1. Read this manual before installing or operating. Keep this manual on hand of the end user, and make use of this manual in maintenance and inspection. 2. All information contained in this manual will be changed without notice. Please contact your Toshiba distributor to confirm the latest information.
E6582051 Introduction Thank you for purchasing the PROFINET option “PNE001Z” for the VF-S15 (CPU1 version 112 or later). Before using the PROFINET option, please familiarize yourself with the product and be sure to thoroughly read the instructions and precautions contained in this manual.
Page 5
E6582051 Safety precautions On the drive and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to VF-S15 along with this instruction manual for completely understanding the safety precautions and adhere to the contents of these manuals.
Page 6
▼ When the drive is energized, never detach the this option from the VF- S15. Doing so could result in electric shock. ▼ Don't place or insert any kind of object into the PNE001Z (electrical wire cuttings, rods, wires). Doing so could result in electric shock or fire.
Page 7
E6582051 ■ Wiring Warning ▼ Shut off power when installing and wiring this option. Wait at least 15 minutes and check to make sure that the charge lamp (VF-S15) is no Mandatory longer lit. ▼ Electrical construction work must be done by a qualified expert. Installation or connection of input power by someone who does not have that expert knowledge may result in fire or electric shock.
Page 8
E6582051 Notes on use Notes ▼ Do not install the drive where the temperature or the humidity will change rapidly. ▼ Keep a distance of 20cm or more between the drive 's power cable and the data transmission cable. Or the drive might malfunction because of noise. ▼...
E6582051 1. Overview The PNE001Z is a dual port PROFINET fieldbus module that can be used in a PROFINET industrial fieldbus. The PNE001Z also offers an embedded Web server which offers comfortable monitoring and setup directly from a standard web browser.
E6582051 1.5. LED indicator The LED shows the present status of the network and module. The behavior of LNK LED Link Activity Color and behavior Meaning No link Green Blink Network Activity at 100 Mbps Green ON Link established at 100 Mbps The behavior of BF LED Module Status Color and behavior...
Page 11
E6582051 If the communication card operates as a Modbus TCP server only, LNK LEDs work as follows. The behavior of LNK LED for ModbusTCP Link Activity Color and behavior Meaning No link Green Blink Network Activity at 100 Mbps Green ON Link established at 100 Mbps Yellow Blink Network Activity at 10 Mbps...
1 byte Drive version, MSB 1 byte Software version 1 byte Communication network fault 1 byte Internal link fault 1.7. GSDML file As for acquisition of a GSDML file for VF-S15, please contact your Toshiba distributor. - 9 -...
E6582051 2. Hardware Setup When using the PNE001Z with VF-S15, sold separately VF-S15 option adapter (SBP009Z) is required. 2.1. Mounting and removing Warning ▼ The mounting/removing of option must be performed without supplying power(Turn off all input power, wait at least 15 minutes, confirm that the charge lamp of inverter is no longer lit).
Page 14
E6582051 2.1.2. Earth wire wiring Grounding terminal of option adapter Recommended tightening torque: 0.5N m Connect attached grounding cable to grounding terminal of inverter. Grounding terminal of inverter 2.1.3. Removing of option ① Remove the connector in the direction of arrow while pushing the release tab. Release tab ②...
E6582051 2.2. Wiring PNE001Z is equipped with dual shielded RJ45 connectors. When you use PNE001Z with VF-S15, the shielding of RJ45 connectors are connected to the grounding terminal of option adapter. Cable specifications • Minimum Cat 5e, • Use equipotential bonding conductors, •...
E6582051 2.3. Installation Topology The PNE001Z support several wiring solutions: Daisy Chain and/or Star topology Ring topology Note: The ring topology can only be used with a Media Redundancy Protocol (MRP) capable managed switch. - 13 -...
E6582051 3. Parameters 3.1. Communication parameters This option doesn't operate if these parameters are not correctly set. Communi Default Title Function Description cation No. setting 0: Terminal board 1: Panel keypad (including remote keypad) 0003 Command mode selection 2: RS485 communication cmod 3: CANopen communication 4: Communcation option...
