All measurements are given in mm unless stated oth- Heat pump operating and installation instructions erwise. Operating and installation instructions for system components WPM system notification list Safety Note Only a qualified contractor should carry out installation, commis- sioning, maintenance and repair of the appliance.
High efficiency circulation pumps can be connected directly via relay outputs or PWM outputs. The PCB of the WPM is located in a wall mounting enclosure that can also accommodate other components such as the relay for the top-hat rail.
These additional functions can be adjusted In conjunction with a control unit for underfloor heating, one room on the programming unit of the WPM heat pump manager. temperature sensor is required per room. The WPE heat pump extension provides:...
Note Note The recesses on the retaining clip are of different sizes. In conjunction with the WPM heat pump manager, use the HSM mixer servomotor. f Press the smaller recess on the retaining clip into one of the notches on the sensor.
Connect the remote control to terminal X1.13. Bus initialisation Connecting the bus cable not only establishes the electrical con- nection for system communication. As part of commissioning, connecting the bus cable will also assign the appliance-specific address required for switching the heat pump. www.stiebel-eltron.com WPM |...
All necessary sensors must be connected before the volt- illuminated. age is connected to the WPM. Any sensors connected later f Release the reset key. The IWS has now been reset and is will not be recognised by the WPM.
SET TEMPERATURE FET 4 °C Set room temperature for the allocated heating circuit COMPRESSOR (displayed only if FET remote control is connected) SILENT MODE RELATIVE HUMIDITY FET 4 I/O CONFIGURATION www.stiebel-eltron.com WPM |...
Page 10
SET TEMPERATURE FIXED VALUE °C HYBRID MODULE ACTUAL TEMPERATURE 2ND HEAT GENERATOR °C DIFFERENTIAL CONTROLLER 1 SET TEMPERATURE 2ND HEAT GENERATOR °C SENSOR TEMPERATURE 1 °C | WPM www.stiebel-eltron.com...
2. SET COMPRESSOR SPEED NHZ 1/2 Hours Runtime of electric emergency/booster heater in booster REL FAN RATE stages 1 and 2. ACTUAL FAN SPEED DEFROST TIME Minutes www.stiebel-eltron.com WPM |...
COMFORT MODE or START TIME PROGRAMMED OPERATION. DAYS DHW CIRCULATION PROGRAM SWIMMING POOL PROGRAM SILENT PROGRAM 1 SILENT PROGRAM 2 | WPM www.stiebel-eltron.com...
TINGS / SILENT MODE / OUTPUT REDUCTION / OUTPUT” back Heating circuit sensor 1 must be connected to the heat pump. to its initial value. Buffer charging pump 1 acts as heating circuit pump 1. The heat pump extension has no function here. www.stiebel-eltron.com WPM |...
Here you can set how long the LOW END TEMPERATURE is main- By reducing the fan speed, the noise level of the heat pump is tained. reduced. On certain heat pumps, the compressor power may also be reduced. | WPM www.stiebel-eltron.com...
COMFORT TEMPERATURE ECO TEMPERATURE MINIMUM TEMPERATURE DHW TEMPERATURES MAXIMUM TEMPERATURE COMFORT TEMPERATURE MIXER DYNAMICS ECO TEMPERATURE ROOM INFLUENCE www.stiebel-eltron.com WPM |...
Page 18
PEAK TARIFF PRICE OFF-PEAK TARIFF PRICE COOLING CIRCUIT 1 GAS PRICE SET FLOW TEMPERATURE OIL PRICE SET ROOM TEMPERATURE ECOLOGICAL COOLING TYPE | WPM www.stiebel-eltron.com...
If no code is entered, only faults relevant to the device user are displayed in the message list. www.stiebel-eltron.com WPM |...
Page 20
MIXER DYNAMICS Using this value, the control characteristics or the effect of mixer runtime on the controller can be adjusted. Mixer runtime [s] WPM setting ROOM INFLUENCE X Outside temperature [°C] Only in conjunction with a remote control.
Page 21
With this parameter, automatic shutdown of heating mode can be activated in summer. Control characteristics can be based on the return temperature, the flow temperature or on a specified combination of the two www.stiebel-eltron.com WPM |...
Page 22
With room temperature-dependent control, the room is heated Fixed value operation relates solely to the control characteristics consistently to the temperature set on the remote control. of heating circuit 1. | WPM www.stiebel-eltron.com...
Page 23
In this menu item, you can specify the parameters of an external - The heat pump is in operation. heat source. - The temperature must be at least 5 K lower than the set boil- er temperature (parameter SET BOILER TEMPERATURE). Conditions for deactivation: www.stiebel-eltron.com WPM |...
Page 24
Set the number of hours of blocking time after which the ex- (after the temperature has fallen below the dual mode tempera- ternal heat source should assume responsibility for heating. ture) before the additional heating levels are switched on. Confirm the selection with OK. | WPM www.stiebel-eltron.com...
In this menu item you can set whether a combi or instantaneous water cylinder is installed in the heat pump system. DHW HYSTERESIS With this parameter, you can specify the switching hysteresis for DHW heating. www.stiebel-eltron.com WPM |...
Page 26
DHW demand, outputs X2.8 and X2.11 are Pasteurisation can only occur if the electric emergency/booster switched. heater is connected, or EXTERNAL HEAT SOURCE has been defined | WPM www.stiebel-eltron.com...
