11
Operation
(continued)
rst (Reset) - Used to reset the boiler from a
hard lockout (as an alternative to momentarily
interrupting power to the control). Pressing the up
key will turn rst momentarily to on. When it goes
back off (typically within one or two seconds), the
control is reset.
F-C (Temperature Units ) - Determines whether
temperature units on the S9361A are displayed in
F or C. Note that this selection only applies to the
temperature displayed on the LED shown in Figure
11.1.
Call for
Example
Heat
Use of DHW
#
From
1
T-T
2
T-T
3
DHW
DHW (dh=dh)
Heat
T'stat on
4
DHW
terminals
5
T-T
6
T-T
109838-01 - 5/20
Table 11.7: Examples Of Thermal Purge Operation
Thermal Purge
Settings
Zone
Time (Pt)
N/A
2 min.
N/A
2 min.
2 min.
Heat
2 min.
(dh=tt2)
N/A
2 min.
N/A
3 min.
Installation, Operating & Service Manual
X-PV
bAc (Return to Status mode) - Exits adjustment
mode. Any changes made to the parameters
described above are saved, and become
effective, as soon as they are made; bAc only exits
adjustment mode.
Boiler
Temp at
Start Temp
Begin
(St)
Call
140F
130
140F
150
140F
150
140F
150
145F
150
140
150
Boiler Behavior
Heating Circulator starts
immediately
Burner fires immediately
Heating Circulator starts
immediately
Burner fires when either:
2 minutes have passed
OR
Temperature falls below 140
DHW Circulator starts immedi-
ately
Burner fires immediately
"DHW" Circulator starts
immediately
Burner fires when either:
2 minutes have passed
OR
Temperature falls below 140
Heating Circulator starts
immediately
Burner fires when either:
2 minutes have passed
OR
Temperature falls below 145
Heating Circulator starts imme-
diately
Burner fires when either:
3 minutes have passed
OR
Temperature falls below 140
41