Page 18
E6582051 Communi Default Title Function Description cation No. setting 0.0 - 100.0 sec. The waiting time of network error detection can be adjusted. If a network error continues past the time Communication error detection C100 set in c100, it is recognized as a communication c100 delay time error, and inverter will operate according the setting...
E6582051 3.2. Monitor parameters The following parameters can be used for network status confirmation of the PNE001Z. Communi Title Function Description cation No. 0: - 1: fa06 (Communication command 1) 2: fa23 (Communication command 2) 3: fa07 (Frequency command, 0.01Hz)
Page 20
E6582051 Communi Title Function Description cation No. 0:Telegram 1 (PROFIdrive) 1:Telegram 100 (Vender Spec. 1) C152 c152 Profile monitor 2:Telegram 101 (Vender Spec. 2) 3:Telegram 102 (Vender Spec. 3) C517- The MAC address of the option module. c517- MAC address (*1) C522 [C517 - C518 - C519 - C520 - C521 - C522] c522...
E6582051 3.3. The details of the parameter setting 3.3.1. Device name (c081-c096) This option module can set the "Device name" of 16 characters. (Device name (c081-c096) is 1 character within one parameter.) The device name is required if the option module uses DHCP to obtain its IP Address. Please set the setting of the device name according to the following rules.
Page 22
IP mode Comments The option uses the address defined in c505-c516. Don’t use on PNE001Z. The option receives its address from a DHCP server. *Device name contains (c081-c096) a valid name. The option receives its address from PROFINET controller.
E6582051 4.2. STW Control Word Data PNE001Z supports only speed control mode. Bit Value Name Note “Switched on” condition Normal stop. No Coast Stop All "Coast Stop (OFF2)" commands are withdrawn Coast Stop (OFF 2) Coast stop. No Quick Stop All "Quick Stop (OFF3)"...
E6582051 4.3. ZSW Status Word Data Value Name Note Ready To Switch-on Power supply is switched on Not Ready To Switch-on Ready To Operate Refer to control word, bit 1. Not Ready To Operate Drive follows set point. Operation Enabled (Refer to control word 1, bit 3) Operation Disabled Fault Present...
Page 26
3. Start the timer which will time-out based on parameter Tmax. PNE001Z checks that the timer (Tmax) has not timed-out and if the actual value is within the tolerance. If both conditions are fulfilled ZSW Bit 8 is set 1 and the timer is stopped.
E6582051 4.4. State Machine ZSW Bit 6 = 1 SWITCH-ON MAINS OFF INHIBIT Power ON STW Bit 0 = 0 A B C D ZSW Bit 0 = 0 NOT READY TO SWITCH-ON from any state STW Bit 3 = 0 STW: xxxx xxxx xxxx x110 FAULT OPERATION...
Page 28
E6582051 4.4.1. Examples of driving by the State Machine When using the PROFIdrive profile, the frequency reference is set to HSW. The setting value “0x0000” - ”0x4000” is equivalent to ”0” - ”Base frequency (parameter )”. When the reverse operation, the frequency reference is set with two's complement of the forward frequency reference.
E6582051 5. Vendor Specification Profile Cyclic command transmission is possible for PNE001Z by the original profile Select the ”Telegram 100”, ”Telegram 101” or ”Telegram 102” as the profile on the configuration. Refer to the PLC configuration tool documents. You will be able to select the command and monitor items from the following table.
And Since 0 and 1 byte of the PZD1 supports the parameter , if "0xC400" is set up here, "0xC400" c001 will be set as fa06 VF-S15 PROFINET Master PNE001Z Parameter Value 1 (FA06) c001 c002 c003 PZD1 PZD2 PZD3 "0xC400"...
E6582051 5.5. The overview of the VF-S15 parameter Refer to a communication functional description (E6581913) for details. 5.5.1. fa06 (Communication command1) Function Note Preset speed operation Preset speed operation is disabled frequencies 1 or preset speed operation Preset speed operation frequencies (1-15) are set by frequencies 2 specifying bits for preset speed...
Page 33
E6582051 5.5.2. fa23 (Communication command 2) Function Note (Reserved) Electric power quantity Electric power quantity (fe76, Reset reset fe77) reset (Reserved) (Reserved) (Reserved) (Reserved) (Reserved) Maximum deceleration Normal Enabled forced stop Select acceleration/deceleration Acceleration/decele- 00: Acceleration/deceleration 1 1-4 by combination of two bits.. ration selection 1 01: Acceleration/deceleration 2 AD1: acc, dec...
Page 34
E6582051 5.5.6. fd01 (Inverter operating status 1 (real time)) Function Note Failure FL No output Under in progress - Trip status includes rtry and Failure Not tripped Tripped the trip retention status are also regarded as tripped statuses. Alarm No alarm Alarm issued Under voltage (moff) Normal Under voltage...
Page 35
E6582051 5.5.8. fd03 (Output current (real time)) The output current is read into 0.01% of units and by the hexadecimal number. For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal number) is read out. Since the minimum unit is 0.01%, 0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%) Also about the following parameters, these are the same as this.
Page 36
E6582051 5.5.12. fc91 (Alarm code) Remarks Function (Code displayed on the panel) Over-current alarm Normal Alarming c flicking Inverter over load alarm Normal Alarming l flicking Motor over load alarm Normal Alarming l flicking Over heat alarm Normal Alarming h flicking Over voltage alarm Normal Alarming...
E6582051 5.7. PROFIdrive parameter (PNU) data type Note Array [6] PNU 915, IND 0 = the drive parameter c001 Unsigned16 PNU 915, IND 1 = the drive parameter c002 PNU 915, IND 2 = the drive parameter c003 PNU 915, IND 3 = the drive parameter c004 PNU 915, IND 4 = the drive parameter c005 PNU 915, IND 5 = the drive parameter c006 Array [6]...
Page 39
5.7.1.2. Example 2. Reading the PNU 964, IND 0 AK = 6 (Request parameter value (array)) SPM = 0 PNU = 964 (0x03C4) IND = 0 (PNE001Z ID) Requirement ・・・ ・・・ Response (Value: 0x0190 = PNE001Z ID) ・・・ ・・・ - 36 -...
E6582051 5.8. Access to drive parameter When access to drive parameter, set “1” to the PNU. The communication number of the drive parameter is set to the sub index IND. Refer to the drive instruction manual about the communication number and unit. * This procedure changes the value of drive EEPROM.
Page 41
E6582051 5.8.1.3. Example 3. Reading the status monitor parameter ( (The operation frequency)) fe02 AK = 6 (Request parameter value (array)) SPM = 0 PNU = 1 IND = 0xFE02(fe02 communication number) Requirement ・・・ ・・・ Response (Value: 0x03E8 (= 1000 -> 10.00Hz)) ・・・...
E6582051 6. PROFIdrive acyclic parameter access In PNE001Z, inverter parameters and PROFIdrive parameters are accessible by acyclic communications in addition to the cyclic communication via Telegram 100 or101. 6.1. Example1. Read the PROFIdrive parameter 6.1.1. Request data table (Read PNU 964 (0x03C4) IND 0)
E6582051 6.3. Example 3. Read the VF-S15 parameter When access to VF-S15 parameter, set “1000” to the PNU. 6.3.1. Request data table (Read (Input voltage)) fd04 Field Description Value Request Header (Byte 1) Request Reference 0x01 Request Header (Byte 2) Request ID (0x01: Request) * 0x01 Request Header (Byte 3)
E6582051 6.4. Example 4. Change the VF-S15 parameter When access to VF-S15 parameter, set “1000” to the PNU. * This procedure changes the value of VF-S15 EEPROM. 6.4.1. Request data table (Change, set 7 to VF-S15 parameter f130 Field Description Value Request Header (Byte 1) Request Reference...
0x02: Positive response for Change the value 0x81: Negative response for Request the value 0x82: Negative response for Change the value Axis 0x01: (Fixed for PNE001Z) Error number 0x00: Impermissible parameter number 0x01: Impermissible parameter number 0x02: Low or High limit exceeded...
