PID Control Block Layout
Table 9.2 Control Block Structure
15
14
Word 0
EN
(1)
RA
Word 1
PID Sub Error Code (MSbyte)
Word 2
Setpoint SP
Word 3
Gain K
c
Word 4
Reset T
i
Word 5
Rate T
d
Word 6
Feed Forward/Bias
Word 7
Setpoint Max (SMax)
Word 8
Setpoint Min (SMin)
Word 9
Deadband
Word 10
Internal Use Do Not Change
Word 11
Output Max
Word 12
Output Min
Word 13
Loop Update
Word 14
Scaled Process Variable
Word 15
Scaled Error SE
Word 16
Output CV% (0 to 100%)
Word 17
MSW Integral Sum
Word 18
LSW Integral Sum
Word 19
Internal Use Do Not Change
Word 20
Internal Use Do Not Change
Word 21
Internal Use Do Not Change
Word 22
Internal Use Do Not Change
(1)
Applies to SLC 5/03 and higher processors with OS Series C FRN 11 and higher firmware.
(2)
Applies to the SLC 5/03 and higher processors.
(3)
You may alter the state of these values with your ladder program.
The control block length is fixed at 23 words and should be programmed as an
integer file. PID instruction flags (word 0) and other parameters are listed in
the following table.
13
12
11
10
09
DN
PV
SP
LL
UL
ATTENTION
Proportional Integral Derivative Instruction
08
07
06
05
DB
(2)
TF
SC
DA
Do not alter the state of any PID control block value unless
you fully understand its function and related effect on your
process.
Publication 1747-RM001G-EN-P - November 2008
04
03
02
01
(2)
(3)
(3)
(3)
RG
OL
CM
AM
9-5
00
(3)