Training Manual FT 51 All the technical strengths, installation and maintenance: Panther Condens 12 KKO 25 KKO 25 KKV 30 KKO...
Page 2
T e c h n i c a l T r a i n i n g T e c h n i c a l T r a i n i n g > > > I n t r o d u c t i o n ............>...
Page 3
T e c h n i c a l T r a i n i n g T e c h n i c a l T r a i n i n g > > > I n t r o d u c t i o n ............This new range of boilers, constructed around a single and unique structure covers a wide range of powers and market segments.
Page 4
The different models: • Panther Condens 12 KKO : system boilers, 3,9 to 12 kW in heating* , for DHW preparation 4,1 to 12,3 kW; • Panther Condens 25 KKO : system boilers, 5,9 to 24,5 kW in heating* , for DHW preparation 6,1 to 30,6 kW;...
Page 5
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Hydraulic description of Panther Condens combi (25 KKV) Pressure relief valve Cold water filter...
Page 6
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Hydraulic operation of Panther Condens Hydraulic diagram in heating Hydraulic diagram in hot water...
Page 7
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Hydraulic description of Panther Condens system (12/25 KKO) Pressure relief valve By-pass...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Technical characteristics Boiler type C13, C33, C43, C53, C83 Description...
Page 9
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Technical characteristics Description Units...
Page 10
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Control panel Panther Condens Domestic hot water circuit temperature control Display...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Safety devices Flame control Thermal fuse...
Page 12
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Air/gas servo : Venturi Burner...
Page 13
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........The gas valve : Safety valves (a) Gas high flow reducer...
Page 14
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... The relation between the fan speed and the usable heating power supplied by the boiler Vmin Vmax...
Page 15
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Hydraulic unit of Panther Condens: Plate heat exchanger** Automatic air vent...
Page 16
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... The heat exchanger: Is made up of flattened stainless steel tubes in a spiral.
Page 17
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Regulation: general functions The burner can be lit following two different procedures depending on the prior condition of the unit: •...
Page 18
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Regulation: •...
Page 19
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Regulation: •...
Page 20
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Access to installer and After-Sales menus : The display has hidden menus accessible by entering a code.
Page 21
Code Parameter Units Description setting modifiable? PANTHER CONDENS 12 KKO ► 4 à 12 kW PANTHER CONDENS 25 KKV ► 5 à 18 kW d.00 Maximum heating power PANTHER CONDENS 25 KKO / 30 KKV ► 6 à 25 kW d.01...
Page 22
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Factory Parameter Code Parameter...
Page 23
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Factory Parameter Code Parameter...
Page 24
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Installer Menu: The external sensor operation Setting is done using 2 parameters: - The sensor slope to be chosen on the curve below (1):...
Page 25
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Factory Parameter Code Parameter...
Page 26
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Factory Parameter Code Parameter...
Page 27
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........The Installation and After-Sales menus by theme: read read...
Page 28
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Appliance status: This function can be used at any time to know what operating phase the appliance is in.
Page 29
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Test modes: By activating the various test modes, you can access special functions on the appliance.
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ........... Gas valve setting : combustion analyser is an essential tool for any work on the gas valve settings.
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > T e c h n i c a l S p e c i f i c a t i o n ..........Change of gas type : Prepare the appliance as for a gas valve adjustment (see previous page), without running it (start/stop button on OFF).
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Reminder of bathroom electrical protection zones This range of boilers cannot be installed in...
Page 34
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Water and gas connections: Panther Condens KKO: Domestic hot water return : 3/4’’...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Drain connections : Drain pipe Condensate trap...
Page 36
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............2 0 0 Repère Position of the exhaust end...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Exhaust connections: - If the exhaust is located within 1.80 of the ground, you must install an end protection kit.
Page 38
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Exhaust connections: Condensation flexible flue connection system (type C3S) This configuration allows reuse of an old flue or ventilation to install a...
Page 39
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Exhaust connections : Double flow ventilation system 2 x Ø...
Page 40
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Exhaust connections : Condensation flexible flue to pressurised chimney connection system (type B23P) In this configuration, the regulatory conditions relating to aeration must be complied with.
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Electrical connections : Two hatches accessible from the electrical box cover can be used to connect various components.
Page 42
> > > I n s t a l l a t i o n ..............Flow rate / pressure curve available at boiler outlet (heating side) : Panther Condens 12 KKO - 25 KKV A Pressure available between Heating flow...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > I n s t a l l a t i o n ..............Installation recommendations: Anti-corrosion and anti-sludge protection: To avoid any corrosion, it is recommended that you add a corrosion inhibitor to the heating circuit water.
Page 44
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e >...
Page 45
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e >...
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Service visit: Additional operations during five-yearly visits.
Page 47
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Fault diagnosis help: Fault Description...
Page 48
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Fault diagnosis help: Fault Description...
Page 49
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............INTERFACE User interface Fuse...
Page 50
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Panther Condens 25/30 KKV circuit diagram : INTERFACE ON / OFF...
Page 51
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Panther Condens 12/25/30 - KKO circuit diagram : ON/OFF 18 17 16 15 14 13 12 11...
Page 52
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Measurements: Thermistor characteristics (NTC2 and 5) T°C...
Page 53
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Measurements: Gas valve: Resistance of servo...
Page 54
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Dismantling / reassembling Removal of the front Front panel...
Page 55
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > M a i n t e n a n c e ..............Dismantling / reassembling Access to the hot water filter The domestic water filter is directly attached to the flow sensor.
Page 56
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e >...
Page 57
(5) --> this menu is used to associate the outside wireless sensor with the room thermostat. All the other thermostats in the Protherm range are compatible with Panther Condens : --> all ON / OFF or time-proportional thermostats -->...
Page 58
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > A c c e s s o i r e s ..............Thermolink LUX: user menu.
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > A c c e s s o i r e s ..............Thermolink LUX: installer menu.
Page 60
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > A c c e s s o i r e s ..............Wireless external sensor (ref.
Page 61
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > A c c e s s o i r e s ..............Option card (ref.
Page 62
F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e > > > A c c e s s o i r e s ..............Tank thermistor (ref.
Page 63
Appliance interface settings : F o r m a t i o n T e c h n i q u e F o r m a t i o n T e c h n i q u e Installer / service menu =>...
Page 64
Suivi des modifications du document : Version Date Modification...