Troubleshooting
Fault Codes
No.
PCB Port
1
TH1
2
TH2
3
TH3
4
TH4
5
TH5
6
TH6
7
TH7
8
TH8
9
TH9
10
TH10
11
TH11
12
TH12
13
CN13
14
CN14
15
IND3
16
IND4
17
IND5
18
IND6
19
IND8
20
IND9
21
CN13
22
CN14
TH2 and
23
TH1-TH2
24
TH3、TH8
25
CN13
26
CN14
27
TH4、TH9
28
TH7
Communication failure between PCB and modular
29
CN29
Communication failure between unit controller and
30
CN4/XP1
TH5,TH6,
31
TH10,TH11
32
CN15
No.15 analog sensor fault (discharge pressure A)
33
CN16
No.15 analog sensor fault (discharge pressure B)
34
/ / /
35
/ / /
Water inlet and outlet connected reversely
PKGP-SVX18B-EN
Fault Description
No.1 analog sensor fault
No.2 analog sensor fault
No.3 analog sensor fault
No.4 analog sensor fault
No.5 analog sensor fault
No.6 analog sensor fault
No.7 analog sensor fault
No.8 analog sensor fault
No.9 analog sensor fault
No.10 analog sensor fault
No.11 analog sensor fault
No.12 analog sensor fault
No.13 analog sensor fault
No.14 analog sensor fault
High-pressure alarm of systemA
High-pressure alarm of systemB
Water flow switch alarm
Overload of water pump
Overload of compressor 1
Overload of compressor 2
Low-pressure alarm of systemA
Low-pressure alarm of systemB
Freezing protection
Abnormal suction temperature
Low pressure overrun A
Low pressure overrun B
Coil superheating
Ambient temperature out of range
controller
PCB
Abnormal discharge temperature
Unit locked
Code on
Code on unit
Modular
controller
controller
20
20
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
2A
2A
2B
2B
2C
2C
2D
2D
H2
65
H1
64
FL
6D
OP
6A
C1
68
C2
69
L1
66
L2
67
E3
8D
E4
91
78
78
7A
7A
98
98
87
87
ED
-
EE
-
AC,AD,
AC,AD,
AE,AF
AE,AF
2E
2E
2F
2F
E0
E0
A0
A0
Fault Handling
Shut down
Shut down
Shut down
Shut down
Shut down
Shut down
Shut down
Shut down
2
Shut down
2
Shut down
2
Shut down
2
Shut down
4
Shut down
2
Shut down
Shut down
2
Shut down
Shut down
Shut down
Shut down
Shut down
2
Shut down
Shut down
2
Shut down all compressors, and keep
the pump continuously running
Shut down all compressors, and keep
the pump continuously running
Shut down the compressors of the
system A. If the fault occurs for two
times within 1 hour, shut down and
give an alarm.
Shut down the compressors of the
system B. If the fault occurs for two
times within 1 hour, shut down and
give an alarm
2
Shut down
2
Shut down
Shut down
Shut down
Shut down
Shut down
Shut down
Forbid starting
Shut down and alarm
1
1 2
41
Need help?
Do you have a question about the CXAJ065 and is the answer not in the manual?