Operation
7
Operation
7.1
Messages
When the supply voltage is switched on, the PNOZmulti safety system copies the configur-
ation from the chip card.
The LEDs "POWER", "DIAG", "FAULT", "IFAULT" and "OFAULT" will light up on the base
unit.
The expansion module PNOZ m ES Profibus is configured and started automatically. The
"ONLINE" and "OFFLINE" LEDs indicate the status of the PNOZ m ES Profibus on
PROFIBUS-DP.
If the expansion module PNOZ m ES Profibus does not receive a configuration from the
base unit for a period of 30 s, the expansion module PNOZ m ES Profibus connects to
PROFIBUS-DP and the "ONLINE" status is displayed on the PROFIBUS-DP. The error
message "No Connection with Base Module" is sent to the Master.
Legend
LED
POWER
ONLINE
OFFLINE
Operating Manual PNOZ m ES Profibus
1002698-EN-05
LED on
LED flashes
LED off
Meaning
Supply voltage is present
Supply voltage is not present
PNOZ m ES Profibus Online, data exchange is possible
Master has sent the telegram "Global Control Clear". Virtual input bits i0 ...
i127 are set to "0".
PNOZ m ES Profibus Not online
PNOZ m ES Profibus Offline, data exchange is not possible
PNOZ m ES Profibus Not offline