Download Print this page

Powers Hydroguard PB410 Series Quick Manual

Pressure balancing mixing valves

Advertisement

Quick Links

Product Specification
Description
n
The Series PB410 HydroGuard
mixer, which delivers a predetermined water temperature,
compensating for pressure fluctuations in the hot or cold
water supplies.
The Series PB410 HydroGuard
construction a poppet-type equalizing valve as part of a
replaceable cartridge. The poppet-type construction offers
a distinct advantage in that it will not stick because of lime
build-up or foreign particles in the supplies. The adjustable
metal-to-metal temperature limit stop prevents accidental
scalding caused by over adjustment of the handle. It also
features integral check stops, back-to-back and shallow wall
installation capability.
Specifications
n
Connections: ..........................................................................
Capacity: ............................................................................................ 5.0 gpm (19L/min.)
Maximum Hot Water Supply Temperature: ....................................... 190°F (88°C)
Maximum Static Pressure: ........................................................... 125 psig (862 kPa)
Maximum Operating Pressure: .................................................... 125 psig (862 kPa)
High Temperature Limit Stop: ..................................... Metal to Metal, Adjustable
Certification: ................................................................................................... CSA B125
Listing: ............................................................................................................. ASSE 1016
Shipping Weight: ................................................................................
Application
n
The Series PB410 HydroGuard
and bath and shower installations for motels, hotels, dormito-
ries, health clubs and high rise apartment buildings.
Operation (See Figure 1)
Hot and cold water enter their respective ports and the
pressures are equalized through the action of the balance
poppet. The entire balancing poppet assembly is contained
in a Celcon cartridge. After the hot and cold pressures are
equalized, they are mixed by the action of a mixing plate. As
the temperature adjustment stem is rotated from shutoff to
maximum hot water temperature, the mixing plate passes
the required proportion of hot and cold water to produce the
control point. With the adjustment stem in its full clockwise
position, shutoff is obtained by closing both supplies.
The temperature limit stop allows the user to set the maxi-
mum discharge temperature. This mixer does not recognize
supply water temperature changes, so any variation in the
water temperature will affect the control point and the maxi-
mum temperature setting.
Series PB410 Pressure Balancing Mixing Valves
is a pressure-compensating
®
features heavy, cast brass
®
" Sweat Inlets/Outlets
1
2
is recommended in showers
®
n
Type PB413/Type P417 (4 port)
Model PB41700000
4.5 lbs. (2.0 kg)
IS-P-PB410

Advertisement

loading
Need help?

Need help?

Do you have a question about the Hydroguard PB410 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Powers Hydroguard PB410 Series

  • Page 1 IS-P-PB410 Series PB410 Pressure Balancing Mixing Valves Type PB413/Type P417 (4 port) Product Specification Description The Series PB410 HydroGuard is a pressure-compensating ® mixer, which delivers a predetermined water temperature, compensating for pressure fluctuations in the hot or cold water supplies. The Series PB410 HydroGuard features heavy, cast brass ®...
  • Page 2 Installation Note: Installation should be in accordance with Figure 1 accepted plumbing practices. Flush all piping thor- Cold Water Supply oughly before installation. 1. Position mixer 1 ⁄ " ± ⁄ " [49mm ± 13mm] from inlet center to Balance Poppet Assembly finished wall surface.
  • Page 3 Installation Cont. 12. The high-temperature limit stop is located at the center of Figure 3 - Rough-in Dimensions - Shower ONLY the bonnet. To adjust the temperature, unscrew two bon- net screws halfway. To increase the temperature, rotate the stem counter-clockwise to the required temperature using the handle for leverage.
  • Page 4 Worn shutoff discs. Replace cartridge. b. Scratched mixing plate. Replace Bonnet/Stem Kit. c. Erosion. Contact a Powers applications engineer to order replacement parts. • Maximum temperature is too low. a. Accumulation of lime deposits in hot water pipes, which restricts the flow of hot water.

This manual is also suitable for: