Installation Manual
8.3 Adding Refrigerant
In North America, the standard pipe length is 7.5m (25'). The additional refrigerant
to be charged can be calculated using the following formula:
Additional refrigerant per pipe length
Connective Pipe
< Standard pipe length
> Standard pipe length
Table 8
CAUTION: CONTAINS REFRIGERANT
NEVER mix refrigerant types.
Bosch Thermotechnology Corp. | 03.2019
Bosch Climate 5000 Series Wall Mounted Ductless Single Split Air Conditioner / Heat Pump | 25
Air Purging
Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25")
Vacuum Pump
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Additional Refrigerant
N/A
Inverter R410A:
Liquid Side: Ø 9.52 (ø 0.375")
Inverter R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Data subject to change