Unit ID Modbus TCP server Accessible data 0-248 Inverter (VF-S15) Inverter parameter Device identification of inverter Communication module (PNE001Z) Device identifications of module 7.3. List of Modbus functions supported Function code Function name Description Size of data Read Holding Registers Read N output words 63 words max.
Last Point Data Lo Exception response format: Byte Meaning Function Code = 83h Exception Code = 01 (Illegal Function) 02 (Illegal Data Address) 03 (Illegal Data Value) Notes If the communication number that doesn't exist is read, PNE001Z returns 0x8000. - 45 -...
E6582051 7.5. "06 (0x06) Write Single Register" function This Modbus request is used to write a given value (Present Data) to the address supplied (Register Address). Request format: Byte Meaning Function Code = 06h Register Address Hi Register Address Lo Preset Data Hi Preset Data Lo Response format:...
E6582051 7.6. "16 (0x10) Write Multiple Registers" function This Modbus request is used to write a number (Number of Registers) of adjacent words starting at a given address (Starting Address). The values to be written are supplied one after another (First Register Data -> Last Register Data).
Read Device ID code 01: Basic 02: Regular 03: Extended Object ID Response format: (ID = 0 - 248) Byte Meaning With the PNE001Z Function Code = 2Bh Type of MEI Read Device ID code 01: Basic 02: Regular 03: Extended Conformity Level...
Page 52
E6582051 Response format: (ID = 251) Byte Meaning With the PNE001Z Function Code = 2Bh Type of MEI Read Device ID code 01: Basic 02: Regular 03: Extended Conformity Level More Follows Next Object Id Number Of Objects 3 for Basic.
The option has webserver function. Writing and reading the drive's parameter and the communication can be monitored by using this function through web network. The chapter describes the function of the integrated webserver of PNE001Z. 8.1. Access to the webserver This web server can be accessed by the navigators listed below: ®...
Page 54
E6582051 From the Home page, you can access to 3 main menus: Home Monitoring Drive Monitor Drive parameters Network Setup Network Parameters Administration Diagnostics TCP/IP Statistics Modbus Statistics If the screen does not appear well, please try to return the magnification of IE7 to 100% - 51 -...
E6582051 8.2. Web pages structure Each web page uses the same structure. Each main menu, "Monitoring", "Network Setup" and "Diagnostics" contains each own sub menu. Sub menus are displayed on the left side of web page. 8.3. Drive Monitor (Main menu: Monitoring) The state of the drive can be confirmed on this page.
E6582051 8.4. Drive parameters (Main menu: Monitoring) The parameters of the drive can be set on this page. The left column is used to select a modify group (or list) of parameters. The right column displays the parameters, its Modbus address and its current value. Start the monitor Set the parameters When you modify the drive parameter from the webserver, please press the set button, and input the...
E6582051 Set the parameters value Input the write value to popup window. 8.5. Network parameters (Main menu: Network Setup) The network parameters of the drive can be confirmed on this page. - 54 -...
E6582051 8.6. Administration (Main menu: Network Setup) The "web read password" and "web write password" of the webserver can be modify on this page. Press the “Password” button, and enter the “web write password”. After that, press the Enter key. Enter the new password, and press the “Save”...
E6582051 8.7. TCP/IP statistics (Main menu: Diagnostics) You can check TCP/IP status on this page. 8.8. Mod statistics (Main menu: Diagnostics) You can check Modbus status on this page. - 56 -...
E6582051 8.9. Activation of JAVA7 To observe the webserver, the version of Java must be at least 1.7.67 in the bits version of your internet browser. We recommend using Internet Explorer. If the version 1.8.25 or other 1.8 version are already installed on your computer, you can install the 1.7.67 too.
Page 61
E6582051 8.9.2. Delete temporary files If you had started a web server in the JAVA8, you will need to delete the temporary file with the following procedure. “OK” to validate and close this window. - 58 -...
Page 62
E6582051 8.9.3. Launch webserver after activation Launch the webserver and enter your username and password. After the loading of Java application, you will see bellow window. Please select “Execute”. After that, you will see a new window, please select “Authorize the execution of the application with the requested version (1.7.67)”...