4.15
Substitution value is active if the block is in bypass
Feature bit
Number of the Feature bit: 9
Substitution value is active if the block is in bypass
You can use this Feature bit to specify whether the block uses the process value or a
substitution value in case of an active bypass.
The default setting is 0.
Bit = 0: Block will use the process value (PV/In/Out).
Bit = 1: Block will use the substitution value (BypPV/BypIn/BypOut).
4.16
Forcing operating modes in the "Local" mode
Feature2 bit
Number of the Feature2 bit: 8
Forcing operating modes in the "Local" mode
You can use this Feature2 bit to specify whether forcing operating modes is possible in the
"Local" mode.
The default setting is 0.
Bit = 0: In the "Local" mode, forcing operating modes is not possible.
Bit = 1: In the "Local" mode, forcing operating modes is possible.
4.17
Read configuration data automatically
Feature bit
Number of the Feature bit: 8
Read configuration data automatically
Using this Feature bit you define if the configuration data is read out automatically at the
restart of the control (OB100) or the re-accessibility of the device via Profibus (OB86, return of
the rack).
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
Configurable response using the Feature I/O
4.17 Read configuration data automatically
57