Testing precautions
Once the fitting is permanently connected to the
mains supply, a commissioning discharge test as
required in AS/NZS 2293.2 must be carried out.
You will need to allow 24 hours for the battery to
fully charge prior to conducting this test,
presently (at the time of writing), the standard
requires that fittings operate in emergency mode
for a period not less than 2 hours for their
commissioning test and for not less than 90
minutes thereafter (it is required that 6 monthly
discharge tests be carried out). You will need to
keep the records for the commissioning test and
enter them into the building emergency services
logbook or via other recording methods as
allowed by AS/NZS 2293.2.
Troubleshooting guide
If you have installed and connected the fitting as per the instructions listed earlier and it does
not function correctly, use the following table as a guide to fixing the problem. Look up the
type of fault in the left column and check the possible causes from the right column.
If the fitting still does not work after checking these possible causes, contact ABB customer
service in Australia on 1800 60 20 20.
No. Fault
1
LED light source and indicating LED not lit
2
LED light source is lit but indicating LED not lit
3
LED light source does not illuminate when the test
button is pressed
4
LED light source works momentarily when the test
button is pressed
ABB Australia Pty Limited
For enquiries
ABB contact centre: 1800 60 20 20
E-mail: AU-ABB-Stanilite@abb.com
www.stanilite.com.au
Construction sites
Continuously switching off the mains power
supply that is connected to emergency light
fittings during the construction phase of an
installation will cause these fittings to discharge
and charge their batteries many times over a
short period; this can shorten life of the battery.
ABB does not recommend such practices and
may not honour the warranty on batteries when
they are subjected to such harsh operating
conditions. Emergency light fittings are designed
to be discharge tested once every 6 months as
per AS/NZS 2293.2, subjecting the product to
repeated discharge or charge cycles is regarded
as an abuse of the fittings.
Possible causes
AC supply not connected or turned off; and/or
Test switch damaged
Test switch damaged; or
Battery not connected or faulty; or
USA not connected or turned off
Test switch damaged; or
Battery not connected or faulty
Battery not yet charged (allow up to 24 hours)
© Copyright 2020 ABB. All rights reserved.
I N S TA L L AT I O N M A N U A L
Stanilite®
Economy e-Luna circular LED
AC, emergency
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. Contact ABB customer service in
Australia on 1800 60 20 20 if you need any
assistance. The installation instructions were
correct at the time of print. To reflect changes in
technology and Australian standards; ABB
reserves the right to amend the instructions
without notice. Updated document can be found
on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with
240 volt electrical installations.
Do not attempt to install or connect this product
unless you are a licensed electrician.
Turn off and isolate the electrical supply before
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block
when the light fitting is energised.
The only user-serviceable part is the battery
pack. LED light source is not user-serviceable.
Do not attempt to service other parts of the
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure
compliance with all relevant building and safety
This document covers
What's inside the box
Safety warning
Economy e-Luna circular
Installation instructions
Masonry wall plugs and
Removal instructions
Installation manual
Testing precautions
Warranty information
Troubleshooting guide
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for data and mains
cabling installation procedures and
requirements.
Important to note:
• This product is designed for indoor use only.
Maintenance
1. Turn off the main power before doing any
maintenance.
2. Do not touch LEDs while maintaining or
cleaning.
3. Do not use chemicals to clean the fixture.
Environmental protection; waste electrical
products should not be disposed of with
household waste. Please recycle where facilities
exist. Check with your local authority or retailer for
recycling advise.
Doc no. 29-HPSP001_G
LED
screws

Advertisement

loading

Summary of Contents for ABB Stanilite Economy e-Luna circular LED

  • Page 1 (ie: AS/NZS 3000, AS/NZS 2293). Refer to the applicable standards for data and mains commencing installation and retain for future If the fitting still does not work after checking these possible causes, contact ABB customer reference. Contact ABB customer service in cabling installation procedures and service in Australia on 1800 60 20 20.
  • Page 2 Installation instructions 1. Twist the diffuser in the anti-clockwise direction and remove it, see figure 1. Motion detect sensor - settings 2. Route the mains cable through the cable entry hole, see figure 2. 3. Secure the base onto the ceiling or wall using the wall plugs and screws supplied or use appropriate Detection area fixings to suit the type of building construction material, see figure 3.