Chapter 6 Wiring; Terminal Blocks - Mitsubishi Electric MELSEC iQ-R Series User Manual

Analog-digital converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

6
WIRING
This chapter describes the wiring of the A/D converter module.
6.1

Terminal Blocks

Precautions
Tighten the module fixing screws and others within the specified torque range.
Screw type
*1
Module fixing screw (M3)
Terminal screw (M3)
Terminal block mounting screw (M3.5)
*1 The hook on the top of the module allows the module to be fixed to a base unit easily. In a place where there is a lot of vibration,
however, fixing with module fixing screws is recommended.
The following table lists an applicable solderless terminal to be connected to the terminal block. When wiring, use the wire and
tightening torque applicable to the table. Use UL listed solderless terminals and, for processing, use the tools recommended
by their manufacturer. Note that a solderless terminal with an insulation sleeve cannot be used.
Solderless terminal
Model
Applicable
tightening torque
R1.25-3
0.42 to 0.58Nm
Signal names of the terminal blocks
The following table shows signal names of the terminal blocks.
■R60AD4
Terminal block
CH1
V-/I-
SLD
CH2
V-/I-
SLD
CH3
V-/I-
SLD
CH4
V-/I-
SLD
FG
Wire
Diameter
0.3 to 0.75
(22 to 18 AWG)
Terminal number
1
2
3
4
5
6
CH1
7
V+
8
CH1
I+
9
CH2
V+
10
CH2
I+
11
CH3
12
V+
CH3
13
I+
CH4
14
V+
15
CH4
I+
16
AG
17
18
Tightening torque range
0.37 to 0.48Nm
0.42 to 0.58Nm
0.66 to 0.89Nm
Type
Material
Stranded
Copper
Signal name
CH1
CH2
CH3
CH4
AG
FG
Temperature rating
75 or greater
V+
V-/I-
I+
SLD
V+
V-/I-
I+
SLD
V+
V-/I-
I+
SLD
V+
V-/I-
I+
SLD
6 WIRING