PRODUCT SPECIFICATION SHEET
ViegaPEX™
Quality Assurance
When the product is marked with the ASTM F876/F877
designation, it affirms that the product was manufactured,
inspected, sampled and tested in accordance with these
specifications and has been found to meet the specified
requirements.
Certifications
- tested for health effects to ANSI/NSF standard
61 and performance to ANSI/NSF standard 14.
NSF CL-R/CL-TD - Tested and conforms to NSF Protocol
P171, Chlorine Resistance of Plastic Piping Materials.
Meets and exceeds pass/fail criteria of both Traditional
Domestic and Domestic Continuous Recirculation ratings.
NSF tested according to ASTM Standard F2023, Evaluating
the Oxidative Resistance of Crosslinked Polyethylene (PEX)
Tubing and Systems to Hot Chlorinated Water greatly
exceeding the minimum chlorine resistance requirements of
ASTM F876.
- IAPMO Certified
- ICBO ER #5287 - listed for plumbing and
hydronic heating applications.
- Intertek Testing Services (Warnock Hersey) -
certification to CSA B137.5 (Canadian
Standards Association)
HUD (Housing and Urban Development) - MR 1276
Minimum Bend Radius
CORRECT:
8 x O.D.
NOTE: ViegaPEX tubing may be bent to a minimum of 5 x O.D.
with approved bend support.
TD-PFVP 0307
INCORRECT:
PIPE FLATTENS
AT THE BEND
2
SDR-9 PEX Tubing
ASTM F876/F877/CTS-OD SDR-9
STOCK TUBING
WALL
CODE
SIZE
O.D.
THICKNESS
PX2
3/8" 0.500±.003
0.070+.010 0.350 .0413
PX3
1/2" 0.625±.004
0.070+.010 0.475 .0535
PX4
3/4" 0.875±.004
0.097+.010 0.671 .1023
PX5
1"
1.125±.005
0.125+.013 0.863 .1689
NOTE: Dimensions are in English units. Tolerances
shown are ASTM requirements. ViegaPEX is
manufactured within these specifications.
Pressure Drop Table
Expressed as PSI/ft. Pressure Drop
SIZE
GPM
3/8"
1/2"
1
.070
.016
1.5
.149
.034
2.2
.303
.069
2.5
.385*
.087
3
.539
.122
3.5
.717
.162
4
.208*
5
.314
6
.440
7
.586
8
9
EXAMPLE: To calculate the
10
pressure drop of a 1/2" line, 40 ft.
11
long, with a 3 gpm flow rate,
12
calculate .122 psi x 40 ft. = 4.9
13
psi pressure drop. Most
14
plumbing codes require 8 psi
16
residual pressure at the fixture.
18
Refer to your local code
20
requirements.
22
*Indicates 8 fps maximum velocity required by some
plumbing codes. NOTE: Maximum flow for each size
based on 12 FPS velocity. PSI x 2.307 = head loss.
Minimum Burst Pressure (PSI) Per ASTM F876/F877
SIZE
73°F (23°C)
3/8"
620
1/2"
480
3/4"
475
1"
475
NOM. WEIGHT VOLUME
(Gal.)
I.D.
PER FT PER 100 FT
0.50
0.92
1.82
3.04
3/4"
1"
.023
.030
.039
.059
.082
.024
.109
.032
.140
.041
.174*
.051
.211
.062
.252
.074
.296
.087
.343
.101
.116
.148*
.184
.224
.267
180°F (82°C)
275
215
210
210
VIEGA
301 N. Main, Floor 9
Wichita, KS 67202
Phone: 1-877-VIEGA-NA
Fax: 1-800-976-9817
service@viega.com
www.viega-na.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MAGNA3 Series and is the answer not in the manual?

Questions and answers

Table of Contents