This switching output is linked to the DHW circulation sensor input and the sensor earth, so the switching is recognised as a short circuit and thus the pump switches on. www.stiebel-eltron.com WPM |...
Page 28
Set the number of hours of tariff blocking time until the ex- ternal heat generator should start providing heating. Confirm PEAK TARIFF PRICE the selection with OK. f Enter the current electricity tariff price. | WPM www.stiebel-eltron.com...
With a brine/water heat pump, if a DHW heating demand is issued, With this parameter, the lower application limit for cooling mode cooling mode is interrupted and DHW heating begins. is specified. If the outside temperature is below the set application limit, cooling mode is deactivated. www.stiebel-eltron.com WPM |...
Page 30
The higher the set dynamics, the slower the downstream heat pumps start up. See description above. - Dynamic 1 After the controller output X2.13 has been switched, the source and buffer charging pumps start in sequence, each after a delay of one minute. | WPM www.stiebel-eltron.com...
Only when the temperature of the swimming pool water is started. differential has reached the start differential minus the set hys- teresis does the output switch off. www.stiebel-eltron.com WPM |...
The value set here specifies the temperature difference from the ADJUSTABLE PUMP RATE set temperature at which the output (X4.10) switches off. SPREAD CONTROL SET VALUES PUMP RATE SPREAD STANDARD SETTING | WPM www.stiebel-eltron.com...
Page 33
PRESET TEMPERATURE 10 V HK PUMP 4 OUTPUT X1.16 HK PUMP 5 PWM 0%...100% OUTPUT PWM 100%...0% 0-10 V 0-10 V OUTPUT www.stiebel-eltron.com WPM |...
With this parameter, you set the minimum flow rate and therefore With these parameters, the operating characteristics and control the pump rate. The pump rate does not fall below the value set of the charging pumps can be specified. here. | WPM www.stiebel-eltron.com...
The time taken to achieve the set spread can vary on account of Please note that high flow temperatures or low outside tempera- this setting. tures may cause the heating output to be reduced. www.stiebel-eltron.com WPM |...
Gateway is required. During the tariff blocking time, the heat pump and the electric emergency/booster heater are blocked. Note This function is available from software version: - WPM: 449-02 HEAT PUMP - ISG: 4.10.0.0 The heat pump is blocked during the tariff blocking time.
Page 38
Please also note the information on flow rate (see the operat- 7 12 15 PWM % ing instructions for the pump and the chapter “Specification / Data table” in the operating and installation instructions for the heat pump). | WPM www.stiebel-eltron.com...
Set the pump rate here. f Observe the operating instructions of the pump manufacturer. 0-10 V f Set the pump rate here. EMERGENCY OPERATION Response to a shutdown of the heat pump in the event of a fault. www.stiebel-eltron.com WPM |...
SENSOR CALIBRATION If the sensors do not measure the temperature correctly, you can correct the measured temperature by +/-5 K in this menu. ACTUAL FLOW TEMPERATURE WP f Correct the measured temperature by +/-5 K. | WPM www.stiebel-eltron.com...
ROOM INFLUENCE ROOM CORRECTION PUMP CYCLES OFF | ON EXTERNAL HEAT SOURCE OFF | ON THREADED IMMERSION HEATER OFF | ON BOILER OFF | ON www.stiebel-eltron.com WPM |...
Page 42
OFF | ON OIL NON-CONDENSING OFF | ON 2ND HEAT GENERATOR SETTING SET TEMPERATURE HYSTERESIS MIXER DYNAMICS HEATING CURVE GAP SOFT START TEMPERATURE | WPM www.stiebel-eltron.com...
Page 43
STANDARD SETTING COOLING STAGES COOLING LIMIT °C COOLING CAPACITY FLOW TEMP HYSTERESIS DYNAMICS ACTIVE DYNAMICS PASSIVE COOLING CIRCUIT 1 OFF | ON www.stiebel-eltron.com WPM |...
Page 44
PUMP RATE HEATING TYPE OF CONTROL MINIMUM PUMP RATE OFF | ON AVERAGE PUMP RATE MAXIMUM PUMP RATE ADJUSTABLE PUMP RATE SPREAD CONTROL | WPM www.stiebel-eltron.com...
Page 45
DESIGN TEMPERATURE °C -15 °C HEAT DEMAND 15 kW CONSTANT OUTPUT 10 kW CONDENSATE RIBBON HEATER OUTSIDE TEMPERATURE °C 5 °C QUICK START OFF | ON www.stiebel-eltron.com WPM |...
Page 47
SYSTEM OFF | ON OFF | ON OFF | ON SENSOR CALIBRATION ACTUAL FLOW TEMPERATURE WP ACTUAL FLOW TEMPERATURE NHZ ACTUAL RETURN TEMPERATURE WP www.stiebel-eltron.com WPM |...
10. Appliance handover 12. Care Explain the appliance function to users and familiarise them with WPM heat pump manager in wall mounted enclosure how it works. A damp cloth is all you need to care for the plastic parts. Never use abrasive or corrosive cleaning agents.
- Restart the system. corresponding fault is written to the message list. - If an ISG is installed, the WPM must have completely started Once the fault time on the IWS and the idle time have elapsed, the up before you reconnect the ISG power supply.