Installing User Interfaces - Philips dynalite Installation Manual

Hide thumbs Also See for dynalite:
Table of Contents

Advertisement

Installing user interfaces

1.
All devices come with three barcode labels, one on the device, and two extras, one for the plan and one
for site documentation.
2.
Follow device Installation Instructions to select appropriate physical placement of user interfaces.
3.
Take care not to damage the wall surface surrounding the user interface particularly when it has the light
wash feature.
4.
All devices must be level and mounted consistently (vertically or horizontally) using the screws provided.
A wall box may be required to comply with local electrical standards. The mounting plate must sit flat
onto the wall surface.
5.
Where panels and buttons are engraved, check all labels are in the correct position before clipping into
position.
6.
Antumbra and touchscreen sensor holes must be positioned at the bottom of the device. Devices have
arrows to show correct orientation.
7.
Antumbra panels should have 30 cm (12 in) clearance from any metal objects or nearby cables (mains
and data). Unearthed nearby metal objects such as stud work and door frames, may lead to false
triggering of the proximity sensor. Ensure wall box and mounting plate are earthed according to the
supplied installation instructions.
8.
For all user interfaces, the cable should exit towards the bottom of the panel.
9.
Touchscreens require an external power supply.
Antumbra
14
th
November 2019
Touchscreen
Dynalite Hardware
.......................................
Installation Guide
.......................................
Page 10
.......................................
www.philips.com/dynalite

Hide quick links: