This version of the Installation Manual, which you may occur between structures and the building can do by contacting Clenergy Australia via and also between structures, fasteners and PV email on sales@clenergy.com.au, or contacting modules, as detailed in AS/NZS 5033: 2014.
• Some areas are designated Region B (52 m/s). Local authorities will advise if this applies in your area. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 4
Terrain Category 4 (TC4) – Terrain with numerous larger, high (10m to 30m tall) and closely-spaced buildings, such as large city centers and well-developed industrial complexes. If your installation site is not at TC 2, 2.5 or 3, please contact Clenergy to obtain a project specific engineering certificate to support your installation.
Page 5
30-60° adjutable tilt legs is certified for reverse tilt installation on the south facing roof. Please refer to Certification Letter and Tilt Legs Spacing Table. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 6
0.2 × length of the building and 0.2 × width of the building Step 5: The lowest value in step 4, equates to a. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 7
2. Rear leg adjustable range: ER-TL-10/15: 260-375 mm; ER-TL-15/30: 390-635 mm; ER-TL-30/60: 675-1205 3. If the info. is different from the table and diagram, it could have different results. Please contact the Clenergy to confirm its applicability. page of 55...
Page 8
Planning page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 9
Planning page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 10
Planning page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 11
Planning (10) page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 12
Planning (11) (12) page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 13
Planning (13) (14) page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 14
Planning (15) page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
③ Grounding Clip ④ ECO Rail ⑤ Grounding Lug ⑥ Adjustable Tilt Legs with L-feet page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 17
(4) In some cases, fasteners could be seized over time. As an option, if want to avoid galling or seizing of thread, apply lubricant (grease or 40# engine oil) to fasteners prior to tightening. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 18
Please refer to safe torques defined in this guide as shown in the figure below. If power tools are required, Clenergy recommends the use of low speed only. High speed and impact drivers increase the risk of bolt galling (deadlock). If deadlock occurs and you need to cut fasteners, please make sure that there is no load on the fastener before you cut it.
Figure 2 Front Leg Installation with Single Screw Figure 3 Tin Foot Front Leg Installation page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 20
Figure 6 Non-preassembly Rear Leg Installation with Single Screw Figure 7 Preassembly Rear Leg Installation with Two Screws page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 21
FREQUENT RAIN SHOULD BE WASHED DOWN WITH FRESH WATER AT LEAST EVERY 6 MONTHS TO MEET THE WARRANTY CONDITIONS OF BUILDEX SCREWS. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 22
Figure 13, 14 and 15. Recommended torque for M8 bolts is 16~20 N·m Figure 13 Figure 14 Figure 15 page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 23
End Clamps. Then fasten lightly with Figure 19 the Allen Key as shown in Figure 19 and 20. Figure 20 page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 25
The recommend torque for Universal Clamps in the End Clamp position is 13~14N·m. The recommend torque for Universal Clamps in the Inter Clamp position is 16~20N·m. page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 26
Fix the Grounding Lug at the side channel of Rail as shown in the figure on the right. Figure 33 page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Clenergy’s written installation instructions, or if the Product has been modified, repaired, or reworked in a manner not previously authorized by Clenergy IN WRITING, or if the Product is installed in an environment for which it was not designed. Clenergy shall not be liable for consequential, contingent or incidental damages arising out of the use of the Product by Purchaser under any circumstances.
Certification Letter and Tilt Legs Spacing Table (Two Screws) page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 29
SolarRoof Adjustable Tilt Legs installation within Australia. The design check has been based on the information in the PV-ezRack SolarRoof Adjustable Tilt Legs_Code Compilant Installation Guide_AU_V3.3 and schematic drawings of the system components by Clenergy (Xiamen) Technology Co. Ltd, provided by Clenergy Australia.
Page 30
According to AS 1170.2011 for all wind regions with ECO-Rails Within Australia Terrain Category 2 For: Clenergy Australia Job Number: 2078 Date: 25 February 2016 COPYRIGHT: The concepts and information contained in this document are the property of Gamcorp (Melbourne) Pty Ltd.
Page 31
Fax: 03 9802 9125 melbourne@gamcorp.com.au Client Name www.gamcorp.com.au ISO 9001:2008 Registered Firm Certificate No: AU1222 Job No: 2078 Client: Clenergy Australia Project: PV-ezRack ® SolarRoof Adjustable Tilt Legs Spacing Table Address: Within Australia Australian Standards AS 1170. 2011 – Structural Design Actions Part 0 –...
Page 32
Client: Clenergy Australia Job: 2078 Project: Date: PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Feb-16 Address: Within Australia Designed: M.A REV K PV-ezRack ® SolarRoof Frame spacing Table for Adjustable Tilt Leg Type of Rail ER-R-ECO Type of Interface...
Page 33
Client: Clenergy Australia Job: 2078 Project: Date: PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Feb-16 Address: Within Australia Designed: REV K PV-ezRack ® SolarRoof Frame spacing Table for Adjustable Reverse Tilt Leg Type of Rail ER-R-ECO Type of Interface...
Page 34
Client: Clenergy Australia Job: 2078 Project: PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Date: Feb-16 Address: Within Australia Designed: REV K General Notes Note 1 Screws minimum embedment length into timber 35 mm Note 2 Recommended screws Metal Purlins/Battens Fasteners to use 0.55 mm –...
Page 35
According to AS 1170.2011 for all wind regions with ECO-Rails Within Australia Terrain Category 3 For: Clenergy Australia Job Number: 2078 Date: 25 February 2016 COPYRIGHT: The concepts and information contained in this document are the property of Gamcorp (Melbourne) Pty Ltd.
Page 36
Fax: 03 9802 9125 melbourne@gamcorp.com.au Client Name www.gamcorp.com.au ISO 9001:2008 Registered Firm Certificate No: AU1222 Job No: 2078 Client: Clenergy Australia Project: PV-ezRack ® SolarRoof Adjustable Tilt Legs Spacing Table Address: Within Australia Australian Standards AS 1170. 2011 – Structural Design Actions Part 0 –...
Page 37
Client: Clenergy Australia Job: 2078 PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Project: Date: Feb-16 Address: Within Australia Designed: REV K PV-ezRack ® SolarRoof Frame spacing Table for Adjustable Tilt Leg Type of Rail ER-R-ECO Type of Interface ER-TL (Adjustable Tilt Leg)
Page 38
Client: Clenergy Australia Job: 2078 PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Project: Date: Feb-16 Address: Within Australia Designed: REV K PV-ezRack ® SolarRoof Frame spacing Table for Adjustable Reverse Tilt Leg Type of Rail ER-R-ECO Type of Interface...
Page 39
Client: Clenergy Australia Job: 2078 PV-ezRack ® SolarRoof Adjust. Tilt Legs Spacing Table Project: Date: Feb-16 Address: Within Australia Designed: REV K General Notes Note 1 Screws minimum embedding length into timber 35 mm Note 2 Recommended screws Metal Purlins/Battens Fasteners to use 0.55 mm –...
Page 40
Gamcorp (Melbourne) Pty Ltd A.C.N 141 076 904 A.B.N 73 015 060 240 www.gamcorp.com.au melbourne@gamcorp.com.au Suite 4, 346 Ferntree Gully Rd, Notting Hill VIC 3168 Tel: 03 9543 2211 Fax: 03 9543 4046 Definition of Roof Zones 1. For flush mounted systems installed on a pitched roof Conditions: a.
Page 41
Gamcorp (Melbourne) Pty Ltd A.C.N 141 076 904 A.B.N 73 015 060 240 www.gamcorp.com.au melbourne@gamcorp.com.au Suite 4, 346 Ferntree Gully Rd, Notting Hill VIC 3168 Tel: 03 9543 2211 Fax: 03 9543 4046 2. For flush mounted systems installed on a pitched roof Conditions: a.
Page 42
Gamcorp (Melbourne) Pty Ltd A.C.N 141 076 904 A.B.N 73 015 060 240 www.gamcorp.com.au melbourne@gamcorp.com.au Suite 4, 346 Ferntree Gully Rd, Notting Hill VIC 3168 Tel: 03 9543 2211 Fax: 03 9543 4046 3. For tilt array systems Condition: a. For pitched roofs where roof angle is between 1˚ and 45˚. In the front figure h= height, b =width and d= length of the building.
Certification Letter and Tilt Legs Spacing Table (One Screw) page page of 55 Unit 1, 10 Duerdin St, Clayton VIC 3168, Australia Tel: +61 3 9239 8088 Fax: +61 3 9239 8024 E-mail: tech@clenergy.com.au www.clenergy.com.au...
Page 44
Building Regulations, have carried out a structural design check of PV-ezRack ® SolarRoof Adjustable Tilt Legs installation within Australia and New Zealand. The design check has been based on the information in the PV-ezRack SolarRoof Adjustable Tilt Legs_Code Compilant Installation Guide_AU_V3.3 and schematic drawings and test reports of the system components by Clenergy (Xiamen) Technology Co.
Page 45
Gamcorp (Melbourne) Pty Ltd A.C.N 141 076 904 A.B.N 73 015 060 240 www.gamcorp.com.au Email: melbourne@gamcorp.com.au Suite 4, 346 Ferntree Gully Rd, Notting Hill VIC 3149. Tel: 03 9543 2211 Fax: 03 9543 4046 The certification excludes assessment of roof structure and PV panels •...
Page 46
Consulting Structural & Civil Engineers A.C.N 141 076 904 A.B.N 73 015 060 240 www.gamcorp.com.au melbourne@gamcorp.com.au Structural Design Documentation PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table According to AS 1170.2-2011 Amdt 3-2013 With ECO-Rail Within Australia & New Zealand Terrain Category 2&3 For:...
Page 47
Certificate No: AU1222 Job No: 2597 Client: Clenergy Australia Project: PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Address: Within Australia & New Zealand Australian Standards AS/NZS 1170. 2011 – Structural Design Actions Part 0 – General Principles Part 1 – Permanent imposed and other actions Part 2 –...
Page 48
2597 Clenergy Australia Client: Job: Date: Aug-16 PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Project: Within Australia & New Zealand Address: Designed: Checked: PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 1.67m x 1m...
Page 49
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 1.67m x 1m Terrain category Tilt Angle to Roof 31° -60° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 50
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 1.67m x 1m Terrain category Tilt Angle to Roof 10° -15° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 51
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 1.67m x 1m Terrain category Tilt Angle to Roof 31° -60° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 52
2597 Clenergy Australia Client: Job: Date: Aug-16 PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Project: Within Australia & New Zealand Address: Designed: Checked: PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60...
Page 53
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 2m x 1m Terrain category Tilt Angle to Roof 31° -60° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 54
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 2m x 1m Terrain category Tilt Angle to Roof 10° -15° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 55
PV-ezRack SolarRoof Adjustable Tilt Legs Spacing Table Type of Rail ER-R-ECO Type of Interface ER-TL-10/15, ER-TL-15/30, ER-TL-30/60 Solar Panel Dimension 2m x 1m Terrain category Tilt Angle to Roof 31° -60° Roof Angle (Φ) – ≤10° Building Height – H (m)
Page 56
General Notes Note 1 Screws minimum embedment length into timber 35 mm Note 2 Recommended screws Metal Purlins/Battens Fasteners to use 0.55 mm – 1.5 mm M6-11 TPI RoofZips 1.9 mm M6-11 TPI RoofZips OR 14g-10 TPI Teks screws 2.4 mm and Above 14g-10 TPI Teks screws Wood purlins and Rafter Fasteners to use...