Page 2
ENGLISH Thank you for choosing Delta’s DVP series PLC. DVP02DA-E2 (DVP04DA-E2) analog output module receives 2 (4) groups of 16-bit digital data from the PLC MPU and converts the digital data into 2 (4) points analog output signals (voltage or current). In...
Control Register Attrib. Register name Explanation Set up by the system, model code: Model name DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081 Firmware version Display the current firmware version in hex. Output mode: Default = H’0000. O R/W CH1 output mode setting Take CH1 for example: Mode 0 (H’0000): Voltage output ( 10V)
Page 5
Attrib. Register name Explanation Function: Set value changing Prohibit set value changing in CH1 ~ CH4. O R/W prohibited Default= H’0000. Function: Save all the set X R/W Save all the set values. Default =H’0000. values Function: Return to default Set all values to default setting.
Page 6
You can apply MOV instruction to operate values in D9900~D9999. When ES2 MPU is connected with DVP02DA-E2/DVP04DA-E2, the configuration of special registers is as below: Module Module Module Module Module Module Module Module Description...
Page 7
Mode 0 (CR#2 ~ CR#5) -10V ~ +10V Gain = 5V (16,000) Offset = 0V (0) Range of digital data -32,000 ~ +32,000 Max./Min. range of digital data -32,768 ~ +32,767 Current output – mode 1: 20mA Gain Current output 10mA +32767 +16000...
Page 8
DVP02DA-E2 DVP04DA-E2 FROM / TO D9900 ~ D9999 DVP-ES2 (OPEN TYPE) ⁄ ⁄ D->A 02DA-E2 2A O (35mm) Figure2 -10V~+10V 0mA~20mA +15V DC/DC DC24V -15V - 7 -...