INSTALLATION AND MAINTENANCE INSTRUCTIONS
FZM-1 Interface Module
Specifications
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC wiring resistance:
External Supply Voltage (between Terminals T3 and T4)
DC Voltage:
Ripple Voltage:
Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Before Installing
This information is included as a quick reference installa-
tion guide. Refer to the control panel installation manual
for detailed system information. If the modules will be
installed in an existing operational system, inform the
operator and local authority that the system will be tempo-
rarily out of service. Disconnect power to the control panel
before installing the modules.
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The FZM-1 Interface Module is intended for use in intel-
ligent, two-wire systems, where the individual address of
each module is selected using the built-in rotary switches.
This module allows intelligent panels to interface and moni-
tor two-wire conventional smoke detectors. It transmits the
status (normal, open, or alarm) of one full zone of con-
ventional detectors back to the control panel. All two-wire
detectors being monitored must be UL compatible with this
module. The FZM-1 has a panel controlled LED indicator
and can be used to replace an MMX-2 module in existing
systems.
Compatibility Requirements
To ensure proper operation, this module shall be connected
to a compatible Notifier system control panel only (list
available from Notifier).
Mounting
The FZM-1 mounts directly to 4 square electrical boxes (see
Figure 2A). The box must have a minimum depth of 2
Surface mounted electrical boxes (SMB500) are available
from Notifier
Wiring
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations. This module is intend-
ed for power-limited wiring only.
N500-49-00
www.PDF-Zoo.com
15 to 32 VDC
5.1 mA (LED on)
270µA (LED flashing)
3.9K Ohms
25 Ohms
18-28 volts power limited (19 to 28VDC when used with MTL isolator model MTL3043 in
intrinsically safe applications)
0.1 Volts RMS maximum
90mA per module
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Noncondensing
4
H x 4 W x 1
D (Mounts to a 4 square by 2
1
1
/2
/4
SMB500 Electrical Box
1
.
/8
1
1
/8
1. Install module wiring in accordance with the job draw-
ings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Some panels support extended addressing. In
order to set the module above address 99 on compatible
systems, carefully remove the stop on the upper rotary
switch with thumb in the direction shown in Figure 1.
3. Secure module to electrical box (supplied by installer),
as shown in Figure 2A.
Figure 1. Removing
Rotary Switch Stop:
Figure 2A. Module mounting:
A78-2610-10
12 Clintonville Rd
Northford, CT 06472-1653
(203) 484-7161
deep box.)
9
0
7 8
9
6
5
10
8
4
11
1
3
12
13
2
7
2
1
14
0
15
TENS
6 7 8 9
5
6
3
4
3
5
4
2
1
0
ONES
ADDRESS
LOOP
Figure 2B:
A78-2611-12
I56-1172-06
A78-2318-07

Advertisement

loading
Need help?

Need help?

Do you have a question about the FZM-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier FZM-1

  • Page 1 Figure 1. Removing Rotary Switch Stop: General Description The FZM-1 Interface Module is intended for use in intel- TENS 6 7 8 9 ligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches.
  • Page 2 RUN TO PROVIDE SUPERVISION OF CONNECTIONS. OPTIONAL BRANCH CIRCUIT DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. TO NEXT INTERFACE MODULE. INSTALL DETECTORS PER MANUFACTURER'S MODULE SUPERVISES SUPPLY A78-2394-29 INSTALLATION INSTRUCTIONS. VOLTAGE AND DETECTOR LOOP. N500-49-00 I56-1172-06 www.PDF-Zoo.com © 2001 Notifier...