, INC. ® If REMBE has not checked the sizing and positioning of the Q-Box II LF, the customer and/or installing contractor has to ensure correct and sufficient design and installation. Venting into explosion hazard area is not allowed. The ratio of the room volume where the vented vessel is located to the vented vessel volume has to be 15:1.
Page 3
The Q-Box II LF safety zone of 5 m (16.5ft) must be marked in the venting direction. This zone shall not be entered during operation of the system. The safety zone can be reduced to 0.5 m (1.65 ft) on the sides and by protection shields or similar means. The use of this equipment ®...
Page 4
Q-Box Side view Safety zone 5 m (16.5 ft) Safety zone in case of installation close to the ground 4 / 7 USB-QBII-LF-11807/0...
Page 5
Compare the dimensions of the existing flange with the Q-Box II LF connection dimensions in the drawing on page 7 and 8. Clean the sealing surfaces at the mounting location and the gasket of the Q-Box II LF carefully. After positioning the Q-Box II LF tighten all studs and nuts cross-like.