CALCI
FB BIT
Def
CALCI
ADV200 WA • Functions description and parameters list
Min
Max
0
16384
0
16384
Min
Max
0
16384
Min
Max
0
0
0
0
Min
Max
0
CALCI
Min
Max
CALCI
0
Min
Max
50
32000
Acc
Mod
ERW VS
ERW VS
Acc
Mod
ERWZ VS
Acc
Mod
ER
VS
ER
VS
Acc
Mod
ERWZ VS
Acc
Mod
ERWZ VS
Acc
Mod
RWZ VS

Advertisement

Table of Contents
loading